COLARELLI CONSTRUCTION, INC. | B= | C | 10/23/2017 | All other required Final inspections are complete. (This is a computer generated result) | RICHB | RICHB | | B= | C | 5663303 |
COLARELLI CONSTRUCTION, INC. | B= | P | 10/17/2017 | Remodel complete pending Mechanical Final / plans reviewed onsite. Additional Inspections Required (computer generated): HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet. | RICHB | RICHB | | B= | P | 5658279 |
COLARELLI CONSTRUCTION, INC. | BFR | P | 08/29/2017 | Framing for new interior wall in kitchen (Rm 110) OK pending other roughs / plans reviewed onsite | RICHB | RICHB | | BFR | P | 5609635 |
COLARELLI CONSTRUCTION, INC. | BE | L | 08/28/2017 | Renewed at 8/28/2017 11:28:06 AM | TERRI | TERRI | | BE | L | 5608681 |
COLARELLI CONSTRUCTION, INC. | BSP | T | 07/21/2017 | PAID (REC#1441035) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: mechanical splice 7-21-17 | TCRIPPEN | TCRIPPEN | | BSP | T | 5572467 |
FRONT RANGE ELECTRIC OF CO, LLC | BSP | P | 07/21/2017 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | P | 5572279 |
COLARELLI CONSTRUCTION, INC. | BSP | P | 01/27/2017 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical | DALEH | DALEH | | BSP | P | 5400295 |
FRONT RANGE ELECTRIC OF CO, LLC | BSP | P | 01/27/2017 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Revised Panels and Load Summary. Revised Kitchen layout. | BERTHA | BERTHA | | BSP | P | 5400252 |
COLARELLI CONSTRUCTION, INC. | BSP | P | 01/27/2017 | PLAN SPLICE: (No Fee) by: TCRIPPEN for Plumbing: plumbing splice 1-17-17 | TCRIPPEN | TCRIPPEN | | BSP | P | 5400208 |
COLARELLI CONSTRUCTION, INC. | BSP | T | 01/27/2017 | PAID (REC#1398106) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Deleted closet | MICHAELA | MICHAELA | | BSP | T | 5400154 |
COLARELLI CONSTRUCTION, INC. | BFR | P | 12/02/2016 | 48" wall framing under hood OK pending other MEPs completed | DAN | DAN | | BFR | P | 5359385 |
FRONT RANGE ELECTRIC OF CO, LLC | E= | C | 10/06/2017 | only 220 outlet for fryer and 120 v recept under hood, recept protected by blank faced gfci, | GARYL | GARYL | | E= | C | 5648236 |
FRONT RANGE ELECTRIC OF CO, LLC | E= | R | 10/04/2017 | no power to the receptacle under the hood --- need some one to meet us here that knows where the outlets are fed from so we can reset breakers --- with this being turned into a kitchen gfci protection is now required --- called @ 3:20 no one showed up @ 4:00 | CRAIGS | CRAIGS | | E= | R | 5645371 |
FRONT RANGE ELECTRIC OF CO, LLC | ER+ | C | 08/30/2017 | 3- receptacles on grill wall / | ROB | ROB | | ER+ | C | 5611130 |
FRONT RANGE ELECTRIC OF CO, LLC | ER | C | 12/02/2016 | knee wall OK | CRAIGS | CRAIGS | | ER | C | 5359370 |
