COLORADO COMMERCIAL CONSTRUCTION, INC. | B= | C | 04/13/2017 | item corrected | DANE | DANE | | B= | C | 5473636 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | B= | P | 04/10/2017 | Temp CO: pending building final ( Expires: 5/10/2017 12:00:00 AM) | MINDY | MINDY | | B= | P | 5469482 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | B= | P | 04/07/2017 | need coat hooks in both restrooms at 48" max above the floor -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet, REFRIGERATION PLUS, LLC Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5468179 |
EL PASO ELECTRIC, LLC. | BSP | T | 04/06/2017 | PAID (REC#1414948) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: To series rate G1 and G2 panels | SHELBY | SHELBY | | BSP | T | 5466092 |
NIELSEN MECHANICAL CONTRACTORS, INC. | BSP | T | 04/05/2017 | PAID (REC#1415292) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: delta 7 | DALEH | DALEH | | BSP | T | 5465680 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | BSP | P | 03/27/2017 | no inspection needed for acoustical non-rated ceiling / did pre-walk of restrooms for final with contractor / rear grab bars in both restrooms not correct - flush handle at women's restroom is on wrong side | DANE | DANE | | BSP | P | 5456427 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | BSP | P | 12/30/2016 | PLAN SPLICE: (No Fee) by: DANM for Construction: Structural engineer letter stating roof structure is adequate for new mechanical | DANM | DANM | | BSP | P | 5379844 |
NIELSEN MECHANICAL CONTRACTORS, INC. | BSP | P | 12/30/2016 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical | JUSTINC | JUSTINC | | BSP | P | 5379840 |
EL PASO ELECTRIC, LLC. | BSP | P | 12/30/2016 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Added cooler equipment, revised kitchen. | BERTHA | BERTHA | | BSP | P | 5379816 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | BFR | P | 12/20/2016 | grab bar backing and water heater platform OK / framing OK pending other roughs / training with Justin L | DANE | DANE | | BFR | P | 5372636 |
LANDMARK PLUMBING AND HEATING, INC. | BSP | T | 12/19/2016 | PAID (REC#1390435) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 12-19-16 | TCRIPPEN | TCRIPPEN | | BSP | T | 5371443 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | BFR | P | 12/08/2016 | need to complete core and shell permit / all interior framing OK except need platform for water heater and need backing for grab bars / discussed accessibility with contractor | DANE | DANE | | BFR | P | 5363873 |
EL PASO ELECTRIC, LLC. | E= | C | 04/07/2017 | | BRET | BRET | | E= | C | 5468218 |
EL PASO ELECTRIC, LLC. | E= | P | 04/06/2017 | have paper work on site for series rating, install lable in disconnect on what type fuss is required for series rating | BRET | BRET | | E= | P | 5467010 |
EL PASO ELECTRIC, LLC. | E= | P | 04/05/2017 | roof only | BRET | BRET | | E= | P | 5465822 |
EL PASO ELECTRIC, LLC. | ER | C | 03/07/2017 | | BRET | BRET | | ER | C | 5433711 |
EL PASO ELECTRIC, LLC. | E= | P | 02/16/2017 | kitchen and dish area receptacles only. | BRET | BRET | | E= | P | 5417609 |
EL PASO ELECTRIC, LLC. | ER | P | 01/25/2017 | walls complete | BRET | BRET | | ER | P | 5398425 |
EL PASO ELECTRIC, LLC. | ER | P | 12/27/2016 | marked on old plans ----------- | CRAIG | CRAIG | | ER | P | 5376811 |
EL PASO ELECTRIC, LLC. | ES | P | 12/14/2016 | Commercial Service: 2 200 amp meters for 110 panel a and panel b need both meters set. | BRET | BRET | | ES | P | 5367793 |
EL PASO ELECTRIC, LLC. | ER | P | 11/16/2016 | wall behind cooler only to start cooler installation. | BRET | BRET | | ER | P | 5346156 |
EL PASO ELECTRIC, LLC. | ER | P | 11/15/2016 | ceiling ok | BRET | BRET | | ER | P | 5344885 |
EL PASO ELECTRIC, LLC. | ESL | P | 11/10/2016 | 1" and 2" pvc for data ------------ 2 - 1" pvc for power --------- 15 - 3/4" pvc for power | CRAIG | CRAIG | | ESL | P | 5341730 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | C | 04/12/2017 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 5472552 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 04/07/2017 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5468532 |
REFRIGERATION PLUS, LLC | H= | C | 04/07/2017 | REFRIGERATION FINAL OK. | NANCY | NANCY | | H= | C | 5468528 |
