COLORADO COMMERCIAL CONSTRUCTION, INC. | B= | C | 05/03/2017 | | MINDY | MINDY | | B= | C | 5494493 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | B= | P | 04/12/2017 | Temp CO: pending building and mechanical finals ( Expires: 5/12/2017 12:00:00 AM) | MINDY | MINDY | | B= | P | 5472846 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | B= | P | 04/07/2017 | final OK pending other finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), DREAM CATCHER MECHANICAL Mechanical Final Inspection is not Completed yet, EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5468174 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | BSP | P | 04/06/2017 | series rate panel A | SHELBY | SHELBY | | BSP | P | 5466113 |
NIELSEN MECHANICAL CONTRACTORS, INC. | BSP | T | 04/05/2017 | PAID (REC#1414738) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: delta 3 | DALEH | DALEH | | BSP | T | 5465689 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | BSP | P | 03/31/2017 | no inspection required for acoustical ceiling grid / still need engineering for water heater shelf framing to complete framing | DANE | DANE | | BSP | P | 5461902 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | BSP | L | 03/27/2017 | met contractor on site - inspection called on wrong permit | DANE | DANE | | BSP | L | 5456435 |
LANDMARK PLUMBING AND HEATING, INC. | BSP | T | 01/27/2017 | PAID (REC#1398058) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 1-27-17 | TCRIPPEN | TCRIPPEN | | BSP | T | 5400139 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | BSP | T | 01/27/2017 | PAID (REC#1398061) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Relocated office room | MICHAELA | MICHAELA | | BSP | T | 5400129 |
NIELSEN MECHANICAL CONTRACTORS, INC. | BSP | P | 01/27/2017 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical | DALEH | DALEH | | BSP | P | 5400121 |
EL PASO ELECTRIC, LLC. | BSP | P | 01/27/2017 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Revised Office 108 and added warmers. | BERTHA | BERTHA | | BSP | P | 5400106 |
COLORADO COMMERCIAL CONSTRUCTION, INC. | BFR | P | 01/26/2017 | need engineering for hard lid shelf for water heater / need to splice in changes to layout at office where panels have moved and created hall to rear door / all other light gauge framing OK pending other rough inspections / discussed accessible elements with contractor | DANE | DANE | | BFR | P | 5399608 |
EL PASO ELECTRIC, LLC. | E= | C | 04/07/2017 | | BRET | BRET | | E= | C | 5468223 |
EL PASO ELECTRIC, LLC. | E= | P | 04/06/2017 | need paper work on series rating, install label in disconnect on what fuss is requied for series rating | BRET | BRET | | E= | P | 5467001 |
EL PASO ELECTRIC, LLC. | E= | P | 04/05/2017 | AIC 14 k at panels 10 k breakers installed. label AIC at panels. breaker for condenser oversized. fountain drink breakers label kitchen gfci. note service disconnect labels on growlers permit. | BRET | BRET | | E= | P | 5465974 |
EL PASO ELECTRIC, LLC. | ER | C | 03/30/2017 | suspended ceiling ok | BRET | BRET | | ER | C | 5461024 |
EL PASO ELECTRIC, LLC. | ER | R | 03/29/2017 | have contractor remove boarder tiles cant install them if fixtures, diffusers and sprinkler heads fill all the other areas of ceiling | BRET | BRET | | ER | R | 5459337 |
EL PASO ELECTRIC, LLC. | ES | P | 02/16/2017 | Commercial Service: need meter set for 200 amp disconnect for unit 130. note to contractor 10 k breaker installed need 22 k | BRET | BRET | | ES | P | 5417626 |
EL PASO ELECTRIC, LLC. | ER | P | 01/31/2017 | open ceiling area ok | BRET | BRET | | ER | P | 5402992 |
EL PASO ELECTRIC, LLC. | ER | P | 01/25/2017 | walls, soffit and hard lids. | BRET | BRET | | ER | P | 5398409 |
