COLORADO STRUCTURES INC | B= | C | 10/18/2017 | All other required Final inspections are complete. (This is a computer generated result) | JEREMYA | JEREMYA | | B= | C | 5659504 |
COLORADO STRUCTURES INC | B= | P | 10/11/2017 | Building final complete pending other final inspections. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), COLORADO MECHANICAL SYSTEMS,INC Mechanical Final Inspection is not Completed yet, INTERSTATE MECHANICAL, INC. Mechanical Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 5652586 |
COLORADO STRUCTURES INC | B= | P | 10/04/2017 | Building final complete pending other finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), COLORADO MECHANICAL SYSTEMS,INC Mechanical Final Inspection is not Completed yet, INTERSTATE MECHANICAL, INC. Mechanical Final Inspection is not Completed yet, INTERSTATE MECHANICAL, INC. Plumbing Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 5644765 |
COLORADO STRUCTURES INC | BLA | C | 08/25/2017 | lath at front elevation OK | DANE | DANE | | BLA | C | 5607756 |
COLORADO STRUCTURES INC | BIN | C | 08/04/2017 | Exterior thermal insulation OK | JEREMYA | JEREMYA | | BIN | C | 5586498 |
COLORADO STRUCTURES INC | BFR | P | 08/04/2017 | Interior wall framing OK // Discussed accessible elements // Partial pendingg other rough inspections | JEREMYA | JEREMYA | | BFR | P | 5586484 |
COLORADO STRUCTURES INC | BM | C | 08/02/2017 | Third party observations | JEREMYA | JEREMYA | | BM | C | 5583071 |
COLORADO STRUCTURES INC | BFN | C | 08/02/2017 | Foundation observation | JEREMYA | JEREMYA | | BFN | C | 5583069 |
COLORADO STRUCTURES INC | BBB | C | 08/02/2017 | Masonry inspection on file | JEREMYA | JEREMYA | | BBB | C | 5583066 |
COLORADO STRUCTURES INC | BFT | C | 08/02/2017 | Reinforcing steel observations on file | JEREMYA | JEREMYA | | BFT | C | 5583064 |
COLORADO STRUCTURES INC | BFR | P | 07/31/2017 | Exterior wall framing OK at store front and at walls on roof // Need all third party inspections | JEREMYA | JEREMYA | | BFR | P | 5581080 |
COLORADO STRUCTURES INC | BFI | C | 06/09/2017 | Rigid foam at perimeter OK | JEREMYA | JEREMYA | | BFI | C | 5531028 |
GDS ELECTRIC | E= | C | 09/25/2017 | rtu 1--5 --- 25 amp units OK | CRAIGS | CRAIGS | | E= | C | 5636328 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 09/13/2017 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | E= | C | 5624930 |
SPECIAL SYSTEMS DESIGN,LLC | ER | C | 09/13/2017 | FIRE ALARM INSPECTION: flow/ tamper , fire alarm panel OK---- signed red card | CRAIGS | CRAIGS | | ER | C | 5624922 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 09/13/2017 | FIRE ALARM INSPECTION: flow/ tamper , fire alarm panel OK---- signed red card | CRAIGS | CRAIGS | | E= | C | 5624923 |
GDS ELECTRIC | ER | P | 09/08/2017 | Ceiling rough in ok for all rooms with grid ceilings / | ROB | ROB | | ER | P | 5620080 |
GDS ELECTRIC | ES | C | 08/16/2017 | Commercial Service: 400 4/w 480 /277 ----- ct meter -- OK to set and wire ct's and energize | CRAIGS | CRAIGS | | ES | C | 5597637 |
