TANDEM ENTERPRISES INC | B= | C | 10/25/2017 | All signed off. | JANE | JANE | | B= | C | 5666127 |
TANDEM ENTERPRISES INC | B= | P | 10/05/2017 | Temp CO: OK per JW to extend ( Expires: 11/4/2017 12:00:00 AM) | GITA | GITA | | B= | P | 5646764 |
TANDEM ENTERPRISES INC | B= | P | 10/05/2017 | Temp CO: OK per JW to extend ( Expires: 11/4/2017 12:00:00 AM) | GITA | GITA | | B= | P | 5646763 |
TANDEM ENTERPRISES INC | B= | P | 09/27/2017 | pending completion of plumb mech and elec finals all phase okay. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: ckauffman@tri-lakesfire.com or 484-0911), FRONT RANGE PLUMBING CO., INC. Mechanical Final Inspection is not Completed yet, PROWEST ELECTRIC, INC. Electrical Final Inspection is not Completed yet, REEVES SPECIALTY SERVICES, INC. Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 5638400 |
TANDEM ENTERPRISES INC | B= | P | 09/06/2017 | Temp CO: Temp CO: pending finals for all three pods ( Expires: 10/6/2017 12:00:00 AM) | NELIDA | NELIDA | | B= | P | 5618003 |
TANDEM ENTERPRISES INC | B= | P | 09/01/2017 | Temp CO: pending finals for pod 3 ( Expires: 10/1/2017 12:00:00 AM) | RITA | RITA | | B= | P | 5614697 |
TANDEM ENTERPRISES INC | B= | P | 09/01/2017 | Phase 3 - pending other required inspections / work station in Type A accessible kitchen to be a minimum of 30" wide / provide exit sign at end of upper level corridor / repair fire caulk at low volt wires in laundry room -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: ckauffman@tri-lakesfire.com or 484-0911), FRONT RANGE PLUMBING CO., INC. Mechanical Final Inspection is not Completed yet, PROWEST ELECTRIC, INC. Electrical Final Inspection is not Completed yet, REEVES SPECIALTY SERVICES, INC. Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 5614108 |
TANDEM ENTERPRISES INC | B= | P | 08/16/2017 | Temp CO: ALL THE FINALS ARE PARTIALED ( Expires: 9/15/2017 12:00:00 AM) | GITA | GITA | | B= | P | 5597707 |
TANDEM ENTERPRISES INC | B= | P | 08/14/2017 | pod 2 / Phase 2 final / Type A accessible unit kitchen microwave exceeds maximum 48" reach range and has no forward approach work area / public rest room has less than 60" clear florr space from side wall to countertop edge / all t stats to be with in 48" of finished floor / provide exit sign at end of corridor where it intersects with main corridor / complete all other required inspections -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: ckauffman@tri-lakesfire.com or 484-0911), FRONT RANGE PLUMBING CO., INC. Mechanical Final Inspection is not Completed yet, FRONT RANGE PLUMBING CO., INC. Plumbing Final Inspection is not Completed yet, PROWEST ELECTRIC, INC. Electrical Final Inspection is not Completed yet, REEVES SPECIALTY SERVICES, INC. Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 5595087 |
TANDEM ENTERPRISES INC | B= | P | 08/08/2017 | Temp CO: Pending finals ( Expires: 9/7/2017 12:00:00 AM) | RITA | RITA | | B= | P | 5588865 |
TANDEM ENTERPRISES INC | B= | P | 08/08/2017 | Temp CO: Pending finals ( Expires: 9/7/2017 12:00:00 AM) | RITA | RITA | | B= | P | 5588864 |
TANDEM ENTERPRISES INC | BSP | P | 07/28/2017 | framing for duct chases in pod 3 okay | BOBF | BOBF | | BSP | P | 5579272 |
PROWEST ELECTRIC, INC. | BSP | P | 07/21/2017 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Splice to add exit lights. | BERTHA | BERTHA | | BSP | P | 5571423 |
TANDEM ENTERPRISES INC | BSP | T | 07/21/2017 | PAID (REC#1440856) PLAN SPLICE FEE: $50 by: BPHILLIPS for Construction: Provided accessibility details for guest bath. | BPHILLIPS | BPHILLIPS | | BSP | T | 5571414 |
TANDEM ENTERPRISES INC | B= | P | 07/10/2017 | Temp CO: pending finals ( Expires: 8/9/2017 12:00:00 AM) | MINDY | MINDY | | B= | P | 5559220 |
TANDEM ENTERPRISES INC | BSP | P | 07/10/2017 | fire protection for low voltage wire penetrations at floor ceiling and roof ceiling in pods 2 and 3 okay | BOBF | BOBF | | BSP | P | 5559094 |
TANDEM ENTERPRISES INC | B= | P | 07/07/2017 | reinspect of phase 1 / still need to complete lowering of sinks and towel bars in all B units / clearance and sink height in public accessible bathroom has not been done, reach range at operable windows cannot exceed 48", eng letter and open hole for foundation on file / install directional exit signs at corridor intersection on both levels / fire protection per previous inspection has been completed -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: ckauffman@tri-lakesfire.com or 484-0911), FRONT RANGE PLUMBING CO., INC. Mechanical Final Inspection is not Completed yet, FRONT RANGE PLUMBING CO., INC. Plumbing Final Inspection is not Completed yet, PROWEST ELECTRIC, INC. Electrical Final Inspection is not Completed yet, REEVES SPECIALTY SERVICES, INC. Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 5557391 |
TANDEM ENTERPRISES INC | BFR | P | 07/06/2017 | pending other required inspections - inside layer of TYpe x at duct chases in pod 2 okay, reminded Wyatt that rated access panels will be required at access openings | BOBF | BOBF | | BFR | P | 5556092 |
TANDEM ENTERPRISES INC | BSP | P | 07/05/2017 | pending other required inspections - fire protection at floor ceiling assemblies for duct chases in pods 2 and 3 okay / showed Wyatt what a listing for cable penetrations looks like out of Hilti book including maximum allowable fill of cable in pipe | BOBF | BOBF | | BSP | P | 5555046 |
TANDEM ENTERPRISES INC | B= | R | 06/29/2017 | Inspection performed in Phase 1 area - all sinks in type B units max height to top of rim 34" / accessible public rest room needs 60" clear space from wall next to toilet to edge of counter / max height of sink in restroom 34" / towel bars and t stats max height 48" in all b units / max reach range for at least 1 window in accessible unit is 48" / need grab bars installed at lower level ramp / escutcheons at sprinkler heads must cover penetration at rated walls and ceilings / fire caulk at wire penetrations in rated ceiling / patch hole in ceiling in fire riser room / no accessible route to upper level B units / need exit sign at east end of ramp going to existing building / complete all door hardware and door lights throughout / amended 6/29 2017 / need all eng observation letters for footing and foundation / reach range for windows in offices cannot exceed 48". Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not | BOBF | BOBF | | B= | R | 5551222 |
