FALCON BUILDERS, LLC | B= | C | 11/21/2017 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 5692386 |
FALCON BUILDERS, LLC | B= | P | 11/21/2017 | . Additional Inspections Required (computer generated): TRUSTED SERVICES, LLC. Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5692050 |
TRUSTED SERVICES, LLC. | BSP | T | 11/20/2017 | PAID (REC#1466757) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 11-20-17 | TCRIPPEN | TCRIPPEN | | BSP | T | 5689947 |
TRUSTED SERVICES, LLC. | BSP | P | 11/20/2017 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised for asbuilt conditions | JUSTINC | JUSTINC | | BSP | P | 5689903 |
TRUSTED SERVICES, LLC. | BSP | T | 11/16/2017 | PAID (REC#1466294) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: delta 2 | DALEH | DALEH | | BSP | T | 5687913 |
SPRINGS FAMILY ELECTRIC | BSP | T | 08/24/2017 | PAID (REC#1448602) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Revise lighting | SHELBY | SHELBY | | BSP | T | 5605920 |
SPRINGS FAMILY ELECTRIC | BSP | T | 08/21/2017 | PAID (REC#1448602) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised one-line, existing House Panel to remain, revised all power plans to indicate new panel and circuit number designation, new layout for Veg Room, revised Veg Room lighting, new panel schedules and light listings to reflect changes. | BERTHA | BERTHA | | BSP | T | 5601550 |
FALCON BUILDERS, LLC | BLA | C | 08/14/2017 | | NATHAN | NATHAN | | BLA | C | 5594817 |
FALCON BUILDERS, LLC | BLA | R | 08/09/2017 | missing holes in bottom weep screed | NATHAN | NATHAN | | BLA | R | 5590781 |
FALCON BUILDERS, LLC | BFR | P | 08/07/2017 | Reviewed Accessible Elements / all interior light steel stud walls okay with completed required inspections | NATHAN | NATHAN | | BFR | P | 5587450 |
FALCON BUILDERS, LLC | BLA | P | 07/28/2017 | Northeast face stucco lath complete / Sheet A2 indicates door infill near south corner is to receive stucco - not ready / plans reviewed on-site | RICHB | RICHB | | BLA | P | 5579308 |
SPRINGS FAMILY ELECTRIC | E= | C | 11/17/2017 | | BRIAN | BRIAN | | E= | C | 5689305 |
SPRINGS FAMILY ELECTRIC | E= | P | 11/09/2017 | FLOWERING ROOMS--OK----------NEED CORRECT SIZE EGC FOR AIR HANDLERS--GROUND TIME CLOCKS---ANCHOR SHELVES TO FLOOR----MISSING BLANKS--PANEL SCH----LABEL DISCONNECTS 1 OF 6 --2 OF 6..... --NEED FLEX INSTALLED ON CHILLER FOR MOVEMENT ----- | BRIAN | BRIAN | | E= | P | 5681553 |
SPRINGS FAMILY ELECTRIC | ES | C | 11/01/2017 | Commercial Service: 2000 amp 4-w ---------OK TO SET METERS FOR ALL---METER 1,2,3,4 --ALL 400 AMP 4-W --METER 5 IS 600 AMP 4-W AND THE HOUSE PANEL ---100 3-W ---------------------OK TO MAIN---- | BRIAN | BRIAN | | ES | C | 5672737 |
SPRINGS FAMILY ELECTRIC | ES | R | 10/31/2017 | Commercial Service: NEED ADDRESSING FOR UNITS --- | BRIAN | BRIAN | | ES | R | 5672658 |
SPRINGS FAMILY ELECTRIC | ES | R | 09/12/2017 | Commercial Service: NOT READY--- | BRIAN | BRIAN | | ES | R | 5623918 |
