HAYS CONSTRUCTION COMPANY, INC. | B= | C | 01/19/2018 | Compliant coat hook has been added | RICHB | RICHB | | B= | C | 5742497 |
HAYS CONSTRUCTION COMPANY, INC. | B= | P | 12/29/2017 | Temp CO: pending building and mechanical finals ( Expires: 1/28/2018 12:00:00 AM) | MINDY | MINDY | | B= | P | 5725537 |
HAYS CONSTRUCTION COMPANY, INC. | B= | P | 12/29/2017 | need accessible coat in restroom -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): BRUNO'S MECHANICAL INC. Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5725164 |
HAYS CONSTRUCTION COMPANY, INC. | BSP | P | 12/18/2017 | inspection for sign footing is on permit L22458 | DANE | DANE | | BSP | P | 5715703 |
HAYS CONSTRUCTION COMPANY, INC. | BFR | C | 11/15/2017 | letter received for hard lid construction in restroom and use of 25 gage studs / braces installed at curtain wall | DANE | DANE | | BFR | C | 5685726 |
BRUNO'S MECHANICAL INC. | BSP | T | 11/07/2017 | PAID (REC#1464635) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 11-7-2017 | TCRIPPEN | TCRIPPEN | | BSP | T | 5679295 |
BRUNO'S MECHANICAL INC. | BSP | P | 11/07/2017 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised gas piping and water heater | JUSTINC | JUSTINC | | BSP | P | 5679188 |
HAYS CONSTRUCTION COMPANY, INC. | BFR | P | 11/06/2017 | need braces maximum 32" OC at curtain wall / need stamped letter stating what gauge studs are to be used for metal framing / 25 gauge studs have been used / need to install grab rail backing in restroom / discussed accessible elements | DANE | DANE | | BFR | P | 5677655 |
EL PASO ELECTRIC, LLC. | BSP | T | 11/06/2017 | PAID (REC#1464636) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Changed lighting in Dining Area 102 | BERTHA | BERTHA | | BSP | T | 5677257 |
HAYS CONSTRUCTION COMPANY, INC. | BSP | T | 11/03/2017 | PAID (REC#1464637) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Add framing at coolers | MICHAELA | MICHAELA | | BSP | T | 5676561 |
BRUNO'S MECHANICAL INC. | BSP | T | 10/27/2017 | PAID (REC#1462489) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: removed cabinet unit heater | DALEH | DALEH | | BSP | T | 5670072 |
HAYS CONSTRUCTION COMPANY, INC. | BSP | T | 10/27/2017 | PAID (REC#1462490) PLAN SPLICE FEE: $50 by: BPHILLIPS for Construction: Revised finishes around restroom and sundae counter. | BPHILLIPS | BPHILLIPS | | BSP | T | 5669986 |
EL PASO ELECTRIC, LLC. | E= | C | 12/27/2017 | | BRET | BRET | | E= | C | 5723010 |
EL PASO ELECTRIC, LLC. | E= | P | 12/15/2017 | Need to check sign disconnect on roof---Menu Board not installed---Bath fixture not completed / | ROB | ROB | | E= | P | 5714340 |
EL PASO ELECTRIC, LLC. | EUG | C | 12/14/2017 | menu board drive thru sign to be non-illuminated ( no conduit installed prior to driveway pour) | BRET | BRET | | EUG | C | 5712685 |