GDS ELECTRIC | ER | P | 08/10/2017 | Walls in one office only. S.E. corner. | JOSEPH | JOSEPH | | ER | P | 5591408 |
GDS ELECTRIC | ER | P | 08/09/2017 | walls except the office walls | CRAIGS | CRAIGS | | ER | P | 5590693 |
GDS ELECTRIC | ESL | C | 06/28/2017 | | CRAIGS | CRAIGS | | ESL | C | 5549352 |
INTERSTATE MECHANICAL, INC. | H= | C | 10/18/2017 | Contractors scope complete | MARKB | MARKB | | H= | C | 5659503 |
COLORADO MECHANICAL SYSTEMS, LLC | H= | C | 10/17/2017 | Correction made | MARKB | MARKB | | H= | C | 5658635 |
COLORADO MECHANICAL SYSTEMS, LLC | H= | P | 10/11/2017 | NEED REMOTE INDICATORS INSTALLED FOR SMOKE SHUTDOWN. FIRE CONTROL PERSONAL TOLD ME RTU'S ARE NOT TIED INTO BUILDING FIRE SYSTEM. OTHER CORRECTIONS MADE | MARKB | MARKB | | H= | P | 5652350 |
COLORADO MECHANICAL SYSTEMS, LLC | H= | P | 10/04/2017 | Need to complete condensate drains on RTU'S. Could not find where smoke shutdown has been installed in RTU's or returns. | MARKB | MARKB | | H= | P | 5645133 |
INTERSTATE MECHANICAL, INC. | HC | C | 09/13/2017 | RELEASE METER | MARKB | MARKB | | HC | C | 5625289 |
INTERSTATE MECHANICAL, INC. | HI | C | 09/13/2017 | 60 PSI TEST OK. | MARKB | MARKB | | HI | C | 5625288 |
INTERSTATE MECHANICAL, INC. | HI | P | 09/12/2017 | Need 60 psi test on 100 psi gauge for welded gas pipe. Piping and support per plan | MARKB | MARKB | | HI | P | 5623468 |
COLORADO MECHANICAL SYSTEMS, LLC | HD | P | 09/06/2017 | TAB REPORT RECEIVED | MARKB | MARKB | | HD | P | 5616800 |
COLORADO MECHANICAL SYSTEMS, LLC | H= | R | 09/05/2017 | TAB received does not match plan on file | MARKB | MARKB | | H= | R | 5615163 |
COLORADO MECHANICAL SYSTEMS, LLC | H= | L | 08/29/2017 | INSPECTION CALLED IN FOR WRONG ADDRESS AFTER SPEAKING WITH TODD KNISLEY | MARKB | MARKB | | H= | L | 5610704 |
COLORADO MECHANICAL SYSTEMS, LLC | HD | P | 08/18/2017 | ABOVE CEILING OK - BY FINAL REVISE WORK SCOPE TO SHOW CORRECT NUMBER OF DUCTS - CURRENTLY PERMIT SHOWS 314 - NEED ROOF INSPECTION - TAB REPORT - SMOKE SHUTDOWN | JERRYF | JERRYF | | HD | P | 5600766 |
COLORADO MECHANICAL SYSTEMS, LLC | HD | L | 08/17/2017 | RESCHEDULED FOR CONTRACTOR BECAUSE OF TIME OF DAY | MARKB | MARKB | | HD | L | 5599561 |
INTERSTATE MECHANICAL, INC. | P= | C | 10/09/2017 | | JOHNS | JOHNS | | P= | C | 5648849 |
INTERSTATE MECHANICAL, INC. | PRD | C | 08/11/2017 | ok for test and design. note: contractor aware of nail pro, WILL VERIFY DOME STRAINERS @ PLUMBING FINAL ROOF INSPECTION | JOHNS | JOHNS | | PRD | C | 5592934 |
INTERSTATE MECHANICAL, INC. | PTO | C | 08/10/2017 | ok for test and design for pto only, please call for prd inspection tomorrow. note: hammer aerestors installed above ceiling @ front bath room, need to check water heater @ final, vtr (3 3") | JOHNS | JOHNS | | PTO | C | 5592132 |
INTERSTATE MECHANICAL, INC. | PB | C | 06/23/2017 | test and design ok. | JOHNS | JOHNS | | PB | C | 5545712 |