HENSEL PHELPS CONSTRUCTION CO | B= | C | 11/17/2017 | Variance for sink/counter height on file | RICHB | RICHB | | B= | C | 5688365 |
HENSEL PHELPS CONSTRUCTION CO | BE | L | 11/16/2017 | Renewed at 11/16/2017 3:24:18 PM | TERRI | TERRI | | BE | L | 5688032 |
HENSEL PHELPS CONSTRUCTION CO | B= | P | 09/08/2016 | Still need to lower sink in work area to 34" max, 36 1/2" at time of inspection / All other items complete -- Schedule a new Building Final when above items are complete. | NICK | NICK | | B= | P | 5287754 |
HENSEL PHELPS CONSTRUCTION CO | B= | R | 09/06/2016 | standard roll in shower-grab bars locations not correct in length-not 6" from corners,missing a total of 3 grab bars without the seat,plans show a seat which is not installed,revise plans to remove seat,if seat is installed the hand shower may not be compliant from end wall dimension, soap dish within 12" above grab bars not allowed/sink in work area is 36 1/2" high where 34" is max,install smoke seal astregal @ doors in smoke barrier | BERTW | BERTW | | B= | R | 5285996 |
HENSEL PHELPS CONSTRUCTION CO | BFR | C | 09/06/2016 | | BERTW | BERTW | | BFR | C | 5285851 |
HENSEL PHELPS CONSTRUCTION CO | BSP | P | 08/17/2016 | fire caulking ok | BERTW | BERTW | | BSP | P | 5271535 |
HENSEL PHELPS CONSTRUCTION CO | BFR | P | 07/28/2016 | Frame for shower walls ok / still need correct head wall detail and inspection / need to move sprinkler line out of rated wall / need UL listed through penetration for low volt over door / membrane penetration listing on file ok / Ned all MEP's complete | NICK | NICK | | BFR | P | 5256186 |
HENSEL PHELPS CONSTRUCTION CO | BSP | R | 07/27/2016 | head wall detail on site was for a concrete floor above and wall is stopping at a fluted metal roof above - need a new head wall detail / wall membrane penetrations in smoke barrier need a listing that matches the conditions on site - listing on site was for multiple electrical through penetrations / all above ceiling multiple electrical conduit penetrations are OK | DANE | DANE | | BSP | R | 5254931 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | BSP | P | 07/26/2016 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: revised bed walls and new crash cart outlet location | SHELBY | SHELBY | | BSP | P | 5254256 |
OLSON PLUMBING & HEATING COMPANY | BSP | T | 07/18/2016 | PAID (REC#1344563) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing spice 7-18-16 | TCRIPPEN | TCRIPPEN | | BSP | T | 5247731 |
HENSEL PHELPS CONSTRUCTION CO | BFR | P | 07/14/2016 | Met on site with Tim / U404 wall listing on site, need to use US gypsum / Still need to inspect head wall for rated walls / Still need listings for all through penetrations and inspect / Putty pack installed for boxes / Ceiling framing channel supports installed / Need mechanical, plumbing, and electrical complete / Framing for notched studs OK / Still need to see framing for revised bathroom with shower | NICK | NICK | | BFR | P | 5244708 |
HENSEL PHELPS CONSTRUCTION CO | BSP | T | 07/13/2016 | PAID (REC#1344562) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Add shower - minor revisions | MICHAELA | MICHAELA | | BSP | T | 5244422 |
HENSEL PHELPS CONSTRUCTION CO | BFR | R | 07/11/2016 | met with Tim/drop ceiling framing needs channel supports to structure/all walls need UL listings on site for next inspection/need headwall details and inspections/through penetrations need listings/steel studs over notched need architects letter for new electric boxes added removed entire stud sections/reviewed putty padding boxes exceed 100 sq/in in 100 sq/ft,changed patient toilet room layout not on plans/need all plans full size and code study paperwork to do next inspection | BERTW | BERTW | | BFR | R | 5241940 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 08/25/2016 | | CRAIGS | CRAIGS | | E= | C | 5277708 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 08/24/2016 | microwave circuits have to have gfci protection -- the device can not go behind the appliance | CRAIGS | CRAIGS | | E= | P | 5276610 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 08/24/2016 | FIRE ALARM INSPECTION: 5 device letter | CRAIGS | CRAIGS | | E= | C | 5276607 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 08/15/2016 | control room above ceiling | CRAIGS | CRAIGS | | ER | P | 5268888 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 08/15/2016 | FIRE ALARM INSPECTION: control room above ceiling | CRAIGS | CRAIGS | | ER | P | 5268887 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 07/11/2016 | walls in 1708 except bathroom and shower area | CRAIGS | CRAIGS | | ER | P | 5241548 |
MECHONE, INC. | H= | C | 09/02/2016 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 5284008 |
MECHONE, INC. | H= | P | 08/26/2016 | PARTIAL PENDING TAB REPORT - ALL SA/RA AND EXHAUST GRILLES ARE COMPLETE | JERRYF | JERRYF | | H= | P | 5279512 |
MECHONE, INC. | HD | P | 08/08/2016 | ABOVE CEILING OK - AT FINAL NEED TAB AND ALL GRILLES | JERRYF | JERRYF | | HD | P | 5263500 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 09/06/2016 | bathroom | TED | TED | | P= | C | 5285970 |
OLSON PLUMBING & HEATING COMPANY | P= | R | 09/06/2016 | could not get through to call ahead number for contact person | TED | TED | | P= | R | 5285639 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 07/28/2016 | shower dwv and water ok | TED | TED | | PTO | C | 5256052 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 07/08/2016 | poha room 1704b, dwv and water for toilet, lav and sink ok, still need shower work completed | TED | TED | | PTO | P | 5240304 |