EL PASO ELECTRIC, LLC. | ER | C | 12/13/2017 | | BRET | BRET | | ER | C | 5711183 |
EL PASO ELECTRIC, LLC. | ER | L | 12/12/2017 | Gave call ahead, nobody on site / | ROB | ROB | | ER | L | 5710747 |
EL PASO ELECTRIC, LLC. | ES | L | 12/12/2017 | Nobody on site / | ROB | ROB | | ES | L | 5710746 |
EL PASO ELECTRIC, LLC. | ER | L | 12/12/2017 | Gave call ahead, nobody on site / | ROB | ROB | | ER | L | 5710743 |
EL PASO ELECTRIC, LLC. | ER | R | 12/11/2017 | not ready | BRET | BRET | | ER | R | 5708617 |
EL PASO ELECTRIC, LLC. | ES | P | 12/06/2017 | Commercial Service: 200 amp service contractor need access to terminate in ct compartment ok to energize | BRET | BRET | | ES | P | 5704808 |
EL PASO ELECTRIC, LLC. | ER | P | 11/06/2017 | walls except half wall for ice cream freezers. | BRET | BRET | | ER | P | 5677317 |
EL PASO ELECTRIC, LLC. | ER | P | 10/30/2017 | walls ok ,bath lid needs exhaust fan hook up | BRET | BRET | | ER | P | 5671410 |
EL PASO ELECTRIC, LLC. | ESL | C | 10/12/2017 | | JOHNN | JOHNN | | ESL | C | 5652803 |
BRUNO'S MECHANICAL INC. | H= | C | 01/04/2018 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 5728934 |
BRUNO'S MECHANICAL INC. | H= | L | 01/03/2018 | STORE APPEARS TO ALREADY BE IN OPERATION AND IS NOT OPEN UNTIL 11:00 AM. | NANCY | NANCY | | H= | L | 5727235 |
BRUNO'S MECHANICAL INC. | H= | P | 12/28/2017 | FIELD CANCELED BY TOM . | LIDO | LIDO | | H= | P | 5723810 |
BRUNO'S MECHANICAL INC. | H= | P | 12/26/2017 | INSTALL CONDENSATE TRAP ELBOW, SEE PAGE 72 PART #16. INSTALL CONDENSATE TRAP AND DRAIN, SEE PAGE 28 FIGURE 16. | NANCY | NANCY | | H= | P | 5722319 |
BRUNO'S MECHANICAL INC. | H= | P | 12/22/2017 | PROVIDE INSTALLATION INSTRUCTIONS FOR WATER HEATER. REMOVE ELECTRIC WATER HEATER FROM SCOPE OF WORK. | NANCY | NANCY | | H= | P | 5721456 |
HOMELAND MECHANICAL LLC | H= | C | 12/22/2017 | REFRIGERATION FINAL OK. NO LEAKAGE ALARM REQUIRED. 14 LBS 7 OZ OF REFRIGERATION IN SYSTEM, NOT 17 LBS 7 OZ. SEE IMAGES FOR LETTER FROM CONTRACTOR STATING HOW MUCH REFRIGERATION IS IN SYSTEM. | NANCY | NANCY | | H= | C | 5720828 |
BRUNO'S MECHANICAL INC. | H= | P | 12/22/2017 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. | NANCY | NANCY | | H= | P | 5720820 |
HOMELAND MECHANICAL LLC | H= | P | 12/20/2017 | 15,314 LBS OF 404A REFRIGERATION ALLOWED, 17 LBS 7 OZ INSTALLED IN SYSTEM. REFRIGERATION LEAKAGE ALARM REQUIRED IN FREEZER. LEAVE ALARM INSTALLATION INSTRUCTIONS ON SITE FOR NEXT INSPECTION. | NANCY | NANCY | | H= | P | 5718432 |
HOMELAND MECHANICAL LLC | HRP | C | 12/08/2017 | FOR FINAL PROVIDE QUANTITY AND TYPE OF REFRIGERANT AND VOLUME OF COOLER. NEED TO VERIFY IF LEAKAGE ALARM IS REQUIRED, SEE SHEET M-2 COOLER CALCULATIONS. SECURE CONDENSER TO PAD. LABEL CONDENSER WITH ADDRESS 1343. COMPLETE CONDENSATE DRAIN. 400 LB TEST OK ON LINES. | NANCY | NANCY | | HRP | C | 5707542 |
