SEVEN SUMMITS CONSTRUCTION LLC | B= | C | 10/03/2017 | Fire Doors Installed | JEREMYA | JEREMYA | | B= | C | 5642949 |
SEVEN SUMMITS CONSTRUCTION LLC | BSP | P | 10/02/2017 | Bar joist penetrations complete per approved detail | JEREMYA | JEREMYA | | BSP | P | 5641827 |
SEVEN SUMMITS CONSTRUCTION LLC | BSP | P | 09/26/2017 | Fire caulk at bar joist per approved detail at north skylight ONLY // Need details for protection around rated door in wall | JEREMYA | JEREMYA | | BSP | P | 5636991 |
SEVEN SUMMITS CONSTRUCTION LLC | BSP | P | 09/15/2017 | PLAN SPLICE: (No Fee) by: MICHAELA for Construction: Firestop detail | MICHAELA | MICHAELA | | BSP | P | 5627605 |
SEVEN SUMMITS CONSTRUCTION LLC | BSP | P | 08/14/2017 | Drywall at wall complete pending assembly for all bar joist penetrations // Secondary, non-rated wall complete | JEREMYA | JEREMYA | | BSP | P | 5594613 |
SEVEN SUMMITS CONSTRUCTION LLC | BSP | P | 08/10/2017 | 2nd layer of rock at each side of wall OK // Contractor has provided Hilti details for pipe and cable penetrations. Still need protection details for all bar joist penetrations | JEREMYA | JEREMYA | | BSP | P | 5591444 |
SEVEN SUMMITS CONSTRUCTION LLC | BSP | P | 08/08/2017 | First layer on D.8 to E OK / second layer on entire East side of 4-hour barrier OK, up to within 2' of bottom chord of trusses - need to inspect top-out once installed | RICHB | RICHB | | BSP | P | 5589174 |
SEVEN SUMMITS CONSTRUCTION LLC | BFR | P | 08/04/2017 | Framing & SAFB from Grid D.8 to E (far north end of 4-hour barrier) complete | RICHB | RICHB | | BFR | P | 5586349 |
SEVEN SUMMITS CONSTRUCTION LLC | BSP | P | 08/04/2017 | First layer drywall on East side of 4-hour barrier OK, - still need first layer installed at D.8 to E, far north end / second layer of drywall on West side of 4-hour barrier OK / OK to tape, finish and firestop | RICHB | RICHB | | BSP | P | 5586341 |
SEVEN SUMMITS CONSTRUCTION LLC | BIN | P | 08/02/2017 | SAFB in 4-hour barrier OK from grids A to C / still need inspection for framing at far north end (Grids D.8 to E) / plans reviewed on-site | RICHB | RICHB | | BIN | P | 5583910 |
SEVEN SUMMITS CONSTRUCTION LLC | BFR | P | 08/02/2017 | Wall framing for 4-hour barrier from D.8 to E (exterior wall) complete / plans reviewed on-site | RICHB | RICHB | | BFR | P | 5583891 |
SEVEN SUMMITS CONSTRUCTION LLC | BSP | P | 07/24/2017 | First layer of drywall on the west side of the 4 hour fire barrier OK // Mineral wool on the north half of the wall OK for first layer of drywall to be added // Still need H-D-W assemblies and penetration details for each penetrating item | JEREMYA | JEREMYA | | BSP | P | 5573327 |
SEVEN SUMMITS CONSTRUCTION LLC | BFR | P | 07/20/2017 | New wall framing on BMC side of demising wall OK // Will need to see penetration details for all bar joists and pipes passing through the 4-hr fire barrier. Will need verification that the fire caulk detail on plans works on a 4-hr wall assembly. | JEREMYA | JEREMYA | | BFR | P | 5570224 |
SEVEN SUMMITS CONSTRUCTION LLC | BSP | T | 07/19/2017 | PAID (REC#1440334) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Add wall in warehouse. SEPARATE PERMITS REQUIRED TO ESTABLISH INDIVIDUAL SUITES. | SHELLEY | SHELLEY | | BSP | T | 5569362 |
SEVEN SUMMITS CONSTRUCTION LLC | BFR | P | 07/17/2017 | Partial framing inspection - approximate grids B.8 to E.8 / framing in accordance with splice and UL U419 / need penetration details (fire sprinkler, welded black pipe, EMC for electrical, etc) / stocked material is 3/4" USG UltraCode core - matches listing / need a copy of UL U419 on-site / plans reviewed on-site with contractor | RICHB | RICHB | | BFR | P | 5567105 |
K1 ROOFING AND RESTORATION, LLC. | BFR | P | 07/05/2017 | Construction has started on wall. Verified bottom track at north half of wall. Layout is complete on entire assembly. | JEREMYA | JEREMYA | | BFR | P | 5554801 |
K1 ROOFING AND RESTORATION, LLC. | B16 | P | 06/28/2017 | Met David at Bert W's desk, I explained this wall needs to be built and inspected for the change of Occupancy permit to get a final inspection completed permit K91327 shows the wall as 3 hour but a variance has been approved for a 4 hour fire barrier | BERTW | BERTW | | B16 | P | 5550072 |
K1 ROOFING AND RESTORATION, LLC. | BSP | T | 05/18/2017 | PAID (REC#1425643) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Fire barrier | MICHAELA | MICHAELA | | BSP | T | 5510916 |