HOMEOWNER | B= | C | 08/10/2020 | building final OK pending P= | LONNYS | LONNYS | | B= | C | 6666823 |
HOMEOWNER | BE | L | 08/19/2019 | Renewed for $250.00 at 8/19/2019 10:47:50 AM (Receipt#1623246) | JANE | JANE | | BE | L | 6305228 |
HOMEOWNER | BFR | P | 12/05/2017 | Frame okay // Complete MEP's | SHAUN | SHAUN | | BFR | P | 5702536 |
HOMEOWNER | BFR | P | 11/27/2017 | Need to complete draftstop and fireblock at drop down ceiling / Remove floating wall blocks // Reviewed egress ladder requirements, smoke and CO requirements to be checked at final with homeowner | JUSTINL | JUSTINL | | BFR | P | 5695079 |
HOMEOWNER | BE | C | 10/30/2017 | | GITA | GITA | | BE | C | 5671397 |
HOMEOWNER | E= | C | 02/12/2020 | | BRETC | BRETC | | E= | C | 6480496 |
HOMEOWNER | E= | R | 02/10/2020 | still need all shop outlets gfci protected, mech rm outlets need 15 amp gfci/afci cb, | JOHNN | JOHNN | | E= | R | 6477655 |
HOMEOWNER | E= | R | 02/07/2020 | Need Arc shields / Wire shop lights correctly / Remove receptacle behind bath tub / GFCI all of shop receptacles / Wire fire place look @ picture / Need cover plates on devices / Rest OK / | CRAIGS | CRAIGS | | E= | R | 6476890 |
HOMEOWNER | E= | L | 02/06/2020 | no one home, | JOHNN | JOHNN | | E= | L | 6475834 |
HOMEOWNER | ER | C | 12/08/2017 | Discussed AFCI/GFCI/TR requirements with owner. / | JOHNN | JOHNN | | ER | C | 5707494 |
HOMEOWNER | ER | R | 12/06/2017 | bath room: need separate 20 amp circuit for lights and outlets, staple nm cable thru out, Discussed AFCI/GFCI/TR requirements with owner. / | JOHNN | JOHNN | | ER | R | 5704840 |
HOMEOWNER | ER | R | 12/05/2017 | grd all 4/0 boxes, grd fan box and add connector, bath rm: separate 20 amp and 15 amp wiring, add outlet with in 3' of sink, staple nm cable thru out, move closet lights per code, | JOHNN | JOHNN | | ER | R | 5702794 |
HOMEOWNER | ER | R | 11/27/2017 | need grd terminal on all 4/0 boxes,and grd connected, check 6'/12' outlet spacing thru out, left of wet bar: mix of 14awg and 12 awg, need 20 amp circuit for bath outlet, grd fireplace and install plate, need proper nm cable connectors at panels, staple all nm cable, remove all devices for inspection, complete re inspect, | JOHNN | JOHNN | | ER | R | 5694461 |
HOMEOWNER | ER | P | 05/08/2017 | exterior basement walls only,-------------------------need outlet per spacing,left of slider,check on next rough | JOHNN | JOHNN | | ER | P | 5498809 |
HOMEOWNER | H= | C | 02/14/2020 | NOTE/ HIGH/LOW COMBUSTION AIR / | DAVIDH | DAVIDH | | H= | C | 6483089 |
WESTERN FIREPLACE SUPPLY, INC. | H= | C | 02/14/2020 | NOTE/ FIREPLACE COMPLETE | DAVIDH | DAVIDH | | H= | C | 6483088 |
WESTERN FIREPLACE SUPPLY, INC. | HV | C | 02/10/2020 | NOTE/ BASEMENT FIREPLACE CLEARANCE TO COMBUSTIBLES AND VENT TERMINATION OK / | DAVIDH | DAVIDH | | HV | C | 6478099 |
WESTERN FIREPLACE SUPPLY, INC. | HI | C | 02/10/2020 | note sniffed joints to fireplace | DAVIDH | DAVIDH | | HI | C | 6478093 |
HOMEOWNER | HSP | P | 08/19/2019 | GAS TO DOWNSTAIRS FIREPLACE WAS INSPECTED ON K65048. DISCUSSED WHAT CUSTOMER NEEDS FOR FINAL MECHANICAL INSPECTION | JON | JON | | HSP | P | 6305305 |
HOMEOWNER | H= | P | 05/30/2018 | PENDING FIRE PENDING F/P MANTEL AND HI/LO TRANSFER GRILLS
| DAVIDH | DAVIDH | | H= | P | 5859217 |
HOMEOWNER | HRR | C | 12/05/2017 | | DAVIDH | DAVIDH | | HRR | C | 5702906 |
HOMEOWNER | HRR | P | 11/27/2017 | PROTECT FLEX THROUGH FIREPLACE CABINET. SEAL RETURN AIR IN WORKSHOP CEILING. NEED RETURN AIR IN COMMON ROOM. NEED EXHAUST DUCT COMPLETED IN BATHROOM. ALSO NEED TO ADD F/P TO PERMIT NOTES: FINISHED BASEMENT, DIRECT VENT FURNACE, 6" OUTSIDE AIR TO RETURN. | DAVIDH | DAVIDH | | HRR | P | 5694848 |
HOMEOWNER | P= | C | 08/10/2020 | | SAMH | SAMH | | P= | C | 6666730 |
HOMEOWNER | PTO | C | 12/05/2017 | VTR for all bathrooms, aav's at both sinks, add 1 sink to scope of work, note: check mixing at tub by final. | TAYLOR | TAYLOR | | PTO | C | 5702513 |
HOMEOWNER | PTO | R | 11/27/2017 | not ready. | TAYLOR | TAYLOR | | PTO | R | 5694438 |