SPRINGS FAMILY ELECTRIC | ER | P | 08/30/2017 | received pic | BRIAN | BRIAN | | ER | P | 5610915 |
SPRINGS FAMILY ELECTRIC | ER | P | 08/29/2017 | REST OF NEW WALLS----NEED PIC OF BAR HANGERS--- | BRIAN | BRIAN | | ER | P | 5610181 |
SPRINGS FAMILY ELECTRIC | ER | P | 08/04/2017 | WALLS---SEE PLANS-- | BRIAN | BRIAN | | ER | P | 5586908 |
TRUSTED SERVICES, LLC. | H= | C | 11/21/2017 | ALL OK | RICKR | RICKR | | H= | C | 5692385 |
TRUSTED SERVICES, LLC. | H= | P | 11/17/2017 | Still need plans to show FC-8 heating bathrooms, changed outside air to FC-8 and changed bath exhaust ducting. Missing 2 supply's in hallway for FC-9. Still need engineer to address building pressure for outside air. Provide Test And Balance report. Rooftop penetrations OK. | MARKB | MARKB | | H= | P | 5688664 |
TRUSTED SERVICES, LLC. | HWP+ | P | 11/09/2017 | CONDENSATE PIPING INSPECTION ONLY | JON | JON | | HWP+ | P | 5681575 |
TRUSTED SERVICES, LLC. | HWP | C | 11/02/2017 | PRESSURE TEST OK - ALL PIPING PER PLAN - BY FINAL REVISE PLANS FOR NEW CONDENSATE DRAINS AND OUTLET LOCATION - STILL NEED TO INSPECT DRAINS | JERRYF | JERRYF | | HWP | C | 5674598 |
TRUSTED SERVICES, LLC. | HD | P | 09/15/2017 | ABOVE CEILING DUCT INSPECTION for whole building - WRAP AT OWN RISK - Need plan splice for changed duct on FC-8 and FC-9. Bath exhaust not per plan. Outside air to 3 fan coils not installed. Engineer to address how relieving building air for outside rate. | MARKB | MARKB | | HD | P | 5627233 |
TRUSTED SERVICES, LLC. | HC | C | 09/15/2017 | RELEASE METER | MARKB | MARKB | | HC | C | 5627229 |
TRUSTED SERVICES, LLC. | HI | C | 09/15/2017 | 10 PSI PRESSURE TEST OK. PIPING PER PLAN | MARKB | MARKB | | HI | C | 5627212 |
TRUSTED SERVICES, LLC. | P= | C | 11/21/2017 | | JOEL | JOEL | | P= | C | 5691113 |
TRUSTED SERVICES, LLC. | P= | P | 11/17/2017 | still need plumbing splice | JOEL | JOEL | | P= | P | 5689139 |
TRUSTED SERVICES, LLC. | P= | R | 11/09/2017 | Not ready and still need revised plan. | JOEL | JOEL | | P= | R | 5681820 |
TRUSTED SERVICES, LLC. | P= | P | 11/08/2017 | revise plans to show added backflow preventer at mop sink, and still need letter to verify pex instead of tyle''L'' copper | JOEL | JOEL | | P= | P | 5680527 |
TRUSTED SERVICES, LLC. | PTO | C | 08/07/2017 | Need engineers letter or plans revised to reflect PEX water pipe in lieu of type "L" copper by final, rest OK. Note: engineers letter received - sent to scanning | SHANEN | SHANEN | | PTO | C | 5587400 |
TRUSTED SERVICES, LLC. | PTO | P | 08/04/2017 | Need engineer's letter for PEX in lieu of type "L" copper water distribution, set and secure men's room closet flange, install 3" floor sink vents and clean outs, rest OK, AAV - drinking fountain, check water heater at final | SHANEN | SHANEN | | PTO | P | 5585818 |
TRUSTED SERVICES, LLC. | PB | C | 07/26/2017 | Test OK | SHANEN | SHANEN | | PB | C | 5576095 |
TRUSTED SERVICES, LLC. | PB | P | 07/25/2017 | Floor sink design OK need test, need bathroom groups completed and tested | SHANEN | SHANEN | | PB | P | 5574824 |