GRB SERVICE SYSTEMS, INC. | B= | C | 12/01/2017 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 5699364 |
GRB SERVICE SYSTEMS, INC. | B= | P | 11/01/2017 | . Additional Inspections Required (computer generated): TDR CONSTRUCTORS, INC. Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5673028 |
GRB SERVICE SYSTEMS, INC. | BFR | P | 08/14/2017 | pharmacy wall framing okay with all completed required inspections | NATHAN | NATHAN | | BFR | P | 5595152 |
GRB SERVICE SYSTEMS, INC. | BFR | P | 07/24/2017 | with completed required rough inspections frame okay at family bathroom in rear. | NATHAN | NATHAN | | BFR | P | 5573655 |
TDR CONTRACTORS, INC. | BSP | P | 06/28/2017 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: SPLICED FOR REVISIONS TO REFRIGERATION AND LAYOUTS | JUSTINC | JUSTINC | | BSP | P | 5548983 |
GRB SERVICE SYSTEMS, INC. | BSP | T | 06/26/2017 | PAID (REC#1437193) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Power and lighting revisions through out. Revised panel schedules. | BERTHA | BERTHA | | BSP | T | 5547307 |
VOGEL PLUMBING, INC. | BSP | T | 06/21/2017 | PAID (REC#1437194) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 6-21-17 | TCRIPPEN | TCRIPPEN | | BSP | T | 5542747 |
GRB SERVICE SYSTEMS, INC. | BSP | T | 06/20/2017 | PAID (REC#1437193) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: revised details and floor plan | SHELLEY | SHELLEY | | BSP | T | 5540367 |
STEVE'S ELECTRIC LLC | E= | C | 10/30/2017 | | BRIAN | BRIAN | | E= | C | 5670541 |
STEVE'S ELECTRIC LLC | E= | R | 10/27/2017 | NEED PIC OF KO PLUG IN J BOX---ARC FLASH STICKERS----CONDUIT INSTALLED INTO 4SQ BOX WITH LOCK NUT--- | BRIAN | BRIAN | | E= | R | 5669559 |
STEVE'S ELECTRIC LLC | E= | P | 10/25/2017 | NEED TO FIX CONDUIT DROPS FROM CEILINGS----VERIFY PANELS----CEILING IN BREAK ROOM--- | BRIAN | BRIAN | | E= | P | 5666502 |
STEVE'S ELECTRIC LLC | E= | T | 10/20/2017 | PAID (REC#1461512): MUST HAVE A LICENSED ELECTRICIAN ON SITE FOR NEXT INSPECTION !! | BRIAN | BRIAN | | E= | T | 5661861 |
STEVE'S ELECTRIC LLC | E= | R | 10/16/2017 | OLD CORRECTIONS PLUS MC ON GRID AND NOT SUPPORTED IN BREAK ROOM---OPEN J BOXES----FIRE ALARM ABOVE CEILING-----------COMPLETE REINSPECT | BRIAN | BRIAN | | E= | R | 5656255 |
STEVE'S ELECTRIC LLC | E= | L | 09/13/2017 | contractor needed to cancel, | JOHNN | JOHNN | | E= | L | 5624778 |
STEVE'S ELECTRIC LLC | E= | R | 09/11/2017 | NEED TO USE APPROVED TRANSITION FROM MC TO EMT-----NEED TO INSTALL ALL OUTLETS IN HARDWARE -----NEED TO SECURE THE BOXES TO THE BEAM ( NO ZIP TIE ) ----MISSING COVER PLATES----------NEED THE ELECTRICIAN ON SITE WITH LADDER AND OPEN THE PANELS FOR NEXT INSPECTION--------- | BRIAN | BRIAN | | E= | R | 5621505 |