FRONT RANGE ELECTRIC OF CO, LLC | EP | P | 12/02/2016 | OK to have the high leg on c phase ( existing loads ) --- need labels stating which phase and what the voltage is to ground per 408.3 F 1 i will check for full voltage breakers on final --240.85( no 120/240 breakers ) have approved plans on site for final | CRAIGS | CRAIGS | | EP | P | 5359353 |
FRONT RANGE ELECTRIC OF CO, LLC | E= | R | 12/01/2016 | see service notes | CRAIGS | CRAIGS | | E= | R | 5358223 |
FRONT RANGE ELECTRIC OF CO, LLC | EP | R | 12/01/2016 | manager not in and no body knew anything about this --------- please meet me here | CRAIGS | CRAIGS | | EP | R | 5358203 |
HVAC SOLUTIONS, INC. | H= | C | 10/23/2017 | CORRECTIONS MADE | JERRYF | JERRYF | | H= | C | 5663302 |
HVAC SOLUTIONS, INC. | H= | R | 10/20/2017 | APPEARS THAT WRONG ADHESIVE WAS USED TO SECURE ROPE AND NEED INSTALL MANUAL FOR ROPE NEED ALL SCREWS AT TOP PLATE SEALED - WILL NEED SITE VISIT TO VERIFY ALL | JERRYF | JERRYF | | H= | R | 5661672 |
HVAC SOLUTIONS, INC. | H= | P | 10/18/2017 | NEED THE FOLLOWING GASKET INSTALLED AT GREASE FAN AND SOMEONE HAS TO CLAIM HOOD ON PERMIT - REST OK - INTERLOCKS ARE IN OPERATION | JERRYF | JERRYF | | H= | P | 5659770 |
HVAC SOLUTIONS, INC. | H= | P | 10/17/2017 | TAB REPORT RECEIVED STILL NEED OTHER CORRECTIONS MADE | JERRYF | JERRYF | | H= | P | 5657285 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 10/09/2017 | ALL TIE DOWNS AND GAS CONNECTIONS ARE COMPLETE | JERRYF | JERRYF | | H= | C | 5648912 |
OLSON PLUMBING & HEATING COMPANY | HI | C | 10/09/2017 | OK PIPING PER PLAN | JERRYF | JERRYF | | HI | C | 5648910 |
HVAC SOLUTIONS, INC. | H= | P | 10/05/2017 | NEED CONSULT WITH SENIOR INSPECTOR ON GREASE WRAP AT EXISTING DUCT - NEED TAB REPORT - ROOF INSPECTION AT FAN - CAP TOP OF HOOD WALL - REPLACE ALL 3/8" ALL THREAD PER MANUFACTURE SPECS. - VERIFY INTERLOCKS - (NOTES ADDED ON 10/6 FIRE WRAP OK) | JERRYF | JERRYF | | H= | P | 5646365 |
HVAC SOLUTIONS, INC. | H= | P | 10/04/2017 | SEE HEATING FINAL NOTES | JERRYF | JERRYF | | H= | P | 5644942 |
HVAC SOLUTIONS, INC. | H= | P | 10/04/2017 | WRONG CALL AHEAD NUMBER GIVEN - APPEARS 2 DIFFERENT MANUFACTURES GREASE WRAP INSTALLED - WILL NEED INSTALL MANUALS FOR BOTH TYPES FOR NEXT INSPECTION TO VERIFY THEY CAN BE INTERMINGLED - MAY NEED TO REMOVE 2ND LAYER TO VERIFY OR REPLACE - ARRIVED ONSITE AT 1:45 - NO HVAC SOLUTIONS PERSONNEL ONSITE | JERRYF | JERRYF | | H= | P | 5644937 |
HVAC SOLUTIONS, INC. | HD | P | 10/02/2017 | GREASE DUCT SMOKE TEST OK - OK TO WRAP WITH 2 LAYERS OF GREASE WRAP AS LONG AS PICTURES OF FIRST LAYER ARE AVAILABLE TO INSPECTOR. Wall behind hood that does not extend 18" above hood will need to be capped off and penetrations sealed liquid tight. Other previous inspector issues may still need to be addressed. | MARKB | MARKB | | HD | P | 5642023 |
HVAC SOLUTIONS, INC. | HD | R | 09/29/2017 | NEW GREASE DUCT WAS WELDED ON THE INSIDE WITH SLIP JOINTS - WILL NEED TO BE GROUND SMOOTH AND SMOKE TEST PERFORMED - NEED CONSULT WITH SENIOR INSPECTOR ON NEW HOOD WALL CONSTRUCTION WITH NO INSPECTION - HAS FRP BEHIND STAINLESS SURFACE - STOPPED INSPECTION MAY BE MORE | JERRYF | JERRYF | | HD | R | 5640589 |