TANDEM ENTERPRISES INC | BSP | R | 06/28/2017 | "listing" for wire sleeves was actually at product description. need an actual listing for 3M wire sleeves that includes maximum fill of sleeve with type of wire being used | BOBF | BOBF | | BSP | R | 5549756 |
TANDEM ENTERPRISES INC | BSP | P | 06/28/2017 | met with Wyatt and Rick and reviewed Color coding of plans for phased occupancy, as well as color coded plans need to be submitted to PPRBD , showed him how phased areas need to have have specific start and stop point | BOBF | BOBF | | BSP | P | 5549754 |
FRONT RANGE PLUMBING CO., INC. | BSP | T | 06/28/2017 | PAID (REC#1436738): PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 6 28 -17 | TCRIPPEN | TCRIPPEN | | BSP | T | 5549531 |
PROWEST ELECTRIC, INC. | BSP | T | 06/28/2017 | PAID (REC#1437433) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised service - added generator and emergency panel(s). Revised/added panel schedules. Revised power and lighting throughout. | BERTHA | BERTHA | | BSP | T | 5549086 |
REEVES SPECIALTY SERVICES, INC. | BSP | P | 06/28/2017 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised to show generator and associated gas piping | JUSTINC | JUSTINC | | BSP | P | 5548871 |
TANDEM ENTERPRISES INC | B16 | P | 06/21/2017 | Spoke with Scott Gratrix permit holder and furniture is being removed so inspections can resume per Bert W | BERTW | BERTW | | B16 | P | 5542849 |
TANDEM ENTERPRISES INC | B16 | R | 06/21/2017 | FIre department has no notes to allow furniture to be moved in to Pod 1, currently furniture is in 2 offices, per Bert W no further inspections until written release to contractor has been issued | BOBF | BOBF | | B16 | R | 5542355 |
TANDEM ENTERPRISES INC | BSP | P | 06/21/2017 | pending other required inspections , drywall install at walls and ceilings of upper and lower levels of pod 3 okay / still need to inspect chases and penetrations on both levels | BOBF | BOBF | | BSP | P | 5542342 |
TANDEM ENTERPRISES INC | BSP | R | 06/19/2017 | Rated ceilings outside IT rooms in lower level of pods 2 and 3 -need to complete tape at joints, seal penetrations and need listing for penetrations for low volt wires coming through rated ceiling | BOBF | BOBF | | BSP | R | 5539680 |
TANDEM ENTERPRISES INC | BSP | P | 06/14/2017 | rc channel in upper level of pod 3 okay | BOBF | BOBF | | BSP | P | 5535439 |
TANDEM ENTERPRISES INC | BSP | P | 06/13/2017 | pending other required inspections / drywall install at rated walls and ceilings upper and lower levels of pod 2 okay except in units P29, P212 and lobby where ceilings have not been installed, will need listings for pipe penetrations at rated ceilings of lower level bathrooms | BOBF | BOBF | | BSP | P | 5534078 |
TANDEM ENTERPRISES INC | BSP | P | 06/08/2017 | 1st layer drywall on rated lid of lower level pod 2 and corridor between pod and 3 okay | BOBF | BOBF | | BSP | P | 5529753 |
TANDEM ENTERPRISES INC | BSP | P | 06/08/2017 | RC channel in upper level of pod 2 okay | BOBF | BOBF | | BSP | P | 5529752 |
TANDEM ENTERPRISES INC | BSP | P | 06/08/2017 | RC channel in lower level pod 3 okay | BOBF | BOBF | | BSP | P | 5529748 |
TANDEM ENTERPRISES INC | BSP | R | 06/06/2017 | listing on page 4.1a -2 is for a 1 hr fire barrier for a shaft wall, wall has been changed to duct chase and stops at rated ceiling, fire barrier must extend to roof / angle protecting fire dampers at fire wall okay / 2nd layer type x on ceiling of lower level corridor between pods 1 and 2 okay | BOBF | BOBF | | BSP | R | 5527283 |
TANDEM ENTERPRISES INC | BSP | P | 06/03/2017 | Drywall installation in pod 1 upper level ceiling including stair way okay / Type C installed | BOBF | BOBF | | BSP | P | 5524709 |
TANDEM ENTERPRISES INC | BSP | P | 05/30/2017 | rc channell in upper and lower level of pod 2 and lower corridor between pods 1 and 2 okay / 2nd layer of type C on ceiling in lower level of pod 1 okay | BOBF | BOBF | | BSP | P | 5519843 |
TANDEM ENTERPRISES INC | BSP | R | 05/26/2017 | American type X installed on roof ceiling in pod 1 listing calls for Certainteed Type C / lower level ceilings okays okay per RC 5111, reviewed upper level issue with Wyatt | BOBF | BOBF | | BSP | R | 5518507 |
TANDEM ENTERPRISES INC | BIN | P | 05/24/2017 | nsulation in upper level of pod 3 okay | BOBF | BOBF | | BIN | P | 5515824 |
TANDEM ENTERPRISES INC | BSP | P | 05/24/2017 | pending other required inspections - rc channel in lower level of pod 1, upper and lower corridors between pod 1 and existing building and upper level of pod 1 except bathrooms on upper level okay | BOBF | BOBF | | BSP | P | 5515809 |
TANDEM ENTERPRISES INC | BSP | P | 05/23/2017 | pod1 rated walls / upper area rated wall drywall and screws okay at at all units. lower level rated walls okay except at areas where HVAC has not been inspected okay | BOBF | BOBF | | BSP | P | 5514002 |
TANDEM ENTERPRISES INC | BIN | P | 05/19/2017 | exterior walls of lower levels of pods 2 and 3 okay | BOBF | BOBF | | BIN | P | 5511741 |
TANDEM ENTERPRISES INC | BIN | P | 05/17/2017 | pending other required inspections - insulation on walls of upper and lower corridors between existing building and pod 1, upper and lower level pod 1 and upper level of pod 2 okay | BOBF | BOBF | | BIN | P | 5509411 |
TANDEM ENTERPRISES INC | BFR | P | 05/17/2017 | pending other required inspections- frame and firecaulk at walls okay in lower levels of pods 2 and 3 | BOBF | BOBF | | BFR | P | 5509404 |
REEVES SPECIALTY SERVICES, INC. | BSP | T | 05/16/2017 | PAID (REC#1425010): PLAN SPLICE FEE: $87.5 by: JUSTINC for Mechanical: Revised dampers | JUSTINC | JUSTINC | | BSP | T | 5508175 |