STEVE'S ELECTRIC LLC | E= | P | 08/24/2017 | PHARMACY ONLY----NEED TO INSTALL ALL THREE MOUNTING SCREWS ON ALL INDUSTRIAL COVERS-----NEED HANDEL TIES ON ANY MULTI WIRE CIRCUITS IN PHARMACY PANEL----- | BRIAN | BRIAN | | E= | P | 5605704 |
STEVE'S ELECTRIC LLC | ER | P | 08/24/2017 | PHARMACY CEILINGS --OK | BRIAN | BRIAN | | ER | P | 5605698 |
STEVE'S ELECTRIC LLC | E= | R | 08/23/2017 | NOT READY | BRIAN | BRIAN | | E= | R | 5604204 |
STEVE'S ELECTRIC LLC | E= | R | 08/23/2017 | NOT READY--- | BRIAN | BRIAN | | E= | R | 5604203 |
STEVE'S ELECTRIC LLC | ER | R | 08/23/2017 | NEED TO REMOVE THE TILE OUT FROM THE ENDS OF THE LIGHT TO SEE THE STRAPS----------NEED K.O. PLUGS IN 2 4- SQ BOXES AND STRAP THE MC CABLES WITH IN 12" OF THE BOXES AND POWER POLES ---THEY NEED TO BE SECURED ----- | BRIAN | BRIAN | | ER | R | 5604200 |
STEVE'S ELECTRIC LLC | E= | L | 08/18/2017 | not ready | JOHNN | JOHNN | | E= | L | 5600691 |
STEVE'S ELECTRIC LLC | ER | P | 08/18/2017 | above ceiling:not ready,perimeter has many open j boxes, 1 row of lights relocated toward counter:need clips or 4 screws, leave all perimeter tiles out and adjacent to ends of troffers for inspection, | JOHNN | JOHNN | | ER | P | 5600690 |
STEVE'S ELECTRIC LLC | ER | P | 08/16/2017 | 1/2 wall only | TOMC | TOMC | | ER | P | 5597183 |
STEVE'S ELECTRIC LLC | ER | P | 08/14/2017 | wall see drawing | CRAIGS | CRAIGS | | ER | P | 5594589 |
STEVE'S ELECTRIC LLC | ER | P | 08/02/2017 | temp pharmacy ok-- | BRIAN | BRIAN | | ER | P | 5583428 |
STEVE'S ELECTRIC LLC | ER | R | 07/31/2017 | NEED TO GROUND ALL THE J BOXES ---TEMP PHARMACY BOOTH--- | BRIAN | BRIAN | | ER | R | 5580522 |
TDR CONTRACTORS, INC. | H= | C | 12/01/2017 | TAB REPORT | JERRYF | JERRYF | | H= | C | 5699363 |
TDR CONTRACTORS, INC. | H= | P | 11/03/2017 | PARTIAL FINAL PENDING TAB REPORT - NO ONSITE PERSONNEL OR CALL AHEAD INFO GIVEN - FAMILY RESTROOM EXHAUST IS CONNECTED | JERRYF | JERRYF | | H= | P | 5675717 |
TDR CONTRACTORS, INC. | H= | P | 11/01/2017 | FINAL PENDING - FAMILY BATH EXHAUST IS NOT HOOKED UP YET. PROVIDE TEST AND BALANCE REPORT. EQUIPMENT ON ROOF OK. | MARKB | MARKB | | H= | P | 5673139 |
SOURCE REFRIGERATION & HVAC | H= | C | 09/27/2017 | REPLACED COOLERS ONLY AND USED EXISTING DRAINS | JON | JON | | H= | C | 5638957 |
TDR CONTRACTORS, INC. | HSP | P | 09/27/2017 | PLANS CALL FOR A WATER HEATER REPLACEMENT FROM SHEET MP-1 PAGE 135. DID NOT SEE A PERMIT? WAS WATER HEATER REPLACED? | JON | JON | | HSP | P | 5638955 |
TDR CONTRACTORS, INC. | H= | P | 08/18/2017 | PARTIAL FINAL FOR PHARMACY AREA ONLY / WILL TAB REPORT AT COMPLETION OF ENTIRE PROJECT | JERRYF | JERRYF | | H= | P | 5600062 |
TDR CONTRACTORS, INC. | HD | P | 08/18/2017 | ABOVE CEILING SA / RA OK IN PHARMACY ONLY - STILL NEED ALL OTHER AREA,S | JERRYF | JERRYF | | HD | P | 5600055 |
