GERALD H PHIPPS INC | B= | C | 06/25/2018 | new Ul listing V489 American Gypsum okay | NATHAN | NATHAN | | B= | C | 5883733 |
GERALD H PHIPPS INC | BE | L | 06/21/2018 | Renewed at 6/21/2018 7:31:31 AM | GITA | GITA | | BE | L | 5880910 |
GERALD H PHIPPS INC | BE | L | 11/07/2017 | Renewed at 11/7/2017 8:53:40 AM | MINDY | MINDY | | BE | L | 5678472 |
GERALD H PHIPPS INC | B= | P | 05/06/2017 | new 1 hr UL smoke and fire assembly with American Gypsum or generic as the drywall used must be provided, U419 is a proprietary listing. Wall penetrations and assembly at headwall okay per HW-D-0624 on file, need all completed required inspections, engineers letter on file. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): PIPE LINE SPECIALTIES DBA PLS MECHANICAL Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5498516 |
GERALD H PHIPPS INC | B= | T | 05/05/2017 | PAID (REC#1422435) AFTER-HOURS INSPECTION: $200 From: TERRI 5/6/17 11:00 am | TERRI | TERRI | | B= | T | 5497079 |
GERALD H PHIPPS INC | BFR | P | 05/04/2017 | need completed mechanical inspection on damper framing / need slip track at top of wall over damper to concrete slab / need headwall detail for connection to bottom of roof slab / | NATHAN | NATHAN | | BFR | P | 5495699 |
GERALD H PHIPPS INC | BSP | R | 04/28/2017 | after review with Jerry Mech inspector new W01 wall needs framing inspection and all sheetrock removed for inspection. Bert W Did not visit site. | BERTW | BERTW | | BSP | R | 5489699 |
STURGEON ELECTRIC CO INC | E= | C | 05/05/2017 | | CRAIGS | CRAIGS | | E= | C | 5496869 |
STURGEON ELECTRIC CO INC | E= | R | 05/01/2017 | gfci protect all receptacles 6" from the sink -- device cant go behind any appliances --- need fire alarm permit pulled through pprbd ------ signed fire alarm permit with the fire dept | CRAIGS | CRAIGS | | E= | R | 5491575 |
STURGEON ELECTRIC CO INC | ER | C | 04/26/2017 | power to fire dampers --- move the washer and dryer outlets -- | CRAIGS | CRAIGS | | ER | C | 5487406 |
PIPE LINE SPECIALTIES INC. | H= | C | 06/22/2018 | SEE IMAGES | JERRYF | JERRYF | | H= | C | 5882304 |
PIPE LINE SPECIALTIES INC. | H= | P | 06/21/2018 | NEED CEILING GRID LABELED - NEED DAMPER PROPERLY SECURED AT 1 DAMPER / ATTACH PICTURES TO NEXT INSPECTION REQUEST / PICTURES TO SHOW RETAINING ANGLES - TAB REPORT NOT REQUIRED | JERRYF | JERRYF | | H= | P | 5881560 |
PIPE LINE SPECIALTIES INC. | HE | C | 01/23/2018 | | TERRI | TERRI | | HE | C | 5744764 |
PIPE LINE SPECIALTIES INC. | H= | P | 09/15/2017 | NEED LETTER FROM ENGINEER DETAILING SUPPORT FOR DAMPERS ABOVE DOUBLE DOORS - FROM SUPPLIED PICTURES BOX HEADER APPEARS TO NOT BE SUPPORTED AT KING STUD - STILL NEED OTHER ITEMS ADDRESSED FROM PREVIOUS INSPECTIONS | JERRYF | JERRYF | | H= | P | 5626853 |
PIPE LINE SPECIALTIES INC. | H= | P | 05/05/2017 | PARTIAL HEAT FINAL PATIENT ROOM OK- STILL NEED SITE VISIT TO VERIFY F/SD DAMPER INSTALLATION / RETAINAGE / PICTURES OF CORRECTIONS IN CORRIDOR AND TAB REPORT | JERRYF | JERRYF | | H= | P | 5497054 |
PIPE LINE SPECIALTIES INC. | HD | P | 05/04/2017 | 3 F/SD FRAMING OK - CONTRACTOR TO MAKE PICTURES AVAILABLE TO INSPECTOR FOR F/SD INSTALL INSPECTION TO REVIEW CORRECTIONS PER - NOTES ADDED AT 2:33 ON 5/4/2017 BUILDING INSPECTOR TO INSPECT WALL AND DOOR FRAMING BEFORE SHEET ROCK | JERRYF | JERRYF | | HD | P | 5496257 |
PIPE LINE SPECIALTIES INC. | HV | P | 05/03/2017 | THIS INSPECTION WAS FOR 7TH FLOOR - DRYER VENT AND TRANSFER DUCT F/SD FRAMING IN PATIENT ROOM OK - STILL NEED CORRIDOR F/SD FRAMING COMPLETED AND INSPECTED | JERRYF | JERRYF | | HV | P | 5494234 |
PIPE LINE SPECIALTIES INC. | H16 | C | 04/27/2017 | NOTIFIED SENIOR BUILDING INSPECTOR ON NEW WALL AND DOORS AT CORRIDOR - APPEARS WALLS ARE COMPLETED AND DOOR IS INSTALLED WITHOUT FRAMING INSPECTION THERE ARE UNSUPPORTED FIRE SMOKE DAMPERS ABOVE DOORWAY | JERRYF | JERRYF | | H16 | C | 5489348 |
PIPE LINE SPECIALTIES INC. | HD | T | 04/27/2017 | PAID (REC#1421740): NOTES ADDED AT 1:55 ON 4?27 - NEED ALL SHEET ROCK REMOVED AT TRANSFER DUCT FRAMING ON ALL 4 SIDES AND SHEET ROCK REMOVED AT HARD LID TO VERIFY FRAMING ON ALL 4 SIDES OF DAMPER IN SUITE - NEED ENGINEER TO ADDRESS UNSUPPORTED FIRE SMOKE DAMPERS AT DOUBLE DOORS - CONTRACTOR TO INSURE PROPER FIRE SMOKE DAMPER GAP AT TRANSFER DUCT - RE INSPECT ALL - STOPPED INSPECTION | JERRYF | JERRYF | | HD | T | 5489252 |
PIPE LINE SPECIALTIES INC. | HD | L | 04/25/2017 | NEED SHEET ROCK REMOVED AT 3 DAMPERS TO VERIFY FRAMING - HAD CONSULT WITH PHILLIP WITH PLS AND MIKE FROM GH PHIPPS - NEED F/SD INSTALL MANUAL AT NEXT INSPECTION - NEED ALL FIRE CAULKING REMOVED AT DAMPERS | JERRYF | JERRYF | | HD | L | 5486638 |