CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H02 | C | 06/19/2024 | ANNUAL 6/24 -- TKE W/ PEAK SERVICE -- / PERFORMED SIX MONTH INSPECTION TO VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION AND ELEVATOR TWO-WAY COMMUNICATION. (Receipt #2076443) | DUSTINS | DUSTINS | | H02 | C | 8122079 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H03 | C | 02/26/2024 | 30 DAY RED TAG POSTED. ELEVATOR SCHEDULED TO BE REMOVED FROM SERVICE IF DEFICIENCIES HAVE NOT BEEN ADDRESSED BY 3/26/24: DOOR RESTRICTOR ON WEST SIDE OF HOISTWAY DOES NOT ENGAGE ALLOWING CAR DOOR TO BE FULLY OPENED OUTSIDE OF LANDING ZONE. (Receipt #2037323)(mlm 3/1/24 - corrections made) moved H06 to align with H02, DS | MATTM | MATTM | | H03 | C | 8006496 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H01 | C | 12/28/2023 | ANNUAL 7/23 - TKE W/ PEAK SERVICE / 60 DAYS TO ADDRESS: NEEDS DOOR RESTRICTORS THROUGHOUT. (Receipt #2020202) | MATTM | MATTM | | H01 | C | 7955685 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H02 | C | 06/06/2023 | HO2 -- ANNUAL 7/22 -- TKE W/ PEAK SERVICE -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7764413 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H01 | C | 12/21/2022 | ANNUAL 7/22 -- TKE W/ PEAK SERVICE -- / NO MAINTENANCE TASK LOGS FOR 2022 WITHIN THE MCP / BUILDING TO KEEP MONTHLY FIREFIGHTERS’ EMERGENCY OPERATION AND QUARTERLY EMERGENCY PHONE TEST LOGS UP TO DATE (Receipt #1922368) | DUSTINS | DUSTINS | | H01 | C | 7618098 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H02 | C | 06/27/2022 | HO2 -- ANNUAL 7/21 -- TKE W/ PEAK SERVICE -- SEE PREVIOUS NOTES (cat 1 -- 7/22, check previous items at H01) | BENH | BENH | | H02 | C | 7426519 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H01 | C | 12/21/2021 | ANNUAL 07/2021-- TKE WITH PEAK SERVICE--/ MAINTENANCE CONTROL PROGRAM IS STILL NON COMPLIANT/MISSING--/ PROVIDE UP TO DATE QUARTERLY EMERGENCY PHONE LOGS AND MONTHLY FIRE EMERGENCY OPERATORS LOG--/ PROVIDE MACHINE ROOM WITH A TYPE "ABC" FIRE EXTINGUISHER (Receipt #1831376) | MIKEM | MIKEM | | H01 | C | 7217084 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H06 | C | 07/28/2021 | WITNESSED HYDRO SAFETY TESTING W/ PEAK ELEVATOR - ARRIVED AND FOUND UNIT SHUT OFF BY BUILDING ENGINEER. AFTER RESTORING POWER, FOUND DEAD AUXILIARY LOWERING BATTERY, INOPERABLE LOW-OIL PRESSURE SWITCH AND UNINTENDED MOVEMENT OF ELEVATOR CAUSING LIFE SAFETY ISSUE. UNIT WAS REMOVED FROM SERVICE AFTER TESTING PENDING REPAIRS. MAINTENANCE / EXAMINATION RECORDS ONSITE SHOW LAST RECORDING IN 2017. IT IS REQUIRED TO HAVE THE ELEVATOR TESTED AND MAINTENANCE / EXAMINATIONS PERFORMED AT MINIMUM ONCE A YEAR TO BE COMPLAINT WITH STATE STATUTES AND REGULATIONS ALONG WITH A MAINTENANCE CONTROL PROGRAM RECORDING ALL TASKS, REPAIRS, ADJUSTMENTS AND TESTING. FAILURE TO COMPLY WITH THESE STATUTES AND REGULATIONS WILL RESULT IN THE ELEVATOR BEING REMOVED FROM SERVICE AT ANYTIME OF NON-COMPLIANCE. | ROBERTV | ROBERTV | | H06 | C | 7053135 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H02 | C | 06/30/2021 | H02 -- CAT1 -- 7/20 -- TKE W/ PEAK SERVICE | ROBERTV | ROBERTV | | H02 | C | 7021408 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H01 | C | 12/10/2020 | ITEMS HAVE BEEN ADDRESSED, THIS VISIT SKIPPED IN LIEU OF WITNESS TEST PERFORMED 7/2020 (Receipt #1735811) | ROBERTV | ROBERTV | | H01 | C | 6803101 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | HE16 | C | 07/17/2020 | PEAK ELEVATOR PERFORMED CATEGORY 1 ON ELEVATOR - EMERGENCY BATTERY POWERED LOWERING BY UPS IS STILL NOT WORKING............. 30 DAYS TO ADDRESS. | ROBERTV | ROBERTV | | HE16 | C | 6642021 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H02 | C | 06/30/2020 | H02 -- No access due to COVID-19, See previous inspection items - (RV: email sent to Superintendent and Dave Strehlow 6/18/2020 regarding compliance within 60 days or elevators will be removed from service) | ROBERTV | ROBERTV | | H02 | C | 6622199 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H01 | C | 12/30/2019 | RP--10--17 TKE --WAY OVERDUE CATEGORY 1 TEST MUST BE COMPLETED NOW ALSO THE UPS UNIT ON ELEVATOR EQUIPMENT IS BEEPING STILL (Receipt #1652822) | JOHNW | JOHNW | | H01 | C | 6439553 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H02 | C | 06/24/2019 | RP--10--17--TKE --CAT 1 ANNUAL EXPIRED --UPS UNIT ON ELEVATOR MACHINE BEEPING | JOHNW | JOHNW | | H02 | C | 6241027 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H01 | C | 12/28/2018 | RP--10--17--TKE --RELIEF PRESSURE TEST EXPIRED (Receipt #1566283) | JOHNW | JOHNW | | H01 | C | 6065035 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H02 | C | 06/25/2018 | RP--10--17--TKE --HO2 | JOHNW | JOHNW | | H02 | C | 5883776 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H01 | C | 12/20/2017 | RP--10--17--TKE (Receipt #1472309) | JOHNW | JOHNW | | H01 | C | 5718244 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H02 | C | 06/21/2017 | HO2 RP--7--16--TKE | JOHNW | JOHNW | | H02 | C | 5542645 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | HE16 | C | 06/02/2017 | REALIGNED INSPECTIONS | ROBERTV | ROBERTV | | HE16 | C | 5524379 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H02 | C | 12/22/2016 | RP--7--16--TKE | JOHNW | JOHNW | | H02 | C | 5375262 |
CHEYENNE MOUNTAIN SCHOOL DISTRICT 12 | H06 | C | 07/22/2016 | ACCEPTANCE AND 5 YEAR | ERIC | ERIC | | H06 | C | 5251491 |