TANDEM ENTERPRISES INC | BFR | P | 05/16/2017 | pending other required inspections / upper and lower corridors between pod 1 and existing building frame and fire caulk okay / pending other required inspections - interior wall framing on upper level pod 3 okay, exterior walls need shims at trimmers and missing SD screws at LGT3 / lower levels of pods 2 and 3 need shims at trimmers throughout and hold downs need anchor bolts tightened | BOBF | BOBF | | BFR | P | 5507842 |
TANDEM ENTERPRISES INC | BSP | T | 05/15/2017 | PAID (REC#1424548) PLAN SPLICE FEE: $50 by: DANM for Construction: Minor floor plan revisions including changing roll-in shower to transfer type in accessible unit and added Sheet A4.1B Firestop Systems and Details | DANM | DANM | | BSP | T | 5505932 |
TANDEM ENTERPRISES INC | BFR | P | 05/12/2017 | all areas are pending other required inspections - ceiling framing in lower level corridor in pod 1 and between pods 1 and 2 okay / wall s and trusses of upper level pod 2 framing and fire caulk okay | BOBF | BOBF | | BFR | P | 5504812 |
TANDEM ENTERPRISES INC | BSP | P | 05/11/2017 | met with Wyatt to review areas that can be drywalled, he will provide listing for hoods over can lights in ceilings and will call in wall inspection for pod 2 | BOBF | BOBF | | BSP | P | 5503537 |
TANDEM ENTERPRISES INC | BSP | P | 05/03/2017 | pending all other required inspections - lower level main corridor floor framing starting at pod 1 through pod 3 okay | BOBF | BOBF | | BSP | P | 5494727 |
TANDEM ENTERPRISES INC | BLA | C | 04/18/2017 | | BOBF | BOBF | | BLA | C | 5478959 |
TANDEM ENTERPRISES INC | BSP | T | 04/17/2017 | PAID (REC#1417761) PLAN SPLICE FEE: $50 by: DANM for Construction: Change rated shaft wall to chase wall (no rating); provide new assembly listing for wall type 15 | DANM | DANM | | BSP | T | 5477303 |
TANDEM ENTERPRISES INC | BSP | P | 04/14/2017 | 1 hour fire partition adjacent to both sides of fire wall okay | BOBF | BOBF | | BSP | P | 5475524 |
TANDEM ENTERPRISES INC | BSP | P | 04/11/2017 | on site meeting with architect, super, mech engineers and Nancy S to review conditions of floor ceiling penetrations and fire wall penetrations. Architect and mech eng to redrawpentrations to allow fire dampers to be installed in chases. Also reviewed exit enclosure requirements and assembly for fire fire barriers | BOBF | BOBF | | BSP | P | 5471876 |
TANDEM ENTERPRISES INC | BLA | P | 04/10/2017 | pods 2 and 3 okay, need to confirm weep screed above paved areas by final / corrodor connections between pods need to have exterior requirements confirmed at emergency exits / pod 1 okay on north, east and west sides | BOBF | BOBF | | BLA | P | 5469918 |
TANDEM ENTERPRISES INC | BSP | R | 04/06/2017 | need mech inspection at all wall penetrations in pod 2 / pod 2 already stocked need to move drywall so a walls can be inspected from at least 1 side / need listings for revised mech equipment to verify framing requirements at wall floor penetrations through rated walls and floors / still need listings for light fixture protection | BOBF | BOBF | | BSP | R | 5466765 |
TANDEM ENTERPRISES INC | BSP | T | 03/31/2017 | PAID (REC#1414786) PLAN SPLICE FEE: $100 by: DANM for Construction: Multiple changes throughout architectural and structural sheets | DANM | DANM | | BSP | T | 5462088 |
TANDEM ENTERPRISES INC | BSP | P | 03/31/2017 | met with Wyatt to review drywall install on wallsType x on walls screws 7" oc, need to complete walls and get all listings for mech chases before complete inspection can be done | BOBF | BOBF | | BSP | P | 5461358 |
TANDEM ENTERPRISES INC | BSP | P | 03/23/2017 | roof framing okay, still need listed assemblies for can lights in rated ceilings, nent fans are not protected need listed assembly for penetration, need listed assembly for wall going around sprinkler pipe, need listed assembly for duct chase going from ceiling through 2nd floor / need assembly for 1 hour hall that extends 10' each side of fire wall / reminded Wyatt that weep screed must a minimum of 1/2" above all paved areas and 4" above final grade | BOBF | BOBF | | BSP | P | 5454070 |
TANDEM ENTERPRISES INC | BSP | P | 03/13/2017 | pending other required inspections - pod 1 upper level walls, trusses and fire protection okay. pod 1 lower level missing posting to headers at 2 rear bedrooms, missing putty packs at elec boxes hallway wall next to office | BOBF | BOBF | | BSP | P | 5438964 |
TANDEM ENTERPRISES INC | BFR | P | 03/01/2017 | still need to complete fire caulk at top plates to complete rated floor assembly / reviewed floor ceiling, roof ceiling and wall assemblies with wyatt | BOBF | BOBF | | BFR | P | 5428520 |
TANDEM ENTERPRISES INC | BSP | R | 02/27/2017 | inspected Fire caulk at rated walls in pod 1, walls are rated 10' beyond each side of fire wall and penetrations need to be fire caulked / need listed assemblies for can lights in ceiling / need listed assembly for tub valve penetrations in fire partitions / fire caulk at penetrations in rated interior walls okay | BOBF | BOBF | | BSP | R | 5426143 |
TANDEM ENTERPRISES INC | BSP | T | 02/25/2017 | PAID (REC#1405802) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY Revised panel schedules P1L2, P2L2, and P3L2 | SHELBY | SHELBY | | BSP | T | 5425038 |
TANDEM ENTERPRISES INC | BSP | R | 02/21/2017 | need to complete firecaulk at all rated walls, need to protect tub traps / need putty pack at all elec boxes that are in same bay and face in opposite directions / reviewed fire barrier requirements at exit enclosure | BOBF | BOBF | | BSP | R | 5420089 |
TANDEM ENTERPRISES INC | BFD | C | 02/10/2017 | exterior | BOBF | BOBF | | BFD | C | 5412392 |
TANDEM ENTERPRISES INC | BSP | P | 02/08/2017 | PLAN SPLICE: (No Fee) by: SHELLEY for Construction: shaft termination detail | SHELLEY | SHELLEY | | BSP | P | 5410040 |
REEVES SPECIALTY SERVICES, INC. | BSP | T | 02/08/2017 | PAID (REC#1401051) PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: splice to delta H | JUSTINC | JUSTINC | | BSP | T | 5409989 |
