PEAK PROFESSIONAL CONTRS INC | B= | C | 01/09/2017 | All other required Final inspections are complete. (This is a computer generated result) | JEREMYA | JEREMYA | | B= | C | 5384403 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 12/28/2016 | Building final OK pending mechanical. Additional Inspections Required (computer generated): AIR TECH MECHANICAL INC Mechanical Final Inspection is not Completed yet, ELECTRIC TECH INC. Electrical Final Inspection is not Completed yet, LANDMARK PLUMBING & HEATING, INC. Mechanical Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 5378517 |
LANDMARK PLUMBING AND HEATING, INC. | BSP | T | 12/22/2016 | PAID (REC#1391160) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 12-22-16 | TCRIPPEN | TCRIPPEN | | BSP | T | 5375426 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 11/14/2016 | Hard lid framing at bathrooms OK // Wall framing at kitchen OK // Only need wall at front door, all other framing complete | JEREMYA | JEREMYA | | BFR | P | 5343794 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 11/02/2016 | All framing and thermal OK | JEREMYA | JEREMYA | | BFR | P | 5334698 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 10/28/2016 | hood wall, pony wall ,office walls and half walls ok / bathroom walls ok pending other rough inspections / need inspect hard lids and soffits | ERICR | ERICR | | BFR | P | 5331252 |
PEAK PROFESSIONAL CONTRS INC | BFR | R | 10/24/2016 | exterior wall where they are installing type 1 hoods / need to call a mechanical inspector to check clearances | ERICR | ERICR | | BFR | R | 5326390 |
PEAK PROFESSIONAL CONTRS INC | BFT | C | 10/19/2016 | 5 footers 36"x36"x16" non structural ok | ERICR | ERICR | | BFT | C | 5322662 |
ELECTRIC TECH INC. | E= | C | 01/09/2017 | signs installed; ok | MATTHEW | MATTHEW | | E= | C | 5384402 |
ELECTRIC TECH INC. | E= | P | 12/21/2016 | install lockable switch for signs, finish running power to patio heaters, install 30 amp breaker for heaters | MATTHEW | MATTHEW | | E= | P | 5373482 |
ELECTRIC TECH INC. | ER | P | 12/14/2016 | ceilings in kitchen area only | GARYL | GARYL | | ER | P | 5367773 |
ELECTRIC TECH INC. | ES | C | 12/08/2016 | Commercial Service: 600 amp 3 phase 120/208 volt with ct metering.------------ Ok to set meter ----------- Notes: Also inspected MLO panel "P" | JOSEPH | JOSEPH | | ES | C | 5363257 |
ELECTRIC TECH INC. | ER | P | 11/08/2016 | kitchen soffit and bath hard lids (need access doors in both bathrooms, boxes 2 low and 1 high; 1 box to be removed in front bath; temp power) | MATTHEW | MATTHEW | | ER | P | 5338851 |
ELECTRIC TECH INC. | ER | P | 10/28/2016 | walls marked on plans | MATTHEW | MATTHEW | | ER | P | 5330574 |
ELECTRIC TECH INC. | ER | P | 10/21/2016 | hood wall, pony wall and 1/2 wall ok | MATTHEW | MATTHEW | | ER | P | 5324929 |
AIRTECH MECHANICAL, INC. | H= | C | 12/30/2016 | HEAT FINAL COMPLETE | LUKE | LUKE | | H= | C | 5379762 |
LANDMARK PLUMBING AND HEATING, INC. | H= | C | 12/28/2016 | ALL FINAL CONNECTIONS / REGS AND LABELS COMPETE | JERRYF | JERRYF | | H= | C | 5378598 |