EL PASO ELECTRIC, LLC. | ESL | C | 01/04/2017 | | BRET | BRET | | ESL | C | 5382727 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | C | 05/01/2017 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 5492632 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 04/28/2017 | PROPERLY ATTACH GUY WIRES TO STRUCTURE. | NANCY | NANCY | | H= | P | 5490871 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 04/12/2017 | TEST AND BALANCE REPORT RECEIVED. SEE PREVIOUS INSPECTION COMMENTS FOR FINAL REQUIREMENTS. | NANCY | NANCY | | H= | P | 5472560 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 04/07/2017 | TOP OF HOOD OK. STILL NEED OTHER CORRECTIONS, TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5468537 |
DREAM CATCHER MECHANICAL | H= | C | 04/07/2017 | REFRIGERATION FINAL OK. | NANCY | NANCY | | H= | C | 5468533 |
LANDMARK PLUMBING AND HEATING, INC. | H= | C | 04/06/2017 | GAS/WATER HEATER VENT FINAL OK. | NANCY | NANCY | | H= | C | 5467175 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 04/05/2017 | INSTALL ALL EQUIPMENT UNDER HOOD. SECURE HOOD SIDE PANEL. CLEAN TOP OF HOOD. EF-3 AND EF-4 WITHIN 10 FEET OF MAKE-UP AIR INTAKE. PROVIDE TEST AND BALANCE REPORT. INTERLOCKS OK. | NANCY | NANCY | | H= | P | 5465888 |
LANDMARK PLUMBING AND HEATING, INC. | HV | C | 03/16/2017 | WATER HEATER VENT OK. | NANCY | NANCY | | HV | C | 5443207 |
DREAM CATCHER MECHANICAL | HRP | C | 03/16/2017 | THREE 300 LB TESTS OK. | NANCY | NANCY | | HRP | C | 5443206 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 03/16/2017 | MAKE-UP AIR: SEAL DUCT CONNECTIONS AT HOOD. REST OK, OK TO WRAP. GREASE DUCTS: GREASE DUCTS INSIDE OF BUILDING OK, WILL NEED TO SEE INSIDE OF DUCTS FROM ROOF. GRID CEILING: SUPPLY AND EXHAUST ABOVE GRID CEILING OK. EXPOSED: EXPOSED DUCTS OK. HOOD WALL: SEAL ALL LAPS. GAPS AND TOP OF METAL TO WALL ABOVE HOOD. SEE EXHAUST HOOD SCHEDULE FOR INTERLOCKS. ALARM REQUIRED FOR C02 BY FINAL. NO ROOF TODAY. NOTE: MAKE-UP AIR UNIT HAS FILL AND DRAIN KIT. | NANCY | NANCY | | HD | P | 5443203 |
LANDMARK PLUMBING AND HEATING, INC. | HV | P | 03/14/2017 | SUPPORT HORIZONTAL VENT PIPES EVERY THREE FEET PER MANUFACTURERS INSTRUCTIONS. | NANCY | NANCY | | HV | P | 5440892 |
LANDMARK PLUMBING AND HEATING, INC. | HC | C | 03/13/2017 | 1,139,000 BTU'S ADDED TO EXISTING METER. | NANCY | NANCY | | HC | C | 5439110 |
LANDMARK PLUMBING AND HEATING, INC. | HI | P | 03/13/2017 | NEED REVISED/APPROVED PRINTS SHOWING ACTUAL GAS LINES INSTALLED ON SITE. 10 LB TEST OK. FOR FINAL INSTALL ANSUL VALVE AND COMPLETE GAS TO MAKE-UP AIR UNIT. | NANCY | NANCY | | HI | P | 5439107 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 01/26/2017 | HOOD WALL OK, OK TO COVER PER MECHANICAL ONLY. SUPPLY ABOVE BATHROOM HARD LIDS OK. | NANCY | NANCY | | HD | P | 5399961 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 01/25/2017 | SEAL SUPPLY RUN OVER TOP OF BATHROOM HARD LIDS. BATH EXHAUST OK. | NANCY | NANCY | | HD | P | 5398965 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 04/05/2017 | NOTE : ALL PUBLIC LAVS TEMPERED , HAMMER ARRESTER ABOVE 3 COMP . ALL TO PLAN | GABE | GABE | | P= | C | 5465732 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 03/31/2017 | water to mau | TED | TED | | PTO | C | 5461741 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 01/27/2017 | PLAN SPLICE VERIFIED , WATER ON TEST , CHECK TIE IN AT FINAL AT WATER HEATER Joel changed to partial to splice plans for water to mau and inspection | GABE | GABE | | PTO | P | 5400486 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 01/24/2017 | ALL WATER ON TEST , NEW PLAN TO SPLICE WITH NEW WATER PIPING , RE TEST ALL NEW WATER , FROM KITCHEN LOW WALL TO REAR OF UNIT OK | GABE | GABE | | PTO | P | 5396923 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 01/20/2017 | ALL DWV ON TEST , WATER ON TEST FROM COLUMN D TO B ONLY , ALL TO PLAN | GABE | GABE | | PTO | P | 5394407 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 01/12/2017 | WOMAN'S LAV DWV AND WATER WALL ONLY , ON TEST TO PLAN | GABE | GABE | | PTO | P | 5387419 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 12/29/2016 | CORRECTIONS MADE , BASE ON TEST TO PLAN | GABE | GABE | | PB | C | 5379150 |
LANDMARK PLUMBING AND HEATING, INC. | PB | P | 12/28/2016 | grease drain test and design ok | TED | TED | | PB | P | 5378398 |