TANDEM ENTERPRISES INC | BFR | P | 02/08/2017 | shaft framing between floors building 1 okay ( 3 locations) | BOBF | BOBF | | BFR | P | 5409858 |
TANDEM ENTERPRISES INC | BSP | P | 02/08/2017 | exterior shear for buildings 1,2 and 3 okay / rear deck posts and deck post to beam connections for buildings 1,2 and 3 okay | BOBF | BOBF | | BSP | P | 5409850 |
TANDEM ENTERPRISES INC | BSP | P | 02/01/2017 | 2nd layer type c on firewall okay | BOBF | BOBF | | BSP | P | 5404131 |
TANDEM ENTERPRISES INC | BSP | P | 01/30/2017 | 1st layer Type C on fire wall okay | BOBF | BOBF | | BSP | P | 5401491 |
TANDEM ENTERPRISES INC | BSP | P | 01/26/2017 | C-H Channel framing and coreboard for fire wall okay | BOBF | BOBF | | BSP | P | 5399541 |
TANDEM ENTERPRISES INC | BSP | P | 01/19/2017 | met with wyatt and plumb and mech contractors and reviewed listings for pipe penetrations | BOBF | BOBF | | BSP | P | 5393075 |
TANDEM ENTERPRISES INC | BFR | R | 01/17/2017 | pod 1 trusses, missing all laterals on trusses ao3,4, 8 and 9 / AO4 trusses to have laterals lapped minimum 2 trusses / per previous conversation with Wyatt, need all listings for pipe penetrations, roof drains may require EJ due to size of pipe and support at plates, need manufacturer requirements for clearances for floor ceiling fire/smoke dampers | BOBF | BOBF | | BFR | R | 5390659 |
TANDEM ENTERPRISES INC | BSP | R | 01/04/2017 | truss details do not match trusses installed, need to verify hardware requirements for 3 ply girders where up lift exceeds 2500# and only 2 H 2.5's installed / exterior coil strapping for all 3 pods okay / talked to Wyatt about required annular space at penetrations at rated walls | BOBF | BOBF | | BSP | R | 5382273 |
TANDEM ENTERPRISES INC | BSP | T | 12/29/2016 | PAID (REC#1392183) PLAN SPLICE FEE: $50 by: DANM for Construction: Additional details for fire wall door framing | DANM | DANM | | BSP | T | 5379482 |
TANDEM ENTERPRISES INC | BSP | P | 12/27/2016 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical | DALEH | DALEH | | BSP | P | 5377231 |
PROWEST ELECTRIC, INC. | BSP | T | 12/23/2016 | PAID (REC#1392184) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Revise utility transformer size and impedance---series rate SDB2, P3L1, and P3L2 | SHELBY | SHELBY | | BSP | T | 5376016 |
TANDEM ENTERPRISES INC | BSP | T | 12/21/2016 | PAID (REC#1392183) PLAN SPLICE FEE: $50 by: DANM for Construction: Minor revisions to floor and framing plans, removal of stone on elevations and change of fire wall listed assembly | DANM | DANM | | BSP | T | 5373584 |
TANDEM ENTERPRISES INC | BSP | P | 12/16/2016 | met with Wyatt, and him fire wall would have to be rebuilt te flect firewall design including all specified components, also requested detail of wall elevation and door assembly in wall | BOBF | BOBF | | BSP | P | 5370565 |
TANDEM ENTERPRISES INC | BSP | P | 12/14/2016 | Training with Bob on fire wall construction | BERTW | BERTW | | BSP | P | 5368522 |
TANDEM ENTERPRISES INC | BFR | R | 12/14/2016 | training with BW / reviewed fire walls with continuity through floors / fire wall installed not per GA WP 7080 / Certainteed core board required and USG installed, need complete listing for USG including locations of melt away tabs / coreboard has been screwed to C-H channels, provide letter to address, need detail for door installation at fire wall / C-H channel has been spliced need to detail on required continuity | BOBF | BOBF | | BFR | R | 5367785 |
TANDEM ENTERPRISES INC | BSP | T | 12/07/2016 | PAID (REC#1389018): PLAN SPLICE FEE: $50 by: DANM for Construction: Trusses | DANM | DANM | | BSP | T | 5363054 |
FRONT RANGE PLUMBING CO., INC. | BSP | T | 11/21/2016 | PAID (REC#1389019): PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 11-21-16 | TCRIPPEN | TCRIPPEN | | BSP | T | 5350158 |
PROWEST ELECTRIC, INC. | BSP | T | 11/18/2016 | PAID (REC#1389020): PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Added F/SD | BERTHA | BERTHA | | BSP | T | 5348818 |
TANDEM ENTERPRISES INC | BSP | T | 11/17/2016 | PAID (REC#1389021): PLAN SPLICE FEE: $50 by: DANM for Construction: Floor elev. clarifications, fire rating details revisions, removal of fireplaces, structural drawing modifications | DANM | DANM | | BSP | T | 5347179 |
TANDEM ENTERPRISES INC | BSP | P | 11/03/2016 | met with Job Super Wyatt 303-304-8616 / reviewed scope of work including accessible elements / rated walls, including having full print outs of all listed assemblies / truusses pending / Type 5B construction / A2 and I1 occ | BOBF | BOBF | | BSP | P | 5335835 |
TANDEM ENTERPRISES INC | BFN | P | 10/07/2016 | met with Wyatt, reviewed scope, okay to use eng for foundation | BOBF | BOBF | | BFN | P | 5313405 |
PROWEST ELECTRIC, INC. | E= | C | 10/23/2017 | Generator ----- j boxes ------ generator panels ok | CRAIG | CRAIG | | E= | C | 5664211 |
PROWEST ELECTRIC, INC. | E= | P | 10/18/2017 | install grd lugs in j boxes in attic' s --------- install cu to grd rod ----------- label 705.10 | CRAIG | CRAIG | | E= | P | 5659741 |
PROWEST ELECTRIC, INC. | E= | P | 09/13/2017 | waiting on generator and wiring of generator for each pods | CRAIG | CRAIG | | E= | P | 5624973 |
PROWEST ELECTRIC, INC. | E= | P | 08/31/2017 | pod 3 ------- remove outlets in laundry area or gfi protect ---------------------- pod 1 rtu 1 breaker to big needs to be 35 amp can' t free air wires inside rtu' s need to have complete raceway or have paper work need to remove all mc from j boxes for generator | CRAIG | CRAIG | | E= | P | 5613113 |
PROWEST ELECTRIC, INC. | E= | P | 08/15/2017 | pod two is complete | CRAIG | CRAIG | | E= | P | 5596262 |
PROWEST ELECTRIC, INC. | ES | P | 08/07/2017 | Commercial Service: service ok | CRAIG | CRAIG | | ES | P | 5588174 |
PROWEST ELECTRIC, INC. | ER | P | 08/07/2017 | | CRAIG | CRAIG | | ER | P | 5588173 |
PROWEST ELECTRIC, INC. | EP | P | 08/07/2017 | pod one 400 amp 4/w sec 1 and 2 ok pod two 600 amp 4/w sec 1 and 2 ok | CRAIG | CRAIG | | EP | P | 5588172 |
