STAN LEWIS, INC | B= | C | 09/09/2016 | Corrections from previous final complete | JEREMYA | JEREMYA | | B= | C | 5288888 |
STAN LEWIS, INC | BSP | T | 09/08/2016 | PAID (REC#1358498) PLAN SPLICE FEE: $50 by: DANM for Construction: Relocated mop sink and related framed plumbing wall (already finaled by plumbing inspector) | DANM | DANM | | BSP | T | 5288347 |
STAN LEWIS, INC | B= | P | 09/06/2016 | Need accessible signage at restrooms / Need pipe protection under sink / Need drawings to show sink wall / Need to remove all door knobs and replace with accessible door hardware -- Schedule a new Building Final when above items are complete. | JEREMYA | JEREMYA | | B= | P | 5285417 |
STAN LEWIS, INC | BSP | T | 08/30/2016 | PAID (REC#1356584) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Add exit signs | SHELBY | SHELBY | | BSP | T | 5281711 |
TRUSTED ELECTRIC | BSP | P | 08/17/2016 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Ballast change | BERTHA | BERTHA | | BSP | P | 5271742 |
STAN LEWIS, INC | BSP | P | 06/30/2016 | Support for new roof top unit per engineer letter | JEREMYA | JEREMYA | | BSP | P | 5234894 |
TRUSTED ELECTRIC | E= | C | 08/24/2016 | | CRAIGS | CRAIGS | | E= | C | 5276808 |
TRUSTED ELECTRIC | E= | C | 08/24/2016 | | CRAIGS | CRAIGS | | E= | C | 5276807 |
TRUSTED ELECTRIC | E= | P | 08/23/2016 | label panels -- two grounds under one lug in the roof top unit | CRAIGS | CRAIGS | | E= | P | 5275760 |
TRUSTED ELECTRIC | E= | P | 08/17/2016 | ballast's in the flower room dont match the drawings --- need to inspect the panel -- roof top units for the flower room | CRAIGS | CRAIGS | | E= | P | 5271270 |
TRUSTED ELECTRIC | ER | C | 08/17/2016 | flower room only | CRAIGS | CRAIGS | | ER | C | 5271264 |
TRUSTED ELECTRIC | ER | P | 07/13/2016 | north rows of lights by the drive thru door ---OK | CRAIGS | CRAIGS | | ER | P | 5243698 |
ADVANTAGE HEATING AND COOLING | H= | C | 08/24/2016 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 5277517 |
ADVANTAGE HEATING AND COOLING | H= | C | 08/23/2016 | TAB REPORT RECEIVED - ALL OK | JERRYF | JERRYF | | H= | C | 5275858 |
ADVANTAGE HEATING AND COOLING | H= | P | 08/17/2016 | NEED OSA READINGS FOR BOTH UNITS LISTED ON TAB REPORT | JERRYF | JERRYF | | H= | P | 5270869 |
ADVANTAGE HEATING AND COOLING | H= | P | 08/10/2016 | PARTIAL PENDING TAB REPORT ON DISPENSARY - REST OK | JERRYF | JERRYF | | H= | P | 5266112 |
ADVANTAGE HEATING AND COOLING | HD | C | 08/10/2016 | ABOVE CEILING OK | JERRYF | JERRYF | | HD | C | 5266111 |
ADVANTAGE HEATING AND COOLING | P= | C | 08/19/2016 | plumbing is complete . 9/8/16 laundry sink in new location was inspected on 8-19-16 | TED | TED | | P= | C | 5273178 |
ADVANTAGE HEATING AND COOLING | P= | P | 08/18/2016 | support drain and water piping to laundry sink, run condensate drain to approved location, support drain and water piping to drinking fountains, need to cap/plug unused toilet drain next to drinking fountains to code | TED | TED | | P= | P | 5272128 |
ADVANTAGE HEATING AND COOLING | PTO | C | 08/11/2016 | bathrooms remodel | TED | TED | | PTO | C | 5266761 |
ADVANTAGE HEATING AND COOLING | P= | T | 08/10/2016 | PAID (REC#1348720) not ready | TED | TED | | P= | T | 5265671 |
ADVANTAGE HEATING AND COOLING | P= | T | 08/09/2016 | PAID (REC#1348313) not ready, plumbing have been removed completely, it looks like the plumber is starting over, will need new pto and test on it, drinking fountains need to be plumbed to code | TED | TED | | P= | T | 5264587 |
ADVANTAGE HEATING AND COOLING | P= | R | 08/05/2016 | see pto note | TED | TED | | P= | R | 5262534 |
ADVANTAGE HEATING AND COOLING | PTO | R | 08/05/2016 | remove covers on drinking fountains, looks like 2 traps on on trap arm, need 60'' from toilet side wall to edge of lavs, one bathroom has exposed piping on the wall next to the toilet, install vacuum breakes on hose bibbs, | TED | TED | | PTO | R | 5262533 |
ADVANTAGE HEATING AND COOLING | PB | C | 07/06/2016 | bathrooms toilet base ok | TED | TED | | PB | C | 5237901 |
ADVANTAGE HEATING AND COOLING | PB | R | 07/05/2016 | sent call ahead 8:55, no access building locked, contact person no show 9:35 | TED | TED | | PB | R | 5236892 |