MOUNTAIN WIRELESS CONSTRUCTION, LLC | B= | C | 02/26/2020 | | DAKOTAB | DAKOTAB | | B= | C | 6493211 |
MOUNTAIN WIRELESS CONSTRUCTION, LLC | BFN | C | 02/26/2020 | Engineer letter for new concrete slab received | DAKOTAB | DAKOTAB | | BFN | C | 6493207 |
MOUNTAIN WIRELESS CONSTRUCTION, LLC | B= | R | 01/15/2020 | Cancelled per Alex. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982). | DAKOTAB | DAKOTAB | | B= | R | 6453577 |
MOUNTAIN WIRELESS CONSTRUCTION, LLC | BE | L | 01/13/2020 | Renewed for $304.00 at 1/13/2020 10:50:55 AM (Receipt#1655322) | SABRINA | SABRINA | | BE | L | 6450832 |
MOUNTAIN WIRELESS CONSTRUCTION, LLC | BE | L | 07/30/2018 | Renewed for Full Fee at 7/30/2018 10:13:45 AM (Receipt#1522003) | MINDY | MINDY | | BE | L | 5917477 |
SOUTH PAW ELECTRIC CORPORATION | BSP | P | 09/22/2017 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Sheets revised with updated electrical service and notation. | BERTHA | BERTHA | | BSP | P | 5634078 |
MOUNTAIN WIRELESS CONSTRUCTION, LLC | BSP | T | 09/22/2017 | PAID (REC#1454712) PLAN SPLICE FEE: $50 by: BPHILLIPS for Construction: Revised floor plan layout | BPHILLIPS | BPHILLIPS | | BSP | T | 5634014 |
MOUNTAIN WIRELESS CONSTRUCTION, LLC | BE | L | 09/20/2017 | Renewed at 9/20/2017 2:08:42 PM | JOHN | JOHN | | BE | L | 5631745 |
SOUTH PAW ELECTRIC CORPORATION | E= | C | 08/02/2018 | | TOMC | TOMC | | E= | C | 5921480 |
SOUTH PAW ELECTRIC CORPORATION | ES | C | 08/02/2018 | Commercial Service: 400 amp CT service ok to set meter | TOMC | TOMC | | ES | C | 5921472 |
SOUTH PAW ELECTRIC CORPORATION | E= | R | 08/01/2018 | | TOMC | TOMC | | E= | R | 5920371 |
SOUTH PAW ELECTRIC CORPORATION | ES | R | 08/01/2018 | Commercial Service: neutral in CT cabinet needs to be bonded to can and sized to service entrance conductors | TOMC | TOMC | | ES | R | 5920358 |
SOUTH PAW ELECTRIC CORPORATION | ES | L | 07/24/2018 | cell site locked at 1:30 | TOMC | TOMC | | ES | L | 5912389 |
SOUTH PAW ELECTRIC CORPORATION | ES | R | 07/19/2018 | Commercial Service: bond CT can --------- install ko plugs in disconnect | CRAIG | CRAIG | | ES | R | 5907708 |
SOUTH PAW ELECTRIC CORPORATION | EE | L | 06/19/2018 | Renewed at 6/19/2018 11:19:29 AM | DEAN | DEAN | | EE | L | 5878408 |
SOUTH PAW ELECTRIC CORPORATION | ES | P | 08/08/2017 | Commercial Service: 400 amp 3/w for new cell tower equipment: ok to energize | MATTHEW | MATTHEW | | ES | P | 5589391 |
SOUTH PAW ELECTRIC CORPORATION | ES | R | 07/19/2017 | plans show parallel 3/0 to service disconnect (500kcmil installed; need plans revised), remove equipment ground from ct can to service disconnect--------------- I inspected to line side of service disconnect only | MATTHEW | MATTHEW | | ES | R | 5569524 |
SOUTH PAW ELECTRIC CORPORATION | EUG | P | 05/10/2017 | pvc from disconnect to ats location----- leave end open at ats switch | MATTHEW | MATTHEW | | EUG | P | 5502390 |
SOUTH PAW ELECTRIC CORPORATION | EUG | R | 05/09/2017 | nobody on site; locked cell tower enclosure---------- service conduits need to be inspected by CSPU-------I need access to inspect underground past service | MATTHEW | MATTHEW | | EUG | R | 5500429 |
KNERL SHEET METAL, INC | H= | C | 01/30/2020 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 6469326 |