VOGEL PLUMBING, INC. | P= | C | 10/30/2017 | corrections made. | TAYLOR | TAYLOR | | P= | C | 5670742 |
VOGEL PLUMBING, INC. | P= | P | 10/12/2017 | front janitor water heater ok, support expansion tank and need shut off valve for rear janitor water heater, support expansion tank and install drain down at auto center water heater, need drain down/ shut off valve, support expansion tank, and can not trap T&P drain at pharmacy water heater, need drain down at vision water heater. | TAYLOR | TAYLOR | | P= | P | 5654017 |
VOGEL PLUMBING, INC. | P= | P | 09/15/2017 | corrections made, note added on 9-28-17 ( after replacing water heaters, need inspection and scope of work corrected ). | TAYLOR | TAYLOR | | P= | P | 5626753 |
VOGEL PLUMBING, INC. | PTO | C | 09/15/2017 | corrections made. | TAYLOR | TAYLOR | | PTO | C | 5626750 |
VOGEL PLUMBING, INC. | P= | R | 09/05/2017 | no corrections made. | TAYLOR | TAYLOR | | P= | R | 5616384 |
VOGEL PLUMBING, INC. | P= | P | 08/28/2017 | waive trip fee, still need to correct PTO items, need trap guard at floor drain in restroom, rest ok. | TAYLOR | TAYLOR | | P= | P | 5609291 |
VOGEL PLUMBING, INC. | P= | P | 08/25/2017 | aquarium area ok, need to complete PTO. | TAYLOR | TAYLOR | | P= | P | 5607714 |
VOGEL PLUMBING, INC. | PTO | P | 08/25/2017 | need to support copper above ceiling at lay away area, need mission band and proper grade/ support at vent for restroom, rest ok. | TAYLOR | TAYLOR | | PTO | P | 5607710 |
VOGEL PLUMBING, INC. | PB | C | 08/17/2017 | floor sink at aquarium ok. | TAYLOR | TAYLOR | | PB | C | 5599351 |
VOGEL PLUMBING, INC. | PB | P | 08/16/2017 | can not horizontal dry vent floor drain at aquarium area. | TAYLOR | TAYLOR | | PB | P | 5598089 |
VOGEL PLUMBING, INC. | PTO | P | 08/02/2017 | dwv test o.k, closet flange set | JOEL | JOEL | | PTO | P | 5584177 |
VOGEL PLUMBING, INC. | PTO | P | 08/01/2017 | lost test DWV. | TAYLOR | TAYLOR | | PTO | P | 5582882 |
VOGEL PLUMBING, INC. | PTO | P | 07/31/2017 | H2O in wall ok, low test DWV. | TAYLOR | TAYLOR | | PTO | P | 5581392 |
VOGEL PLUMBING, INC. | PTO | R | 07/25/2017 | this inspection was for rear restroom ( undersized cold water piping, need 1 inch DCW installed to toilet that tie's into 1 1/4 DCW, need approved concrete anchors at closet flange, test all new DWV, need ladder on next inspection to verify all piping above ceiling. ) | TAYLOR | TAYLOR | | PTO | R | 5575646 |
VOGEL PLUMBING, INC. | PB | P | 07/18/2017 | rear restroom ok. | TAYLOR | TAYLOR | | PB | P | 5568342 |
VOGEL PLUMBING, INC. | PB | P | 07/17/2017 | this inspection was for rear restroom ( leak at vent and can not horizontal dry vent toilet/ floor drain ). | TAYLOR | TAYLOR | | PB | P | 5566867 |