PROWEST ELECTRIC, INC. | ER | P | 08/07/2017 | pod one is complete -------------- pod two still needs smokes in dorm rooms | CRAIG | CRAIG | | ER | P | 5588171 |
PROWEST ELECTRIC, INC. | E= | P | 08/04/2017 | pod two ----- install smoke detectors in dorm rooms and breaker locks for heaters ----------- check on s.o cords connected water heaters ------------- need to inspect all electric panel | CRAIG | CRAIG | | E= | P | 5586538 |
PROWEST ELECTRIC, INC. | EUG | P | 07/10/2017 | south ballard light ug west building to east building and 1/4 pvc to pool location | BRET | BRET | | EUG | P | 5559211 |
PROWEST ELECTRIC, INC. | E= | P | 06/27/2017 | pod one pending stairwell heaters disconnect or definite off switch, 120 volt smoke detectors not installed in dorm rooms. checking on s.o cord connected water heaters | BRET | BRET | | E= | P | 5548294 |
FOUNDERS FIRE AND ELECTRIC LLC | E= | C | 06/27/2017 | FIRE ALARM INSPECTION: | BRET | BRET | | E= | C | 5548293 |
FOUNDERS FIRE AND ELECTRIC LLC | ER | C | 06/27/2017 | FIRE ALARM INSPECTION: | BRET | BRET | | ER | C | 5548292 |
PROWEST ELECTRIC, INC. | EUG | P | 06/14/2017 | 1 1/4" and 5 - 1" and 3/4" pvc to generator pad ok | CRAIG | CRAIG | | EUG | P | 5535075 |
PROWEST ELECTRIC, INC. | ES | C | 06/12/2017 | Commercial Service: 1600 amp 3 phase 120/208 v. new service ok to set meter | CRAIG | CRAIG | | ES | C | 5532624 |
PROWEST ELECTRIC, INC. | EUG | P | 06/12/2017 | 1/2" and 3/4" pvc to north pole lights ok | CRAIG | CRAIG | | EUG | P | 5532616 |
PROWEST ELECTRIC, INC. | ES | P | 06/09/2017 | Residential Underground: Pre release ok / | CRAIG | CRAIG | | ES | P | 5530359 |
PROWEST ELECTRIC, INC. | EUG | P | 06/07/2017 | 1 1/4" , 5 - 1" , 3/4" , and 1/2" all pvc to west generator all pvc stops west on main at this time | CRAIG | CRAIG | | EUG | P | 5528538 |
PROWEST ELECTRIC, INC. | EUG | P | 05/31/2017 | north trench except across drive for pole lights and west end to generator | BRET | BRET | | EUG | P | 5521484 |
PROWEST ELECTRIC, INC. | ER | P | 05/17/2017 | patio ceilings in all 3 guest house ok | CRAIG | CRAIG | | ER | P | 5508787 |
PROWEST ELECTRIC, INC. | ER | P | 05/15/2017 | WALLS / CEILING FOR UP STAIR GOING TO MAIN BUILDING OK CEILING OK IN ALL GUEST HOUSES OK BUT CEILING FOR EXHAUST FANS AND SMOKE DAMPERS NOT READY | CRAIG | CRAIG | | ER | P | 5506750 |
PROWEST ELECTRIC, INC. | ER | P | 04/03/2017 | walls and ceiling for guest house 2 -------- and offices going to maim building only | CRAIG | CRAIG | | ER | P | 5463392 |
FOUNDERS FIRE AND ELECTRIC LLC | ER | P | 04/03/2017 | FIRE ALARM INSPECTION: walls and ceiling for all guest house ok --------------- note except for hvac | CRAIG | CRAIG | | ER | P | 5463391 |
PROWEST ELECTRIC, INC. | ES | R | 03/13/2017 | Commercial Service: not ready | CRAIG | CRAIG | | ES | R | 5439078 |
PROWEST ELECTRIC, INC. | EUG | P | 03/13/2017 | 6 - 3" pvc from xfmr to MDP 6 - 3" pvc feeders 1 1/2" pvc from MDP t corner of building for pool -------------- talked to contractor about ADA | CRAIG | CRAIG | | EUG | P | 5439071 |
FOUNDERS FIRE AND ELECTRIC LLC | ER | P | 03/13/2017 | FIRE ALARM INSPECTION: walls in guest house 1 & 2 14/2 / 16/2 fplr ------------------- note talked to contractor about ADA | CRAIG | CRAIG | | ER | P | 5439066 |
PROWEST ELECTRIC, INC. | ER | P | 02/28/2017 | guest house 1 wall for P1L1 / P1L2 ok walls for breeze ways ok | CRAIG | CRAIG | | ER | P | 5426696 |
PROWEST ELECTRIC, INC. | ER | P | 02/13/2017 | walls ok for guest house 1 for first / second floor ------------ note walls with panels P1L1 / P1L2 not ready panels not set | CRAIG | CRAIG | | ER | P | 5413413 |
PROWEST ELECTRIC, INC. | EUG | P | 10/25/2016 | 6 - 3" pvc for guest house 3 only ok talked to electrician about ufer | CRAIG | CRAIG | | EUG | P | 5327453 |
PROWEST ELECTRIC, INC. | EUG | P | 10/18/2016 | 2 -- 3" pvc to each guest house 1 and 2 only ok note 240.87 for main panel | CRAIG | CRAIG | | EUG | P | 5321358 |
FRONT RANGE PLUMBING CO., INC. | H= | C | 10/16/2017 | GAS FINAL OK. | NANCY | NANCY | | H= | C | 5657213 |
REEVES SPECIALTY SERVICES, INC. | H= | C | 10/16/2017 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 5657212 |
FRONT RANGE PLUMBING CO., INC. | H= | P | 10/12/2017 | NO CALL AHEAD NUMBER, NO PERSONNEL ON SITE SO GUESSED ON WHAT INSPECTION WAS CALLED IN FOR. INSPECTED GAS LINE CONNECTION TO GENERATOR. NEED TO LABEL MEDIUM PRESSURE GAS LINE AT GENERATOR. STILL NEED CONTRACTOR THAT INSTALLED GENERATOR TO ADD IT TO THEIR SCOPE OF WORK. STILL NEED GAS LINES INSTALLED TO POOL EQUIPMENT. | NANCY | NANCY | | H= | P | 5653256 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 09/29/2017 | INSTALL FACTORY VENT EXTENSIONS FOR ROOF TOPS FOR POD 1-2-3 . REMOVE THE DAMPER OR LOCK OPEN DAMPER IN MAKE UP AIR GRILL TO LAUNDRY .NEED TO CONSULT WITH PREVIOUS INSPECTOR .NEED TEST AND BALANCE REPORT . | LIDO | LIDO | | H= | P | 5641212 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 09/28/2017 | Field canceled by contractor . | LIDO | LIDO | | H= | P | 5640050 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 08/31/2017 | POD THREE; LAUNDRY ROOM LACKS REQUIRED MAKE-UP AIR. LABEL ALL DAMPER ACCESS DOORS INCLUDING DOOR IN ATTIC. PROVIDE TEST AND BALANCE REPORT FOR POD THREE. STILL NEED CORRECTIONS FOR POD TWO, SEE INSPECTION COMMENTS DATED 8/11/17. TEST AND BALANCE RECEIVED FOR POD TWO. POD ONE: LAUNDRY ROOM LACKS REQUIRED MAKE-UP AIR. | NANCY | NANCY | | H= | P | 5613558 |
FRONT RANGE PLUMBING CO., INC. | H= | P | 08/31/2017 | GAS/WATER HEATER VENT FINAL OK FOR ALL PODS. STILL NEED GAS FOR POOL EQUIPMENT AND GENERATOR. | NANCY | NANCY | | H= | P | 5613557 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 08/16/2017 | TEST AND BALANCE REPORT FOR POD 2 RECEIVED AND SCANNED, SEE IMAGES. | NANCY | NANCY | | H= | P | 5598216 |
FRONT RANGE PLUMBING CO., INC. | H= | P | 08/16/2017 | POD 2: PROVIDE INFORMATION ON GRAY GLUE USED ON WATER HEATER VENT PIPE, NEED TO VERIFY ASTM NUMBER IS APPROVED BY WATER HEATER MANUFACTURER. GAS ALL OK. POD 1: PROVIDE INFORMATION ON GRAY GLUE USED ON WATER HEATER VENT. CONDENSATE TUBING IS KINKED. STILL NEED TO SEE GAS ON ROOF. POD 3: PROVIDE INFORMATION ON GRAY GLUE USED ON WATER HEATER VENT. CONDENSATE TUBING KINKED. STILL NEED TO SEE GAS ON ROOF. | NANCY | NANCY | | H= | P | 5597238 |
