HOMEOWNER | B= | C | 03/03/2017 | Unfinished basement -- No deck | DAKOTAB | DAKOTAB | | B= | C | 5431429 |
HOMEOWNER | BSP | T | 02/28/2017 | PAID (REC#1406528) PLAN SPLICE FEE: $50 by: DALEH for Mechanical | DALEH | DALEH | | BSP | T | 5426656 |
HOMEOWNER | BIN | C | 12/02/2016 | | BOBF | BOBF | | BIN | C | 5359565 |
HOMEOWNER | BFR | C | 12/02/2016 | | BOBF | BOBF | | BFR | C | 5359561 |
HOMEOWNER | BFR | P | 11/28/2016 | install fha straps at stud in powder and up stairs bathroom / okay to insulate | BOBF | BOBF | | BFR | P | 5354411 |
HOMEOWNER | BLA | C | 11/10/2016 | | DALE | DALE | | BLA | C | 5342142 |
HOMEOWNER | BSP | P | 11/08/2016 | narrow wall okay | BOBF | BOBF | | BSP | P | 5339576 |
HOMEOWNER | BSP | P | 11/04/2016 | Detail calls for panel splice to be with 24" of mid-height of wall at narrow braced wall | DAKOTAB | DAKOTAB | | BSP | P | 5336887 |
HOMEOWNER | BSP | R | 10/27/2016 | garage portal wall not framed or nailed per detail 4-S6 / rest of exterior shear okay / front porch with posts okay | BOBF | BOBF | | BSP | R | 5330114 |
HOMEOWNER | BFN | C | 10/20/2016 | Engineer letter of observation for foundation on file -- Eufer noted -- Engineer letter for pad J and H on file -- Foundation design in house plan set | DAKOTAB | DAKOTAB | | BFN | C | 5323166 |
HOMEOWNER | BFT | C | 10/20/2016 | Engineer letter of observation for footing on file -- Engineer letter on file for pads J and H -- Open hole on file -- 2000 PSF - Drain usable - 10% | DAKOTAB | DAKOTAB | | BFT | C | 5323162 |
HOMEOWNER | BFD | C | 09/16/2016 | soils report on file, okay to backfill | BOBF | BOBF | | BFD | C | 5294966 |
HOMEOWNER | BFD | R | 09/15/2016 | need open hole and soils to verify drain requirements | BOBF | BOBF | | BFD | R | 5294433 |
HOMEOWNER | BFI | P | 09/15/2016 | basement is not a walkout, foundation insulation not required | BOBF | BOBF | | BFI | P | 5294432 |
HOMEOWNER | BFT | R | 09/15/2016 | no paperwork uploaded or on site / need open hole, spois, foundation design and eng letter for footing | BOBF | BOBF | | BFT | R | 5294430 |
HOMEOWNER | BFN | R | 09/15/2016 | no paper work uploaded or on site / need eng letter for steel and eufer | BOBF | BOBF | | BFN | R | 5294429 |
HOMEOWNER | BFN | P | 08/25/2016 | ok to use engineer to do inspections with observation letters to follow | BERTW | BERTW | | BFN | P | 5278527 |
HOMEOWNER | BFT | P | 08/25/2016 | ok to use engineer to do inspections with observation letters to follow | BERTW | BERTW | | BFT | P | 5278523 |
HERRON ELECTRIC COMPANY | E= | C | 03/03/2017 | | BRET | BRET | | E= | C | 5431414 |
HERRON ELECTRIC COMPANY | E= | R | 03/02/2017 | ground bar in future hot tub disconnect not bonded to can. remove nm cable from a/c whips not approved for wet location., install wire nuts on neutral conductors in a/c disconnects. gfci receptacle cannot be located in ceiling above water heaters (not readily accessible). breaker lock for oven unit must be molded to breaker or attach to dead front. | BRET | BRET | | E= | R | 5430191 |
HERRON ELECTRIC COMPANY | ES | C | 03/02/2017 | Residential Underground: 200 amp service new res. | BRET | BRET | | ES | C | 5430173 |
HERRON ELECTRIC COMPANY | ES | R | 02/28/2017 | clear area around panel so I can safely open up energized panels. | BRET | BRET | | ES | R | 5427502 |
