PEAK PROFESSIONAL CONTRS INC | B= | C | 07/21/2016 | All other required Final inspections are complete. (This is a computer generated result) | DANE | DANE | | B= | C | 5250294 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 07/12/2016 | items corrected. Additional Inspections Required (computer generated): NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5242959 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 07/08/2016 | Temp CO: Fire, Mechanical and Bldg finals pending ( Expires: 8/7/2016 12:00:00 AM) | MINDY | MINDY | | B= | P | 5240718 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 07/08/2016 | still need to make curb under storefront weather resistant / still need to remove temporary wall in front of storefront -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5240688 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 07/05/2016 | post address / complete storefront / remove temp wall at front of store / make front wall weather resistant / need fire final / need M= / bathrooms pre-existing -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5236981 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 07/05/2016 | need to complete storefront at front door / all other framing complete | DANE | DANE | | BFR | P | 5236976 |
NIELSEN MECHANICAL CONTRACTORS, INC. | BSP | T | 06/24/2016 | PAID (REC#1337583) PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical | JUSTINC | JUSTINC | | BSP | T | 5230297 |
PEAK PROFESSIONAL CONTRS INC | BSP | T | 06/06/2016 | PAID (REC#1333554) PLAN SPLICE FEE: $50 by: JIMA for Construction: splice chnaged wall types ( clouded areas only ) | JIMA | JIMA | | BSP | T | 5215268 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 06/03/2016 | hard lid at front of sales area now OK pending other rough inspections / plans spliced in to remove U419 from plans but wall type 4 still calls 2 layers of 5/8" rock and only one has been installed at all areas that call for wall type 4 | DANE | DANE | | BFR | P | 5214542 |
PEAK PROFESSIONAL CONTRS INC | BSP | T | 06/03/2016 | PAID (REC#1333229) PLAN SPLICE FEE: $50 by: JIMA for Construction: splice removed rated walls ( not required ) | JIMA | JIMA | | BSP | T | 5214001 |
PEAK PROFESSIONAL CONTRS INC | BFR | R | 06/01/2016 | lower dropped ceiling at front of unit needs to be tied up to the structure above per plan / still need to change the unit separation wall rating and need to change and splice into plans changes at rear of unit ./ Training with Matt M | DANE | DANE | | BFR | R | 5212202 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 05/19/2016 | storage room demising wall OK pending other roughs / upper hard lid at front of store OK pending other roughs / columns in middle of floors OK pending other roughs / unit separation walls are called out on plans as rated UL 419 walls and need to be removed from plans if not needed / bathrooms not in scope of work on plans | DANE | DANE | | BFR | P | 5202963 |
EL PASO ELECTRIC, LLC. | BSP | T | 05/16/2016 | PAID (REC#1329810) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Added Key Plan showing electrical service location. Added note indicating "New service disonnect must be grouped with existing service disconnects." | BERTHA | BERTHA | | BSP | T | 5200409 |
PEAK PROFESSIONAL CONTRS INC | BFT | C | 05/10/2016 | new thickened edge curb for storefront entry OK / R10 insulation installed | DANE | DANE | | BFT | C | 5195723 |
EL PASO ELECTRIC, LLC. | E= | C | 06/30/2016 | | RANDY | RANDY | | E= | C | 5235002 |
EL PASO ELECTRIC, LLC. | ER | C | 06/30/2016 | | RANDY | RANDY | | ER | C | 5235001 |
EL PASO ELECTRIC, LLC. | ES | C | 06/30/2016 | Commercial Service: 200 AMP service no action needed | RANDY | RANDY | | ES | C | 5235000 |
EL PASO ELECTRIC, LLC. | ES | P | 06/24/2016 | Commercial Service: 200 amp service made to main disconnect only. | BRET | BRET | | ES | P | 5230473 |
EL PASO ELECTRIC, LLC. | ER | P | 06/01/2016 | hard lids in front part of store, | GARYL | GARYL | | ER | P | 5212653 |
EL PASO ELECTRIC, LLC. | ER | P | 05/26/2016 | all walls,,,,, only walls | GARYL | GARYL | | ER | P | 5209309 |
EL PASO ELECTRIC, LLC. | ER | R | 05/13/2016 | rough not ready | BRET | BRET | | ER | R | 5198975 |
EL PASO ELECTRIC, LLC. | ESL | P | 05/12/2016 | 2 cut outs in slap,,,,, | GARYL | GARYL | | ESL | P | 5198278 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | C | 07/21/2016 | MECHANICAL FINAL OK. REVISED TEST AND BALANCE REPORT AND ENGINEER LETTER APPROVING REPORT RECEIVED. | NANCY | NANCY | | H= | C | 5250293 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 07/11/2016 | TEST AND BALANCE REPORT RECEIVED. OUTSIDE AIR READING OUTSIDE OF THE +/- 10% ALLOWED. PROVIDE REVISED BALANCE REPORT OR LETTER FROM ENGINEER APPROVING THIS READING. | NANCY | NANCY | | H= | P | 5241644 |
ARTISAN PIPE SYSTEMS, INC. | H= | C | 07/01/2016 | GAS FINAL OK. | NANCY | NANCY | | H= | C | 5236608 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 06/27/2016 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5231893 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 06/21/2016 | PROVIDE FURNACE INSTALLATION INSTRUCTIONS TO VERIFY VENT SIZING. NEED ACCESS TO ROOF TO SEE VENT TERMINATION. NEED REVISED/APPROVED PRINTS FOR EF-1 AND SUPPLY IN CORRIDOR. SUPPLY/RETURN DUCTS OK. | NANCY | NANCY | | HD | P | 5227492 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | L | 06/17/2016 | FRONT AND BACK DOORS LOCKED AT 3:45 PM. | NANCY | NANCY | | HD | L | 5225427 |
ARTISAN PIPE SYSTEMS, INC. | HC | C | 05/24/2016 | OK TO SET METER FOR UNIT 443 | NANCY | NANCY | | HC | C | 5207446 |
ARTISAN PIPE SYSTEMS, INC. | HI | C | 05/24/2016 | FOR ALL FUTURE GAS TESTS NEED A 10 LB TEST ON A 30 LB GAUGE NOT A 60 LB GAUGE. 10 LB TEST OK. INSTALLED AS PER PRINTS EXCEPT MAIN LINE IS 1 1/4 INCH NOT 1 INCH. | NANCY | NANCY | | HI | C | 5207445 |
ARTISAN PIPE SYSTEMS, INC. | P= | C | 07/01/2016 | | TAYLOR | TAYLOR | | P= | C | 5236551 |
ARTISAN PIPE SYSTEMS, INC. | PTO | C | 05/13/2016 | WH PAN TO DRAIN TO MOP SINK , ALL TO PLAN | GABE | GABE | | PTO | C | 5198695 |
ARTISAN PIPE SYSTEMS, INC. | PB | C | 05/10/2016 | NOTE : BASE TO PLAN , OK TO COVER | GABE | GABE | | PB | C | 5196203 |