REEVES SPECIALTY SERVICES, INC. | HSP | P | 08/14/2017 | SEE IMAGES FOR LETTER FROM TRANE APPROVING SHOP FABRICATED EXTENSIONS FOR RTU EXHAUST. | NANCY | NANCY | | HSP | P | 5595452 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 08/14/2017 | EQUIPMENT ON ROOF LACKS ADEQUATE ACCESS. DUCTS AND OTHER MATERIALS INSTALLED IN ATTIC BLOCK WALKWAY AND DOOR TO ROOF EQUIPMENT WELL. SEE IFGC 306.3 (APPLIANCES IN ATTICS) AND IFGC 306.5 ( EQUIPMENT AND APPLIANCES ON ROOF OR ELEVATED STRUCTURES). | NANCY | NANCY | | H= | P | 5594356 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 08/11/2017 | POD 2 MECHANICAL FINAL INSPECTION. LAUNDRY ROOM LACKS MAKE-UP AIR FOR TWO DRYERS. PROVIDE KEYS TO OPEN DAMPER ACCESS DOORS. LABEL ALL DAMPER ACCESS DOORS. DAMPER ACCESS DOOR NEXT TO SUPPLY AIR GRILL IN NORTH WEST PATIENT ROOM DOES NOT OPEN TO PROVIDE ACCESS TO DAMPER. PERMANENTLY LABEL EQUIPMENT ON ROOF, NO BLACK MARKERS PLEASE. INSTALL FACTORY RTU VENT EXTENSIONS. QUESTION REGARDING ACCESS TO EQUIPMENT ON ROOF THROUGH ATTIC. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5593880 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 08/10/2017 | POD 2. RTU-2: TWO DAMPERS IN ATTIC, FRAMING AND SHEET ROCK OK. | NANCY | NANCY | | HD | P | 5592624 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 08/01/2017 | POD 3 LOWER LEVEL. NORTH EAST BATHROOM EXHAUST FAN CONNECTION OK. OK TO COVER PER MECHANICAL ONLY. | NANCY | NANCY | | HD | P | 5582993 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 07/25/2017 | POD 3 LOWER LEVEL AT THE TWO BATHROOMS EAST END OF CORRIDOR: THREE DAMPERS, BREAK AWAY CONNECTIONS AND RETAINING ANGLES OK. OK TO COVER PER MECHANICAL ONLY. | NANCY | NANCY | | HD | P | 5574908 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 07/21/2017 | POD 3 NORTH EAST END BATHROOMS AND CORRIDOR: INSTALL DAMPERS TO SLEEVES. PROPERLY INSTALL RETAINING ANGLES PROPERLY INSTALL ROUND PIPE TO DAMPERS FOR THE BREAK AWAY CONNECTIONS. | NANCY | NANCY | | HD | P | 5572611 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 07/20/2017 | PROVIDE INSTALLATION INSTRUCTIONS FOR DAMPERS AS REQUESTED AT LAST INSPECTION. ALWAYS HAVE INSTRUCTIONS ON SITE. INSTALL BREAK AWAY CONNECTIONS PER MANUFACTURER. INSTALL RETAINING ANGLES PER MANUFACTURER. STILL NEED TO VERIFY INSTALLATION OF DAMPERS IN SLEEVES. DO NOT COVER ANYTHING IN THIS AREA UNTIL NEXT INSPECTION. | NANCY | NANCY | | HD | P | 5570327 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 07/18/2017 | POD THREE LOWER LEVEL. TWO BATHROOMS ON EAST END. PROVIDE FIRE DAMPER INSTALLATION INSTRUCTIONS, NEED TO VERIFY HOW DAMPERS ARE TO BE INSTALLED IN SLEEVES. NEED BUILDING INSPECTION TO VERIFY HEIGHT OF SOFFIT ACROSS HALLWAY AND SOFFITS IN BATHROOMS, CEILING WILL BE LESS THAN 6'8" WHEN SHEET ROCK IS INSTALLED. DAMPERS ACROSS HALLWAYS NEED RETAINING ANGLES AND ACCESS DOORS INSTALLED. NORTH EAST BATHROOM: ROUGH DUCTS OK, OK TO CLOSE UP WRAP. COMPLETE EXHAUST DUCT AND INSTALL FAN. SOUTH EAST BATHROOM: ROUGH DUCTS AND EXHAUST OK, OK TO CLOSE UP WRAP. DO NOT CLOSE UP ANY SOFFITS IN THIS AREA. | NANCY | NANCY | | HD | P | 5568101 |
REEVES SPECIALTY SERVICES, INC. | HD | R | 07/14/2017 | ALL FIRE DAMPER OPENINGS OK TO INSTALL DAMPERS AT POD 3 / 1ST AND 2ND FLOORS - PER CONVERSATION WITH LEROY FROM REEVES STILL NEED TO VERIFY CORRECT FRAMING IN ATTIC ON DAMPER AT POD 2 ATTIC | JERRYF | JERRYF | | HD | R | 5565266 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 07/13/2017 | NEED ALL DAMPER OPENINGS SHEET ROCKED AND FIRE TAPED - HAD MEETING WITH LEROY ON THESE ISSUES | JERRYF | JERRYF | | HD | P | 5563889 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 07/12/2017 | ABOVE SOFFIT BATH ROOM FANS IN 1ST FLOOR APARTMENTS IN POD 3 OK - NEED DAMPERS REMOVED IN WALLS TO VERIFY SHEET ROCK DOESN'T HAVE ANY BREECHES NEED DAMPER FRAMED ON 2ND FLOOR AT CEILING - NEED TO CHECK POD 2 DAMPER AT CEILING ON 2ND FLOOR | JERRYF | JERRYF | | HD | P | 5561448 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 07/11/2017 | POD 2 1ST FLOOR - ABOVE SOFFIT MAIN SA DUCT OK - 4 BATH FANS AND VENTS OK | JERRYF | JERRYF | | HD | P | 5560086 |
FRONT RANGE PLUMBING CO., INC. | H= | P | 07/10/2017 | PARTIAL FINAL FOR PHASE 1 POD 1 ONLY - ALL OK - STILL NEED ALL POD 2 AND 3 AND GENERATOR LINE | JERRYF | JERRYF | | H= | P | 5558558 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 07/06/2017 | TRANE LETTER RECEIVED STILL NEED REVISED TAB REPORT FOR PHASE 1 TO COMPLETE PHASE 1 FINAL | JERRYF | JERRYF | | H= | P | 5555565 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 07/05/2017 | THIS INSPECTION WAS FOR PHASE 1 / POD 1 - NEED MANUFACTURE APPROVED SNORKEL OR ENGINEER LETTER FROM MANUFACTURE APPROVING SHOP BUILT SNORKEL - NEED REVISED TAB REPORT SHOWING ALL OSA READINGS AT PTAC UNITS - ALL OTHER CORRECTIONS MADE | JERRYF | JERRYF | | H= | P | 5554517 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 07/05/2017 | FIRE DAMPER AND DUCT CONNECTIONS OK ON MAIN FLOOR AT POD 2 SOUTH CHASE CEILING - NEED INSTALL MANUAL FOR FIRE DAMPERS USED IN BASEMENT TO VERIFY PROPER RETAINAGE - FIRE DAMPERS HAVE EXPOSED WOOD AT CONNECTIONS TO DUCT / CANNOT HAVE BREECHES | JERRYF | JERRYF | | HD | P | 5554513 |
REEVES SPECIALTY SERVICES, INC. | H= | R | 06/30/2017 | NEED THE FOLLOWING TO COMPLETE PHASE 1 FINAL - EXTEND EXHAUST FLUE ON RTU #2 NEEDS TO BE 10' AWAY OR 3' ABOVE ECONOMIZER INTAKE AT RTU #1 / REST OF ROOF OK - LABEL ALL FIRE DAMPER ACCESS DOORS - PER PREVIOUS NOTES NEED TAB REPORT TO STATE OSA READINGS FOR ALL PTAC UNITS PER NOTES ON EQUIPMENT SCHEDULE | JERRYF | JERRYF | | H= | R | 5552261 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 06/28/2017 | AFTER CONSULT WITH JOHN WELTON INSTRUCTED WYATT WITH TANDEM TO CALL JOHN FOR PHASED TCO INFORMATION - THIS INSPECTION WAS FOR POD 1 PHASED TCO - PARTIAL PENDING THE FOLLOWING - TAB REPORT - INSTALL AND INSPECT DRYER VENTS FROM ROOF TO DRYERS - INSTALL AND LABEL ALL FIRE DAMPER ACCESS DOORS - UNDER CUT ALL DOORS FOR RA PATH PER PLAN - SOMEONE NEEDS TO CLAIM ALL ELECTRIC HEATERS - NEED TAB REPORT TO INCLUDE MINIMUM OSA SETTING AT ALL PTAC UNITS | JERRYF | JERRYF | | H= | P | 5549200 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 06/27/2017 | THIS INSPECTION WAS FOR POD 2 MAIN DUCT IN CHASE FROM BASEMENT TO ATTIC CHASE - NEED OPENINGS AT CEILING PENETRATIONS ADDRESSED BEFORE COMPLETING CHASE | JERRYF | JERRYF | | HD | P | 5548738 |
