HOMEOWNER | B= | C | 11/29/2016 | All other required Final inspections are complete. (This is a computer generated result) | BOBF | BOBF | | B= | C | 5355640 |
HOMEOWNER | B= | P | 11/22/2016 | . Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | BOBF | BOBF | | B= | P | 5352020 |
HOMEOWNER | BSP | P | 11/21/2016 | eng. for sono-tubes full 30" | DALE | DALE | | BSP | P | 5349397 |
HOMEOWNER | BFR | C | 11/18/2016 | Engineer letter received for piers and beam pocket | DAKOTAB | DAKOTAB | | BFR | C | 5349098 |
HOMEOWNER | BSP | R | 11/17/2016 | sonotube is installed the entire length of piers / sonotube is only allowed at the upper 10" max of the pier / okay to provide engineering letter for piers completed prior to inspection | BRIANB | BRIANB | | BSP | R | 5347902 |
HOMEOWNER | BSP | P | 11/17/2016 | PLAN SPLICE: (No Fee) by: SHELLEY for Construction: clarified window headers and beam support | SHELLEY | SHELLEY | | BSP | P | 5347344 |
HOMEOWNER | BFR | R | 11/15/2016 | missing stamped engineering design for exterior garden level wall framing and window headers / need to revise plans to reflect as built condition - approved plans show finished basement - basement to remain unfinished / if building garage will need approved design for garage as well / went over plans with the homeowner / no inspection done | BRIANB | BRIANB | | BFR | R | 5344787 |
HOMEOWNER | BSP | P | 11/07/2016 | deck piers not inspected, dig down along side to verify depth | DALE | DALE | | BSP | P | 5338131 |
HOMEOWNER | BSP | P | 10/14/2016 | Tie down and marriage line connections OK -- Serial # 16M33169 | DAKOTAB | DAKOTAB | | BSP | P | 5319554 |
HOMEOWNER | BFD | C | 09/26/2016 | open hole on file / 3000 psf / habitable drain | BRIANB | BRIANB | | BFD | C | 5301959 |
HOMEOWNER | BFD | R | 09/23/2016 | need open hole report to verify drain requirements / drain is installed habitable to sump pit - okay / damp proof okay | BRIANB | BRIANB | | BFD | R | 5301523 |
HOMEOWNER | BFN | C | 09/16/2016 | eufer tied in | BOBF | BOBF | | BFN | C | 5295902 |
HOMEOWNER | BFT | C | 09/07/2016 | including interior pads / 3000 psf | DALE | DALE | | BFT | C | 5287372 |
HOMEOWNER | E= | C | 11/21/2016 | | BRET | BRET | | E= | C | 5350605 |
HOMEOWNER | ER | C | 11/02/2016 | check sub panel on final | CRAIG | CRAIG | | ER | C | 5334697 |
HOMEOWNER | ES | C | 11/02/2016 | Residential Overhead: 200 amp 3/w seal meter | CRAIG | CRAIG | | ES | C | 5334693 |
HOMEOWNER | EUG | C | 10/25/2016 | feeder from pole to house ok; need equipment ground ran in conduit at pole------- need to add disconnect at outside of house | MATTHEW | MATTHEW | | EUG | C | 5327333 |
HOMEOWNER | ER | R | 10/21/2016 | see note for eug | CRAIG | CRAIG | | ER | R | 5325194 |
HOMEOWNER | EUG | R | 10/21/2016 | install equipment grd ---------- complete raceway for feeder to panel in house -------- separate neutrals and grds in house panel ------------ install irreversible crimp for all gec ---------- where is ufer ??? | CRAIG | CRAIG | | EUG | R | 5325186 |
HOMEOWNER | H= | C | 11/21/2016 | Unfinshed basment | MARK | MARK | | H= | C | 5349425 |
HOMEOWNER | HRR | C | 11/14/2016 | Direct vent equipment, Unfinished basement | JACK | JACK | | HRR | C | 5343419 |
HOMEOWNER | HC | C | 11/01/2016 | RELEASE METER | JEFFL | JEFFL | | HC | C | 5333083 |
HOMEOWNER | HI | C | 11/01/2016 | Floor flanges required to final permit | JEFFL | JEFFL | | HI | C | 5333076 |
HOMEOWNER | HO | C | 10/31/2016 | pressure test ok. Notes-- 80' of 1'' installed from meter to home. | JEFFL | JEFFL | | HO | C | 5331819 |
HOMEOWNER | HI | P | 10/31/2016 | Floor flanges required at gas terminations. Re check pressure test. Notes-- 1'' main.. 1 furnace.. 1 wh.. 1 fp.. 1 range.. | JEFFL | JEFFL | | HI | P | 5331812 |
HOMEOWNER | HI | P | 10/28/2016 | Low test. Re inspect all. | JEFFL | JEFFL | | HI | P | 5330696 |
HOMEOWNER | HO | R | 10/28/2016 | No test on outside gas line. | JEFFL | JEFFL | | HO | R | 5330693 |
HOMEOWNER | P= | C | 11/21/2016 | unfinished basement, certificate of potable water to scanning | TED | TED | | P= | C | 5349836 |
HOMEOWNER | PTO | C | 11/14/2016 | | JACK | JACK | | PTO | C | 5343458 |
TALMICH PLUMBING & HEATING LLC | PB | C | 10/03/2016 | basement base to sewage ejector | TED | TED | | PB | C | 5308655 |