BRUNO'S MECHANICAL INC. | H= | P | 12/06/2017 | ADD WATER HEATER VENT ONTO MECHANICAL SCOPE OF WORK AND CALL FOR INSPECTION WHEN READY. REMOVE SAG FROM SUPPLY FLEX TO OFFICE. INSTALL T-STAT. PLUMBING VENT WITHIN 10 FEET OF RTU ECONOMIZER, MUST BE 10 FEET AWAY OR 3 FEET ABOVE INTAKE. PERMANENTLY LABEL RTU WITH ADDRESS 1343. SCREEN BATH EXHAUST ON ROOF. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5704983 |
BRUNO'S MECHANICAL INC. | H= | P | 12/05/2017 | NEED REFRIGERATION CONTRACTOR ATTACHED TO PERMIT.NEED CONTRACTOR INSTALLING WATER HEATER VENT TO ADD IT TO THEIR SCOPE OF WORK AND CALL FOR INSPECTION. INSULATION ALREADY FALLING OFF OF DUCTS, PROPERLY WRAP AND SECURE INSULATION. PROPERLY INSTALL FLEX DUCTS, PER MANUFACTURER NEED TWO WRAPS OF TAPE AND ZIP TIE ON INSIDE SLEEVE THEN EITHER TAPE OR BAND OUTER SLEEVE. PROPERLY INSTALL SUPPLY AIR IN OFFICE. INSTALL SUPPLY AIR IN BATHROOM. NO ROOF TODAY. | NANCY | NANCY | | H= | P | 5702863 |
BRUNO'S MECHANICAL INC. | HD | P | 11/02/2017 | NEED REFRIGERATION CONTRACTOR ATTACHED TO PERMIT. PROPERLY SUPPORT BATHROOM EXHAUST DUCT, A CUT STUD IS UNACCEPTABLE FOR SUPPORT.BY FINAL NEED REMOTE INDICATOR FOR SMOKE DETECTION. BY FINAL INSTALL THERMOSTAT NO HIGHER THAN 48" ABOVE FINISHED FLOOR OR PROVIDE LOCK BOX. TRUNK LINE AND LATERALS OK, NO ROOF INSPECTION TODAY,NO DIFFUSERS YET.
| BENH | BENH | | HD | P | 5675396 |
BRUNO'S MECHANICAL INC. | HC | C | 11/01/2017 | RELEASE METER FOR 2 LB SYSTEM. I APOLOGIZE I'M A NEW INSPECTOR AND I WILL TRY NOT FORGET TO INFORM YOU THAT THE SYSTEM IS 2 LB | BENH | BENH | | HC | C | 5674037 |
BRUNO'S MECHANICAL INC. | HC | C | 10/31/2017 | RELEASE METER FOR 2 LB SYSTEM | BENH | BENH | | HC | C | 5671903 |
BRUNO'S MECHANICAL INC. | HI | C | 10/31/2017 | CONTRACTOR INSTALLING VENT FOR WATER HEATER NEEDS TO ADD IT TO SCOPE OF WORK AND CALL FOR INSPECTION WHEN READY..NEED REFRIGERATION CONTRACTOR ATTACHED TO PERMIT. 10 LB TEST OK, INSTALLED AS PER PRINT EXCEPT MAIN LINE INCREASED TO 1 1/2 INCH | BENH | BENH | | HI | C | 5671902 |
BRUNO'S MECHANICAL INC. | P= | C | 12/28/2017 | Corrections made | SHANEN | SHANEN | | P= | C | 5724666 |
BRUNO'S MECHANICAL INC. | P= | P | 12/19/2017 | Adjust tempering at lavatory and hand sink, rest OK | SHANEN | SHANEN | | P= | P | 5717798 |
BRUNO'S MECHANICAL INC. | P= | R | 12/18/2017 | No hot water re-inspect all | SHANEN | SHANEN | | P= | R | 5715916 |
BRUNO'S MECHANICAL INC. | PTO | C | 10/31/2017 | Check water heater at final, Test OK, design per plans | SHANEN | SHANEN | | PTO | C | 5672568 |
BRUNO'S MECHANICAL INC. | PB | C | 10/12/2017 | | JOEL | JOEL | | PB | C | 5652997 |
BRUNO'S MECHANICAL INC. | PB | P | 10/11/2017 | need 3'' for f.s at 3-comp. hand sink must have direct connection, test o.k | JOEL | JOEL | | PB | P | 5651568 |