HERRON ELECTRIC COMPANY | E= | R | 02/28/2017 | install w/r receptacles exterior(currently t/r), neutral conductor used as ground conductor in a/c and hot tub disconnects. ( hot tub pre-wire only). island receptacles do not meet code requirement with 10" overhang of counter top. gfci required for dishwasher and washer use afci/gfci breakers.missing receptacle main n.e bedroom switch wall. breaker lock for oven unit. gfci all 120 volt receptacle in unfinished basement (above w.h and at crawl access. | BRET | BRET | | E= | R | 5427492 |
HERRON ELECTRIC COMPANY | ER | C | 11/21/2016 | have access to wiring at hood open at time of final | BRET | BRET | | ER | C | 5350521 |
HERRON ELECTRIC COMPANY | ER | R | 11/17/2016 | install ground screws in exterior pan boxes, verify mud room outlet is not on dedicated garage circuit, land homeruns in panel, attach to ufer, install kitchen ex-fan, correct spacing in master bed room and bedroom that over looks front door, trim attic, wirenut grounds in master closet light, run power for sump-------- unfinished basement, no vac, verify rest on re-inspect | MATTHEW | MATTHEW | | ER | R | 5347830 |
HERRON ELECTRIC COMPANY | EUG | C | 11/10/2016 | 4/0al from pole to house ok | MATTHEW | MATTHEW | | EUG | C | 5342092 |
HERRON ELECTRIC COMPANY | ER | P | 11/10/2016 | front exterior patio cover ok | MATTHEW | MATTHEW | | ER | P | 5342074 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | H= | C | 03/02/2017 | Correction made. | JEFFL | JEFFL | | H= | C | 5430061 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | H= | R | 03/01/2017 | Return air still needs moved 10' from indirect furnace. Rest ok. | JEFFL | JEFFL | | H= | R | 5428920 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | H= | P | 02/21/2017 | Need plan splice showing 90% furnaces installed and sizes. Need plan splice showing garage as heated. Furnace for main floor leaking condensate out of vent at furnace. Move return air in basement 10' furnace. Note: No fireplace mantel and 2 A/C installed | MARKB | MARKB | | H= | P | 5420882 |
L & L GAS SHOP, LLC. | HC | C | 11/09/2016 | RELEASE METER | MARK | MARK | | HC | C | 5340466 |
L & L GAS SHOP, LLC. | HI | C | 11/09/2016 | 10 lb test ok. Note: 1 1/2 Main w/ meter at house. 2- furnaces, 2- water heaters, cook top, fireplace, future garage heat, future bbq. | MARK | MARK | | HI | C | 5340465 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | HRR | C | 11/07/2016 | Corrections made. | MICHAELS | MICHAELS | | HRR | C | 5338375 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | HRR | P | 11/04/2016 | Missing heat run to craft room, laundry vent dropped below roof deck. Equipment change letter or correct equipment by final. Note: Unfinished basement, 2- a/c coil and line sets, 2- 6" outside air, 2- non direct vent furnaces. | MARK | MARK | | HRR | P | 5336683 |
AFAB PLUMBING LLC | P= | C | 03/02/2017 | certificate of potable water to scanning | TED | TED | | P= | C | 5429163 |
AFAB PLUMBING LLC | P= | P | 03/01/2017 | need certificate of potable water, rest ok, unfinished basement, 3/4 pvb installed | TED | TED | | P= | P | 5428659 |
TRADITIONAL PLUMBING AND HEATING LLC | PTO | C | 11/21/2016 | unfinished basement, aav basement bathroom group at final, check tempering valve master tub at final | TED | TED | | PTO | C | 5349757 |
HOMEOWNER | PWO | C | 10/19/2016 | H2O SLEEVED THROUGH FOUNDATION | GABE | GABE | | PWO | C | 5322732 |
TRADITIONAL PLUMBING AND HEATING LLC | PB | C | 09/26/2016 | | TIM | TIM | | PB | C | 5302535 |