REEVES SPECIALTY SERVICES, INC. | HD | R | 06/26/2017 | NEED CONSULT WITH PREVIOUS INSPECTOR / SENIOR INSPECTOR AND BUILDING INSPECTOR ON RADIATION DAMPERS AT CEILING PENETRATIONS AT CHASES --- DO NOT COVER - NEED PROPER INSTALL MANUAL FOR DAMPERS BEING USED POTTORFF CFD521 TO VERIFY INSTALLATION (((((( NOTES: RESTROOM FAN DAMPERS IN POD 2 MAIN LEVEL OK ONLY))))))) | JERRYF | JERRYF | | HD | R | 5547147 |
FRONT RANGE PLUMBING CO., INC. | HO | P | 06/14/2017 | NEED REVISED/APPROVED PRINT FOR UNDERGROUND GAS LINE SHOWING NEW SIZING AND GENERATOR BEING INSTALLED. CONTRACTOR INSTALLING GENERATOR NEEDS TO ADD IT TO THEIR SCOPE OF WORK. 60 LB TEST OK. INSTALLED AS PER NEW DRAWING ON SITE. COVER AT OWN RISK. | NANCY | NANCY | | HO | P | 5536120 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 06/12/2017 | POD # 2 UPPER LEVEL . RTU -1-2 OK TO SOFFIT TRUNK LINES NO TAPS YET.,RTU-3 ABOVE CEILING TRUNK LINE AND LATERALS OK TO WRAP, RTU -1-2-3 NEED TO SEE CONNECTIONS AT DROPS, MUA FOR LAUNDRY ROOMS ? | LIDO | LIDO | | HD | P | 5532387 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 06/09/2017 | THIS INSPECTION WAS FOR POD 2 MAIN FLOOR - ABOVE CEILING FIRE DAMPER FRAMING OK IN ALL CEILING MOUNTED DAMPERS AT CHASE'S - ALL RESTROOM AND CORRIDOR RADIATION DAMPERS / RETAINAGE AND FINAL DUCT CONNECTIONS OK | JERRYF | JERRYF | | HD | P | 5530512 |
REEVES SPECIALTY SERVICES, INC. | HD | L | 06/06/2017 | FIRE DAMPER FRAMING OK IN THE FOLLOWING AREA'S 1ST FLOOR PODS 2 AND 3 CORRIDOR WALLS AND 2ND FLOOR STAIRWELL/ CORRIDOR TRANSFERS / STILL NEED ALL FLOOR CEILING DAMPER FRAMING | JERRYF | JERRYF | | HD | L | 5527606 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 06/02/2017 | POD 1 UPPER LEVEL. SMALL OFFICE AND JANITORS CLOSET CEILING RADIATION DAMPERS OK. POD 1 LOWER LEVEL. FOUR EXHAUST FANS ABOVE CEILING IN TYPE "B" RESTROOMS OK. 14 X 10 SUPPLY DUCT AND BRANCH DUCTS OK. OK TO COVER PER MECHANICAL ONLY. | NANCY | NANCY | | HD | P | 5524695 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 06/01/2017 | POD 1 UPPER LEVEL. PROVIDE INSTALLATION INSTRUCTIONS SHOWING CEILING RADIATION DAMPERS ARE APPROVED TO HAVE BATH EXHAUST FANS INSTALLED ON THEM. SECURE ANGLES TO STRUCTURE AT ALL DAMPERS INSTALLED AT CHASES. STILL NEED TO SEE DAMPERS INSTALLED IN SMALL OFFICE AND JANITOR CLOSET. POD 1 LOWER LEVEL. PROVIDE INSTALLATION INSTRUCTIONS FOR ALL DAMPERS INSTALLED THROUGH WALLS, NEED TO VERIFY BREAK AWAY CONNECTIONS AND RETAINING ANGLE INSTALLATION. 6 INCH ROUND SUPPLY AIR INTO OFFICE OK, OK TO WRAP. 10 X 8 SUPPLY DUCT IN BATHROOM SOFFIT OK, OK TO COVER PER MECHANICAL ONLY. | NANCY | NANCY | | HD | P | 5523384 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 05/25/2017 | POD 1 LOWER LEVEL. FRAMING FOR TWO FIRE/SMOKE DAMPERS AT TWO HOUR WALL OK. FIVE FIRE DAMPER FRAMES IN RATED WALLS OK. STILL NEED TO SEE FRAMING FOR ROUND DAMPER. | NANCY | NANCY | | HD | P | 5517660 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 05/24/2017 | POD 1 UPPER LEVEL ABOVE CEILING. RTU'S 1 AND 2 SUPPLY AND RETURN TRUNK LINES AND LATERALS OK. OK TO CLOSE UP WRAP. NO CEILING RADIATION DAMPERS, EXHAUST FANS, EXHAUST DUCTS OR BYPASS DAMPER YET. | NANCY | NANCY | | HD | P | 5516473 |
FRONT RANGE PLUMBING CO., INC. | HC | C | 05/22/2017 | OK TO SET 2 LB METER. | NANCY | NANCY | | HC | C | 5512935 |
FRONT RANGE PLUMBING CO., INC. | HI | C | 05/22/2017 | STILL NEED UNDERGROUND GAS LINE INSTALLED FOR POOL EQUIPMENT. 60 LB TEST OK. BY FINAL INSTALL REGULATORS, COMPLETE CONNECTIONS TO EQUIPMENT AND LABEL ALL EXPOSED MEDIUM PRESSURE GAS LINES. | NANCY | NANCY | | HI | C | 5512925 |
FRONT RANGE PLUMBING CO., INC. | HI | T | 05/17/2017 | PAID (REC#1425724) LOW TEST AT 40 POUNDS | JERRYF | JERRYF | | HI | T | 5509880 |
FRONT RANGE PLUMBING CO., INC. | HI | P | 05/16/2017 | NEED A 60 LB TEST ON A 100 LB GAUGE. PODS 1, 2 AND 3 GAS INSTALLED AS PER PRINTS EXCEPT IN POD 2 THE 1 INCH GAS WAS INCREASED TO 1 1/4 INCH AND IN POD 3 THE 1 1/4 INCH GAS WAS INCREASED TO 1 1/2 INCH. BY FINAL INSTALL REGULATORS AND MEDIUM PRESSURE LABELS. | NANCY | NANCY | | HI | P | 5508143 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 04/28/2017 | MET WITH WYATT TO DISCUSS SHAFT WALL FRAMING FOR FIRE/SMOKE DAMPERS. NEED ENGINEER TO PROVIDE INFORMATION REGARDING WHERE THE BREAK AWAY CONNECTIONS ARE TO BE INSTALLED AT THIS WALL. | NANCY | NANCY | | HD | P | 5490992 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 04/11/2017 | MEETING WITH MECHANICAL ENGINEERS AND ARCHITECT TO DISCUSS PENETRATIONS THROUGH FLOOR/CEILING ASSEMBLIES, ROOF/CEILING ASSEMBLIES, FIRE WALLS AND FIRE BARRIERS. | NANCY | NANCY | | HD | P | 5471871 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 03/22/2017 | Continuation of notes. WERE TO BE INSTALLED IN A DROP CEILING. UPPER LEVEL FANS ARE INSTALLED AT THE RATED CEILING WITH NO PROTECTION OF OPENING. LOWER LEVEL FANS ARE BEING INSTALLED AT THE DROP CEILING, FOR FANS BEING INSTALLED IN THE DROP CEILING CONTRACTOR IS TO VERIFY IF DAMPERS ARE REQUIRED AT RATED LID OR IF THERE IS A HILTI TYPE LISTING THAT WOULD ALLOW THE 4 INCH EXHAUST DUCT TO BE INSTALLED WITHOUT A DAMPER. AS PREVIOUSLY REQUESTED PLEASE CALL FOR FREQUENT INSPECTIONS. ALL DAMPER OPENINGS ARE REQUIRED TO BE INSPECTED FOR PROPER FRAMING PRIOR TO BEING COVERED BY SHEET ROCK. INSTALLATION INSTRUCTIONS ARE REQUIRED FOR ALL DAMPER INSPECTIONS. QUESTIONS? CONTACT ME OR CALL FOR AN INSPECTION BUT DON'T KEEP PROCEEDING FORWARD WITHOUT ANSWERS. | NANCY | NANCY | | HD | P | 5452510 