LANDMARK PLUMBING AND HEATING, INC. | HC | C | 12/28/2016 | OK FOR METER RELEASE | JERRYF | JERRYF | | HC | C | 5378597 |
LANDMARK PLUMBING AND HEATING, INC. | HI | C | 12/28/2016 | PRESSURE TEST OK - PIPING PER PLAN - ALL REGS / LABELS AND VENTS COMPLETE | JERRYF | JERRYF | | HI | C | 5378593 |
AIRTECH MECHANICAL, INC. | HV | C | 12/28/2016 | ALL OK | JERRYF | JERRYF | | HV | C | 5378592 |
AIRTECH MECHANICAL, INC. | H= | P | 12/22/2016 | 2 LB GAS REGULATOR ON THE ROOF IS TO CLOSE TO MAKE UP AIR UNIT'S FRESH AIR, NEEDS TO BE 10' AWAY OR 3' ABOVE NEED TEST AND BALANCE REPORT.. NOTE: REST OK.. | LUKE | LUKE | | H= | P | 5375495 |
AIRTECH MECHANICAL, INC. | H= | P | 12/21/2016 | NO ONE ON SITE FOR FINAL INSPECTIONS WILL NEED SOMEONE TO SHOW ME THE HOOD INTERLOCKS AND ROOF THANK YOU.. | LUKE | LUKE | | H= | P | 5374217 |
LANDMARK PLUMBING AND HEATING, INC. | HI | P | 12/08/2016 | PRESSURE TEST OK ON INTERIOR COOK LINES ONLY - STILL NEED ALL EXTERIOR PIPING / MUA AND FINAL CONNECTIONS - BY FINAL NEED ALL 26 STUBS SHOWN ON PERMIT CURRENTLY SHOWS 9 STUBS | JERRYF | JERRYF | | HI | P | 5363792 |
AIRTECH MECHANICAL, INC. | HD | P | 11/17/2016 | GREASE LIGHT TEST COMPLETE ON HOOD NUMBER ONE AND HOOD NUMBER TWO OK TO WRAP. NOTE: WILL NEED STAINLESS STEEL BEHIND HOOD COMPLETE BY FINAL SMOOTH WASHABLE SURFACE.. | LUKE | LUKE | | HD | P | 5348020 |
AIRTECH MECHANICAL, INC. | HD | P | 11/15/2016 | FOUND HOLES ON THE FIRST TEST CONTRACTOR CANCELED ON SITE. | LUKE | LUKE | | HD | P | 5345027 |
AIRTECH MECHANICAL, INC. | HD | P | 11/03/2016 | GREASE DUCT LIGHT TEST PERFORMED AT SHOP - PICTURES WILL BE ADDED IN THE AM ON 11/4 | JERRYF | JERRYF | | HD | P | 5335113 |
AIRTECH MECHANICAL, INC. | HD | P | 11/02/2016 | LIGHT TEST PERFORMED AT AIR TECH SHOP PICTURES WILL ENTERED IN THE AM - JOINTS THAT NEED TO BE VERIFIED ARE PAINTED WITH GREEN PAINT - ((((OK TO WRAP CURB DROP))))) - REST OK | JERRYF | JERRYF | | HD | P | 5333990 |
AIRTECH MECHANICAL, INC. | HD | P | 10/26/2016 | HOOD WALL OK, OK TO COVER. | NANCY | NANCY | | HD | P | 5328728 |
AIRTECH MECHANICAL, INC. | HD | P | 10/25/2016 | INSTALL CHANNEL AND SHEET ROCK IN BETWEEN METAL STUDS ON OUTSIDE HOOD WALL. CALL FOR INSPECTION BEFORE COVERING. | NANCY | NANCY | | HD | P | 5326869 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 12/23/2016 | | JOEL | JOEL | | P= | C | 5376313 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 12/22/2016 | need plans revised as noted, no hot water, support indirect waste drains, plug c/o's need access to t&p pop offs both tankless units remove test cap on vent | TIM | TIM | | P= | P | 5374607 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 10/27/2016 | less toilet rough, had to open floor to move all risers, need plan revised to show recurc. piping changes | TED | TED | | PTO | P | 5329835 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 10/26/2016 | need recurc. water line run, need to complete bathrooms | TED | TED | | PTO | P | 5328822 |