LANDMARK PLUMBING AND HEATING, INC. | H= | C | 04/06/2017 | GAS/WATER HEATER VENT FINAL OK. | NANCY | NANCY | | H= | C | 5467176 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 04/05/2017 | SEAL METAL TO WALL ABOVE HOOD. CLEAN TOP OF HOOD. INSTALL EQUIPMENT UNDER HOOD. PROVIDE TEST AND BALANCE REPORT. INTERLOCKS OK. | NANCY | NANCY | | H= | P | 5465883 |
LANDMARK PLUMBING AND HEATING, INC. | HV | C | 03/23/2017 | WATER HEATER VENT OK. | NANCY | NANCY | | HV | C | 5454526 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 03/21/2017 | COMBUSTIBLE MATERIALS ON TOP OF HOOD. METAL ON HOOD WALL ABOVE CEILING NOT PROPERLY SEALED. SUPPLY, RETURN AND EXHAUST DUCTS ABOVE CEILINGS OK. WHAT IS THE 24 X 12 TRANSFER SHOWN ON PLANS FOR? ON FUTURE JOBS PLEASE CALL FOR ABOVE CEILING INSPECTIONS BEFORE ALL THE HARD LIDS GET INSTALLED. | NANCY | NANCY | | HD | P | 5452025 |
REFRIGERATION PLUS, LLC | H= | P | 03/20/2017 | PERMANENTLY LABEL CONDENSER WITH UNIT 110. WOOD SUPPORTS UNDER CONDENSER APPEAR TO BE PINE, NEED TO BE RED WOOD OR PRESSURE TREATED. REST OK. | NANCY | NANCY | | H= | P | 5446265 |
LANDMARK PLUMBING AND HEATING, INC. | HC | C | 03/01/2017 | 690,000 BTU'S ADDED TO EXISTING METER. | NANCY | NANCY | | HC | C | 5428968 |
LANDMARK PLUMBING AND HEATING, INC. | HI | P | 03/01/2017 | NEED REVISED APPROVED PRINTS SHOWING ACTUAL GAS LINES INSTALLED ON SITE. ADD WATER HEATER VENT ONTO SCOPE OF WORK AND CALL FOR INSPECTION. NEED WATER HEATER INSTALLATION INSTRUCTIONS ON SITE. 10 LB TEST OK. | NANCY | NANCY | | HI | P | 5428962 |
REFRIGERATION PLUS, LLC | HRP | C | 02/21/2017 | TWO 200 LB TESTS OK. NO ROOF YET. NO REFRIGERATION LEAKAGE ALARMS REQUIRED. | NANCY | NANCY | | HRP | C | 5420810 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 02/01/2017 | MANUFACTURER GREASE DUCT ABOVE HOOD OK. WILL NEED TO SEE INSIDE OF GREASE DUCT FROM CURB LOOKING DOWN. MAKE-UP AIR ABOVE HOOD OK. SEAL GAPS BETWEEN SHEETS OF STAINLESS ON WALL BEHIND AND ABOVE HOOD. WILL STILL NEED TO SEE ABOVE HOOD AT FUTURE INSPECTION, TOP OF HOOD NEEDS 18 INCH CLEARANCE TO COMBUSTIBLES. | NANCY | NANCY | | HD | P | 5404727 |
REFRIGERATION PLUS, LLC | HRP | L | 01/27/2017 | DOORS LOCKED AT 4:40 PM. PLEASE GIVE THE LOCK BOX CODE FOR NEXT INSPECTION. | NANCY | NANCY | | HRP | L | 5400985 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 01/25/2017 | HOOD WALL OK. OK TO COVER PER MECHANICAL ONLY. | NANCY | NANCY | | HD | P | 5398957 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 01/19/2017 | TYPE I HOOD IS LISTED AS NEEDING 18 INCH CLEARANCE TO COMBUSTIBLES ON THE BACK SIDE. HOOD WALL MUST BE FRAMED WITH METAL STUDS, SHEET ROCK IS OK TO INSTALL ON THE METAL STUDS. NO COMBUSTIBLE MATERIALS SUCH AS PVC IS ALLOWED IN THE WALL BEHIND THE HOOD 18 INCHES IN ALL DIRECTIONS FROM THE HOOD. ALSO MUST MAINTAIN REQUIRED CLEARANCE TO COMBUSTIBLES FROM THE EQUIPMENT BEING SET UNDER THE HOOD. | NANCY | NANCY | | HD | P | 5392486 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 12/07/2016 | NEED REFRIGERATION CONTRACTOR ATTACHED TO PERMIT. CONTRACTOR INSTALLING WATER HEATER VENT NEEDS TO ADD IT TO THEIR SCOPE OF WORK AND CALL FOR INSPECTION WHEN READY. ROUGH SUPPLY AND RETURN AIR DUCTS ABOVE CEILING AND EXPOSED OK. TWO BATH EXHAUST OK. NO EF-3 YET. DON'T FORGET THE 24X12 TRANSFER GRILL BY FINAL. FLEX INSTALLED, NO DIFFUSERS YET. | NANCY | NANCY | | HD | P | 5362696 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 04/07/2017 | ok. corrections made. | JOHNS | JOHNS | | P= | C | 5467794 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 04/06/2017 | NEED HAMMER ARRESTERS AT DISH X 2 , NEED TO CORRECT 3 COMP DRAIN AT BAR , REST TO PLAN | GABE | GABE | | P= | P | 5466690 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 01/25/2017 | NOTE : ALL DWV AND WATER ON TEST , NAIL PROTECTION IN PLACE , BATH GROUPS OK . ALL CORRECTIONS MADE | GABE | GABE | | PTO | C | 5398443 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 01/24/2017 | LEAK IN WATER LINE IN BATH GROUP WALL , NEED NAIL PLATES AT BOTH KITCHEN WALLS , SET CLOSET FLANGES , RETEST ALL WATER AND DWV IN BATH WALL | GABE | GABE | | PTO | P | 5396995 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 12/27/2016 | pony wall ok (aav at final in wall) | TED | TED | | PTO | P | 5377130 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 11/02/2016 | SANITARY AND GREASE WASTE TO PLAN , ON TEST | GABE | GABE | | PB | C | 5334389 |