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 03/22/2017 | AT TODAY'S INSPECTION THE FOLLOWING ITEMS WERE DISCUSSED FOR POD 1. (1) PRINTS STILL SHOW ALL CEILING PENETRATIONS TO BE PROTECTED WITH FIRE/SMOKE DAMPERS, CONTRACTOR IS TO FIND A FIRE/SMOKE DAMPER APPROVED FOR INSTALLATION IN A WOOD ROOF/CEILING ASSEMBLY AND INSTALL PER INSTRUCTIONS. (2) FIRE/SMOKE DAMPERS INSTALLED IN SHAFT WALL CONSTRUCTION. OPENINGS MUST BE FRAMED PER MANUFACTURERS INSTRUCTIONS OR WILL NEED ENGINEER DRAWING SHOWING HOW WALL IS TO BE FRAMED TO MEET DAMPER MANUFACTURERS UL LISTING. (3) FIRE/SMOKE DAMPERS THROUGH A WOOD FLOOR/CEILING ASSEMBLY. CONTRACTOR IS TO FIND A DAMPER APPROVED FOR THIS TYPE OF ASSEMBLY AND INSTALL PER MANUFACTURERS INSTRUCTIONS. (4) CONTRACTOR TO VERIFY THAT DUCTS GOING FROM SECOND TO FIRST FLOOR ARE IN A SHAFT NOT A CHASE. IF THIS IS RATED AS A SHAFT THEN WILL NEED INFORMATION ON HOW FIRE/SMOKE DAMPER IS TO BE INSTALLED, SEE IMC 607.5.5.1 (ENCLOSURE AT THE BOTTOM). (5) BATH EXHAUST FANS. ENGINEER WAS UNDER THE IMPRESSION THAT ALL FANS | NANCY | NANCY | | HD | P | 5452441 |
REEVES SPECIALTY SERVICES, INC. | HD | T | 03/16/2017 | PAID (REC#1411195): AS NOTED ON INSPECTION DATED 1/4/17 MECHANICAL CONTRACTOR IS TO HAVE DAMPER INSTALLATION INSTRUCTIONS ON SITE WHEN CALLING FOR INSPECTION. PRINTS STILL SHOW FIRE/SMOKE DAMPERS BEING INSTALLED IN ROOF/CEILING ASSEMBLY OF POD 1 LEVEL 2. EF-1 PENETRATIONS THROUGH 1 HOUR RATED CEILING ASSEMBLY ARE NOT PROTECTED. FRAMING FOR RTU-2 FIRE/SMOKE DAMPERS GOING INTO MAIN BUILDING CORRIDOR IS PROBABLY NOT CORRECT. MECHANICAL CONTRACTOR HAS FAILED TO CALL INSPECTIONS IN A TIMELY MANNER. MECHANICAL CONTRACTOR HAS FAILED TO ADDRESS HOW PENETRATIONS THROUGH RATED WALLS, CEILING AND FLOORS ARE TO BE PROTECTED AFTER BEING TOLD BY INSPECTOR MULTIPLE TIMES THAT THERE APPEARS TO BE A PROBLEM WITH THE DRAWINGS. | NANCY | NANCY | | HD | T | 5443628 |
BROOKS PLUMBING & HEATING INC. | HI | P | 01/17/2017 | THIS INSPECTION SHOULD HAVE BEEN FOR PERMIT K06651. GAS CONTRACTOR NEEDS TO ATTACH TO PERMIT K06651 AND HAVE THIS INSPECTION COMMENT MOVED TO THAT PERMIT. NEED APPROVED PRINTS SHOWING GENERATOR LOCATION, EQUIPMENT SCHEDULES,GAS LINE SIZING, ELECTRICAL ETC. IS SECOND GENERATOR DIESEL? LOW TEST TODAY. | NANCY | NANCY | | HI | P | 5390939 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 01/04/2017 | NEED GAS CONTRACTOR ATTACHED TO PERMIT. NEED APPROVED SPLICE ON SITE FOR ALL INSPECTIONS. MECHANICAL CONTRACTOR MUST HAVE ALL DAMPER INSTALLATION INSTRUCTIONS ON SITE WHEN CALLING FOR INSPECTION. QUESTION REGARDING FIRE/SMOKE DAMPERS AT CEILING PENETRATIONS, CUT SHEET PROVIDED BY MECHANICAL CONTRACTOR FOR ROUND FIRE/SMOKE DAMPERS ARE TO BE INSTALLED IN CONCRETE FLOOR ONLY, NOT A WOOD CEILING ASSEMBLY. ARE RANGES BEING INSTALLED IN THE KITCHENS OF PODS 2 AND 3? IF YES, HOOD EXHAUST WILL NEED TO VENT TO OUTSIDE OF BUILDING, RECIRCULATION HOOD NOT ALLOWED. | NANCY | NANCY | | HD | P | 5382677 |
FRONT RANGE PLUMBING CO., INC. | P= | C | 08/28/2017 | ALL UNITS . OK TO PLAN . POD 3 | GABE | GABE | | P= | C | 5608688 |
FRONT RANGE PLUMBING CO., INC. | P= | P | 08/15/2017 | ALL CORRECTIONS MADE , POD 2 COMPLETE | GABE | GABE | | P= | P | 5595922 |
FRONT RANGE PLUMBING CO., INC. | P= | P | 08/08/2017 | NEED DOUBLE STOPS AT ALL DISH WASHER CONNECTIONS , NEED HAMMER ARRESTERS AT LAUNDRY , NEED VAC BREAK AT HAND HELD IN ROOL IN SHOWER IN UNIT 12 BASEMENT , REST OK ALL UNITS . OK FOR TCO | GABE | GABE | | P= | P | 5588874 |
FRONT RANGE PLUMBING CO., INC. | P= | P | 07/06/2017 | POD 1 ALL OK , NOTE : ALL SINKS ARE TEMPERED , - DISPENSARY SINK , ALL TO PLAN . OK FOR TCO | GABE | GABE | | P= | P | 5555761 |
FRONT RANGE PLUMBING CO., INC. | P= | R | 06/28/2017 | NEED GAS TO WATER HEATER FOR FINAL INSPECTION , WAIVED TRIP FEE THIS TIME ONLY , NEED TO TEMPER ALL SINKS , REMOVE SHROUD FROM SINKS , | GABE | GABE | | P= | R | 5549460 |
FRONT RANGE PLUMBING CO., INC. | PWO | P | 06/15/2017 | NOTE : WATER FROM POD 3 TO POOL , ( 1 INCH TYPE K ??? ) NEED LETTER TO OK JOINT IN COPPER , NEED TO INSTALL INSULATION AS PER PLANS , NEED PIPE TYPE AND SIZE VERIFIED , | GABE | GABE | | PWO | P | 5537438 |
FRONT RANGE PLUMBING CO., INC. | PTO | C | 03/22/2017 | correction made, aav on all 3 pod washer box venting in wall above boxes, pto complete on all 3 pods | TED | TED | | PTO | C | 5452350 |
FRONT RANGE PLUMBING CO., INC. | PTO | P | 03/21/2017 | water for all three pods on retest after washer boxes added ok, all washer boxes are ''s'' trapped, copper water main to all 3 pods ok | TED | TED | | PTO | P | 5446639 |
FRONT RANGE PLUMBING CO., INC. | PTO | P | 02/03/2017 | POD 1 DWV AND WATER COMPLETE , ON TEST , WATER UP SIZED AT WASHER | GABE | GABE | | PTO | P | 5406126 |
FRONT RANGE PLUMBING CO., INC. | PTO | P | 01/25/2017 | dwv in pod 2 and 3 only on test | GABE | GABE | | PTO | P | 5398258 |
FRONT RANGE PLUMBING CO., INC. | PTO | P | 01/13/2017 | DWV ONLY , NEED TO SECURE CLOSET FLANGES BY NEXT INSPECTION | GABE | GABE | | PTO | P | 5388685 |
FRONT RANGE PLUMBING CO., INC. | PRD | P | 12/14/2016 | POD 3 AND 2 , NEED TO ISOLATE PIPING FROM TRUSS PLATES AND NAIL PLATE/BOCCA AT ALL PIPING . CHECK AT TOP OUT , NEED TO RED LINE OR SPLICE PLANS TO SHOW LOCATION CHANGE OF ROOF DRAINS | GABE | GABE | | PRD | P | 5367712 |
FRONT RANGE PLUMBING CO., INC. | PWO | P | 10/14/2016 | COPPER RUN UNDER FOOTER TO POOL , ALL TO PLAN AND ON TEST | GABE | GABE | | PWO | P | 5318579 |
FRONT RANGE PLUMBING CO., INC. | PWO | R | 10/13/2016 | PLANS CALL FOR TYPE K COPPER , HDPE 1 INC IN DITCH , NEED PLANS SPLICED AND OR LETTER FROM ENGINEER FOR USE OF HDPE | GABE | GABE | | PWO | R | 5317629 |
FRONT RANGE PLUMBING CO., INC. | PB | C | 10/12/2016 | NOTE : ALL DWV ON TEST AND TO PLAN ON POD 1 , ALL OTHER CORRECTIONS MADE , DWV ON TEST , TRAPS INSTALLED | GABE | GABE | | PB | C | 5316499 |
FRONT RANGE PLUMBING CO., INC. | PB | P | 10/11/2016 | this inspection was for pods 2 & 3, need to install and test all tub traps, rest ok, per plan. | TAYLOR | TAYLOR | | PB | P | 5315210 |