SHARP GENERAL CONTRACTORS, INC | B= | C | 04/03/2017 | All other required Final inspections are complete. (This is a computer generated result) | BOBF | BOBF | | B= | C | 5463267 |
SHARP GENERAL CONTRACTORS, INC | B= | P | 03/29/2017 | pending elec and plumbing finals building okay. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: ckauffman@tri-lakesfire.com or 484-0911), ELECTRIC TECH INC. Electrical Final Inspection is not Completed yet, LANDMARK PLUMBING & HEATING, INC. Plumbing Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 5458916 |
ELECTRIC TECH INC. | BSP | T | 03/22/2017 | PAID (REC#1411645) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Revise xray feeder | SHELBY | SHELBY | | BSP | T | 5452264 |
AIRTECH MECHANICAL, INC. | BSP | T | 03/21/2017 | PAID (REC#1411304) PLAN SPLICE FEE: $50 by: DALEH for Mechanical | DALEH | DALEH | | BSP | T | 5451174 |
SHARP GENERAL CONTRACTORS, INC | BFR | P | 02/07/2017 | REVIEWED ACCESSIBLE ELEMENTS / need elec attached to permit / pending completion of other required inspections, frame okay | BOBF | BOBF | | BFR | P | 5408497 |
ELECTRIC TECH INC. | E= | C | 03/29/2017 | | CRAIG | CRAIG | | E= | C | 5459223 |
ELECTRIC TECH INC. | E= | P | 03/28/2017 | install outlet in second patient office -------- gfi outlet in break rm under sink | CRAIG | CRAIG | | E= | P | 5458127 |
ELECTRIC TECH INC. | ER | P | 03/20/2017 | above ceiling ok | CRAIG | CRAIG | | ER | P | 5445525 |
ELECTRIC TECH INC. | ER | R | 03/17/2017 | field cancelled | CRAIG | CRAIG | | ER | R | 5444169 |
ELECTRIC TECH INC. | ER | P | 02/08/2017 | walls only marked on plans note hospital grade mc | CRAIG | CRAIG | | ER | P | 5409908 |
AIRTECH MECHANICAL, INC. | H= | C | 03/23/2017 | MECHANICAL FINAL OK. REVISED TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 5453464 |
AIRTECH MECHANICAL, INC. | H= | P | 03/20/2017 | TEST AND BALANCE REPORT RECEIVED. OUTSIDE AIR READINGS OUTSIDE OF +/- 10% ALLOWED. DESIGN OUTSIDE AIR SHOWN ON PAGE 11 IS NOT CORRECT. | NANCY | NANCY | | H= | P | 5445131 |
AIRTECH MECHANICAL, INC. | H= | P | 03/17/2017 | REVISE FURNACE SCHEDULE. FURNACES ARE LENNOX G500H-48C-110-02, 80% EFFICIENT. NO CONCENTRIC VENT KIT REQUIRED. CONDENSATE GOES TO FLOOR DRAIN IN MECHANICAL ROOM. INSTALL SMOKE DETECTION OR REMOVE NOTE 7. ALSO REVISE CONDENSER TO HS29-048-1P. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5444807 |
AIRTECH MECHANICAL, INC. | H= | P | 03/14/2017 | CANCELED PER CONTRACTORS REQUEST. | NANCY | NANCY | | H= | P | 5440597 |
AIRTECH MECHANICAL, INC. | HD | P | 02/23/2017 | ROUGH DUCTS ABOVE CEILING OK. INSTALL ALL GRILLS AND DIFFUSERS WHEN GRID IS COMPLETE. INSTALL T-STAT AS PER PRINT. | NANCY | NANCY | | HD | P | 5423634 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 03/29/2017 | tenant finish | TED | TED | | P= | C | 5459321 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 02/16/2017 | check water hammers for 2 bathrooms at final | TED | TED | | PTO | C | 5417167 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 01/26/2017 | NOTE : BASE ON TEST . NEED TO RED LINE / SPLICE PLANS TO SHOW LAYOUT BY FINAL | GABE | GABE | | PB | C | 5399530 |