PEAK PROFESSIONAL CONTRS INC | B= | C | 03/14/2017 | All other required Final inspections are complete. (This is a computer generated result) | NICK | NICK | | B= | C | 5440356 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 03/06/2017 | Building final OK pending all other finals complete. Additional Inspections Required (computer generated): ARTISAN PIPE SYSTEMS, INC. Plumbing Final Inspection is not Completed yet, RIAL HEATING & AIR COND, INC Mechanical Final Inspection is not Completed yet. | NICK | NICK | | B= | P | 5432678 |
PEAK PROFESSIONAL CONTRS INC | BFR | C | 03/06/2017 | Stamped letter from architect on file for all through penetrations | NICK | NICK | | BFR | C | 5432677 |
PEAK PROFESSIONAL CONTRS INC | BSP | P | 01/27/2017 | Detail for 1hr rated soffit on file for corridor, assemble per design OK / Need through penetration listings for all penetrations in scope of work | NICK | NICK | | BSP | P | 5400470 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 01/09/2017 | inspected attachment of 5/8 type x gypsum board to rated corridor wall per 720.1(2)13-1.1 ok / need detail for horizontal assembly at rear office exit door in to rated corridor wall / need penetration sealing details for penetrations through rated corridor walls/ need to seal all petrations for this scope of work | ERICR | ERICR | | BFR | P | 5384498 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 12/29/2016 | received Architects letter on changing type d wall 1 hr rating prescriptive method from 09 ibc 720.1(2)13-1.3 using nails to method 09 IBC 720.1(2)13-1.1 using screws / framing of office walls ok / 1 hr corridor wall framing to deck ok / existing 1 hr corridor walls do not got to deck need to know if grid ceiling in corridor is rated / reviewed accessible elements in breakroom and other counter tops being called to 34" maximum height/ need to complete other rough inspections | ERICR | ERICR | | BFR | P | 5378890 |
EL PASO ELECTRIC, LLC. | E= | C | 02/24/2017 | | BRIAN | BRIAN | | E= | C | 5424021 |
EL PASO ELECTRIC, LLC. | ER | C | 02/24/2017 | ceilings--ok | BRIAN | BRIAN | | ER | C | 5424011 |
EL PASO ELECTRIC, LLC. | ER | P | 01/05/2017 | walls --ok | BRIAN | BRIAN | | ER | P | 5382833 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 03/07/2017 | MECHANICAL FINAL OK. TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 5432954 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 03/03/2017 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT, SEE NOTE 4 ON SHEET M1.0 REGARDING OUTSIDE AIR. | NANCY | NANCY | | H= | P | 5430722 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | R | 03/02/2017 | CEILING IS COVERED PER PREVIOUS NOTES UNABLE TO VERIFY FINAL CONNECTIONS AT ALL SA GRILLES - PER PREVIOUS NOTES NEED PLAN REVISED DELETING ALL SOUND BOOTS AT RA GRILLES - RESEARCH DOOR HAS BEEN UNDER CUT AND IS OK | JERRYF | JERRYF | | H= | R | 5430176 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 03/01/2017 | CEILING CLOSED UP PRIOR TO MECHANICAL FINAL INSPECTION. RESEARCH OFFICE DOOR NOT UNDERCUT. IF NOT INSTALLING TRANSFER AIR DUCTS WITH 1 INCH LINER NEED REVISED/APPROVED PRINTS. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5427973 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 02/08/2017 | ROUGH DUCTS ABOVE CEILING OK INCLUDING EXHAUST DUCT. NO FLEX, DIFFUSERS OR BATH EXHAUST FAN YET. | NANCY | NANCY | | HD | P | 5409695 |
ARTISAN PIPE SYSTEMS, INC. | P= | C | 03/14/2017 | correction made. | TAYLOR | TAYLOR | | P= | C | 5440355 |
ARTISAN PIPE SYSTEMS, INC. | P= | P | 03/03/2017 | need to install dishwasher to verify hi- loop, rest ok. | TAYLOR | TAYLOR | | P= | P | 5430809 |
ARTISAN PIPE SYSTEMS, INC. | PTO | C | 01/04/2017 | | TIM | TIM | | PTO | C | 5381714 |