FAUROT CONSTRUCTION, INC. | B= | C | 09/13/2017 | Building final complete // State Electric final is complete, see DORA State Permit #821758 // Kitchen remodel is on separate permit | JEREMYA | JEREMYA | | B= | C | 5624812 |
FAUROT CONSTRUCTION, INC. | B= | P | 08/30/2017 | State plumbing final completed on file/State electrical final is partialed pending kitchen on file still need completion from state -- Schedule a new Building Final when above items are complete. | BERTW | BERTW | | B= | P | 5611595 |
FAUROT CONSTRUCTION, INC. | B= | P | 08/18/2017 | Temp CO: pending final ( Expires: 9/17/2017 12:00:00 AM) | RITA | RITA | | B= | P | 5600003 |
FAUROT CONSTRUCTION, INC. | B= | P | 08/18/2017 | All safety glass installed. Additional Inspections Required (computer generated): PROCRAFT MECHANICAL Mechanical Final Inspection is not Completed yet. | JEREMYA | JEREMYA | | B= | P | 5599687 |
FAUROT CONSTRUCTION, INC. | BSP | P | 08/11/2017 | Need all door glass installed // Complete Fire Final // Need copies of DORA sign offs for Electric and Plumbing | JEREMYA | JEREMYA | | BSP | P | 5593106 |
FAUROT CONSTRUCTION, INC. | BFR | P | 07/25/2017 | Discussed repairs required on existing rated assemblies. Contractor will have all penetrations sealed by next inspection | JEREMYA | JEREMYA | | BFR | P | 5574791 |
FAUROT CONSTRUCTION, INC. | BFR | P | 07/10/2017 | Final wall framing in Area A rooms 113-117 & 142 OK // Hardlid framing outside rooms 145 & 146 OK // Furr out wall at common 125 OK | JEREMYA | JEREMYA | | BFR | P | 5558885 |
FAUROT CONSTRUCTION, INC. | BFR | P | 06/23/2017 | 103 walls, 102 ceiling, 125 store front wall and soffitt, men and woman restroom ok with all other inspections | DALE | DALE | | BFR | P | 5545487 |
FAUROT CONSTRUCTION, INC. | BFR | P | 06/15/2017 | partial framing inspection for area A walls in rooms 129,123,122,121,120,119,118,143,144,103,104,105,107,109,111 -- reviewed w/ Eric w/Faurot accessibility for building as well as site -- existing bathroom group to receive new vertical grab bars to be checked -- verify with mechanical inspector hood location in kitchen at future work -- discussed state paperwork/ mechanical final/ site requirements by final | SCOTTS | SCOTTS | | BFR | P | 5536639 |
FAUROT CONSTRUCTION, INC. | BSP | T | 06/13/2017 | PAID (REC#1431565) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Add door and column - update finishes | MICHAELA | MICHAELA | | BSP | T | 5534280 |
FAUROT CONSTRUCTION, INC. | BFR | P | 06/06/2017 | Walked Area B (East end) 1st floor with Eric (Faurot) - highlighted inspection area on plans / interior non-bearing partitions and soffits OK in classrooms, labs & corridors - approximately Grid H through P / exterior fur-out on Grid P OK / no inspection done in bath, locker, utility or stair rooms / discussed accessible elements / permit set reviewed on-site | RICHB | RICHB | | BFR | P | 5526532 |
PROCRAFT MECHANICAL, INC. | H= | C | 08/21/2017 | CONTRACTORS SCOPE COMPLETE | MARKB | MARKB | | H= | C | 5602136 |
PROCRAFT MECHANICAL, INC. | H= | P | 08/21/2017 | Found outside air on TAB and sent to scanning. TAB received. | MARKB | MARKB | | H= | P | 5601342 |
PROCRAFT MECHANICAL, INC. | H= | P | 08/18/2017 | Received test and balance report No outside air reported. Still lack inspection ofdifussers in cafeteria and data room. | JACK | JACK | | H= | P | 5599994 |
PROCRAFT MECHANICAL, INC. | HD | P | 08/01/2017 | ABOVE CEILING DUCT, VAV'S, FLEX AND DIFFUSERS COMPLETE IN ALL AREAS EXCEPT FOR: Need EF-11 fan installed in data room and diffusers installed in cafeteria. Provide Test And Balance Report | MARKB | MARKB | | HD | P | 5582545 |
PROCRAFT MECHANICAL, INC. | HD | P | 07/21/2017 | AREA ( B ) FROM GRID LINES P - J ABOVE CEILING RETURN AIR GRILLS IN PLACE AND S/A REGISTER AND VAV TIE INS OK, ( EXCEPT FOR ROOMS # 135 , 126 ) ROOM # 143 OK . STILL NEED TO LOOK AT HARD LIDS .WILL CONSULT WITH BUILDING INSPECTOR ABOUT GC QUESTIONS ON RETURN AIR PLENUM TO EXISTING RTU-1 | LIDO | LIDO | | HD | P | 5571624 |
PROCRAFT MECHANICAL, INC. | HD | P | 07/14/2017 | ABOVE CEILING SA LOW PRESSURE RUN OUTS / MAINS OK TO WRAP FROM GRID LINES 2/4 THROUGH E - STILL NEED ALL MEDIUM PRESSURE TIE INS AT VAV'S, FLEX AND DIFFUSERS | MARKB | MARKB | | HD | P | 5564598 |
PROCRAFT MECHANICAL, INC. | HRR | P | 07/06/2017 | ABOVE CEILING SA LOW PRESSURE RUN OUTS / MAINS AND RESTROOM EXHAUST OK TO WRAP FROM GRID LINES 1 AND 2 AND A THROUGH G - STILL NEED ALL MEDIUM PRESSURE TIE INS AT VAV'S | JERRYF | JERRYF | | HRR | P | 5556082 |
PROCRAFT MECHANICAL, INC. | HD | P | 06/27/2017 | ABOVE CEILING DUCT FOR AREA "A" - MEDIUM AND LOW PRESSURE SIDE FOR GRIDS E/G - 2/4 OK TO WRAP. NO FLEX OR DIFFUSERS INSTALLED AT THIS TIME. | MARKB | MARKB | | HD | P | 5548666 |
PROCRAFT MECHANICAL, INC. | HD | P | 06/23/2017 | ABOVE CEILING DUCT - LOW PRESSURE SIDE OF VAV 3-24 ABOVE BATHROOMS OK TO WRAP. NO FLEX OR DIFFUSERS. NEED APPROVED DUCT MATERIAL ON BATH EXHAUST RM 159 & 160 FOR EF-5(E). | MARKB | MARKB | | HD | P | 5544680 |
PROCRAFT MECHANICAL, INC. | HD | P | 06/07/2017 | PARTIAL DUCT INSPECTION FOR AREA B ABOVE CEILING OK FOR WRAP ON ALL LOW PRESSURE MAINS AND RUN OUTS IN THE FOLLOWING AREA'S - ROOMS 132 - 130 - 129 - 128 - 161 AND FROM GRID LINES H THROUGH P AND 1 THROUGH 3 EXCLUDING ALL AT VAV 3-24 - STILL NEED ALL MEDIUM PRESSURE TIE INS AND NEW VAV BOXES INSTALLED IN THESE AREA'S - AT FUTURE INSPECTION VERIFY ACCESS TO THE FOLLOWING EXISTING VAV BOXES 3-21 AND 3 - 26 | JERRYF | JERRYF | | HD | P | 5527931 |