HVAC SOLUTIONS, INC. | H16 | C | 05/01/2017 | SPOKE WITH RYAN FROM COLARELLI ABOUT THE ISLAND CANOPY HOOD. ALSO SPOKE WITH MOLLY RICE FROM CAPTIVE AIRE TO TRY TO RESOLVE SOME OF THE CODE INFRACTIONS WITH THE EXISTING TYPE ONE HOOD. THE HOOD HAS HAD SOME FACTORY SEALED SEAMS BREECH AND ARE NOW LEAKING GREASE INTO THE BACK AREA'S OF THE HOOD. THIS CANNOT BE FIELD REPAIRED BACK TO ORIGINAL. THERE IS A CHANCE THAT THESE AREAS COULD BE WELDED AND LIGHT CHECKED AFTER SOME DISCUSSION ABOUT HOW TO ACHIEVE THIS PROCESS. ALSO DISCUSSED THE 6 INCH CLEARANCE REQUIREMENT AROUND APPLIANCES. RYAN IS CONTACTING CAPTIVE AIR AGAIN TO IDENTIFY AREA OF CONTAINMENT WITHIN THIS HOOD. AFTER THAT INFORMATION IS OBTAINED MORE DISCUSSION WITH RBD ABOUT ADDING A DIVIDER OFF THE TOP OF THE STEM WALL TO TRY TO MEET THE EXCEPTION FOR 507.12 WILL HAVE TO BE ADDRESSED. AT THIS POINT THE EXISTING ISLAND HOOD HAS BEEN ALTERED AND DOES NOT APPEAR TO MEET THE UL-710 LISTING. THIS MEANS THAT ALL THE REQUIREMENTS OF IMC 507 MUST BE ACHIEVED. | JON | JON | | H16 | C | 5492614 |
HVAC SOLUTIONS, INC. | HD | P | 04/13/2017 | GREASE DUCT WRAP OK. SPOKE WITH CONTRACTOR ABOUT MEETING IMC 507.12. Still need to seal patches in curb and provide gasket under fan. ANSUL system or temp sensor not in place. Still waiting on manufacturer response about back of hood and lack of wall to ceiling. | MARKB | MARKB | | HD | P | 5474146 |
HVAC SOLUTIONS, INC. | HD | P | 04/12/2017 | GREASE DUCT WRAP - Need to get second layer up to bottom of curb and need to finish banding. | MARKB | MARKB | | HD | P | 5473015 |
HVAC SOLUTIONS, INC. | HD | P | 04/10/2017 | FIRST LAYER OF WRAP OK - Ensure banding is compliant with manufacturers install instructions by next inspection. Met with Robert (HVAC Solutions) on site - Removed half of double-island hood to end up with single-island hood. Contractor to verify with hood manufacturer about what needs to happen to hood for this process - how do we finish off back of hood?. Hood needs to comply with 2009 IMC 507.12 when equipment is installed. | MARKB | MARKB | | HD | P | 5470068 |
HVAC SOLUTIONS, INC. | HD | P | 04/06/2017 | GREASE DUCT LIGHT TEST COMPLETE FROM CURB DOWN TO HOOD - OK TO WRAP. Wall behind hood not installed. Will need clean able surface on end of hood 18" above hood. Need to fix screw holes in hood for ANSUL system. NOTE ADDED: 4' wall behind hood is what the plans call for | MARKB | MARKB | | HD | P | 5466665 |
HVAC SOLUTIONS, INC. | HD | P | 04/03/2017 | NEED TO INCLUDE FULL SCOPE OF WORK, GREASE DUCT. CANCELED ON SITE.. | LUKE | LUKE | | HD | P | 5463586 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 04/19/2017 | sink and recirc pump ok. | JOHNS | JOHNS | | P= | C | 5479668 |