RIGHTWAY FACILITY SERVICES OF TEXAS, LLC | B= | C | 03/07/2018 | core and shell permit now complete | MINDY | MINDY | | B= | C | 5782241 |
RIGHTWAY FACILITY SERVICES OF TEXAS, LLC | B= | P | 02/16/2018 | Temp CO: TCO extension ( Expires: 3/18/2018 12:00:00 AM) | MINDY | MINDY | | B= | P | 5768159 |
RIGHTWAY FACILITY SERVICES OF TEXAS, LLC | B= | P | 02/13/2018 | No further inspections needed, this permit okay with completed core/shell permit. -- Schedule a new Building Final when above items are complete. | NATHAN | NATHAN | | B= | P | 5763889 |
RIGHTWAY FACILITY SERVICES OF TEXAS, LLC | B= | P | 02/05/2018 | With all completed required blocking inspections and completion of core and shell permit B= okay. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977). | NATHAN | NATHAN | | B= | P | 5756905 |
RIGHTWAY FACILITY SERVICES OF TEXAS, LLC | B= | P | 01/17/2018 | Temp CO: pending building, mechanical and engineering finals ( Expires: 2/16/2018 12:00:00 AM) | MINDY | MINDY | | B= | P | 5740409 |
RIGHTWAY FACILITY SERVICES OF TEXAS, LLC | B= | P | 01/12/2018 | front door lock not installed, need shell completed prior to final inspection of interior finish. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977), DREAM CATCHER MECHANICAL Mechanical Final Inspection is not Completed yet, REEVES SPECIALTY SERVICES, INC. Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5737046 |
RIGHTWAY FACILITY SERVICES OF TEXAS, LLC | B= | P | 01/10/2018 | need all completed required inspections, need indicator lock at front door and signage above for door to remain unlocked, lower soap dispenser to 40" to bottom both restrooms. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, DREAM CATCHER MECHANICAL Mechanical Final Inspection is not Completed yet, GREAT AMERICAN ELECTRIC LLC Electrical Final Inspection is not Completed yet, REEVES SPECIALTY SERVICES, INC. Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5734516 |
LANDMARK PLUMBING AND HEATING, INC. | BSP | T | 01/02/2018 | PAID (REC#1473787) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 1-2-18 | TCRIPPEN | TCRIPPEN | | BSP | T | 5726082 |
RIGHTWAY FACILITY SERVICES OF TEXAS, LLC | BSP | P | 12/29/2017 | NEED PATCH COMPLETED ABOVE HOOD AT KITCHEN, ADD MARKING PROTECT ALL OPENINGS ABOVE CEILING, interior above ceiling penetrations at rated wall okay,NEED CORE AND SHELL COMPLETED BEFORE FINAL INSPECTION CAN BE DONE AT INTERIOR FINISH, | NATHAN | NATHAN | | BSP | P | 5725222 |
RIGHTWAY FACILITY SERVICES OF TEXAS, LLC | BFR | P | 11/28/2017 | framing of all walls and lids okay with completed required MEP's frame items correted. | NATHAN | NATHAN | | BFR | P | 5695753 |
RIGHTWAY FACILITY SERVICES OF TEXAS, LLC | BFR | P | 11/20/2017 | need all completed MEP rough inspections, backing at restroom walls needed, water heater closet not framed at this point. Reviewed Accessible Elements / | NATHAN | NATHAN | | BFR | P | 5690145 |
RIGHTWAY FACILITY SERVICES OF TEXAS, LLC | BFN | P | 11/06/2017 | inspection is called for slab pour which is not an inspection that is required. vapor barrier and welded wire are in place. | NATHAN | NATHAN | | BFN | P | 5677184 |
GREAT AMERICAN ELECTRIC LLC | E= | C | 01/11/2018 | | BRIAN | BRIAN | | E= | C | 5735671 |
GREAT AMERICAN ELECTRIC LLC | E= | P | 01/10/2018 | NEED FUSED DISCONNECTS ON THE EF AND MUA --WITH 15 AMP FUSE----REST OK | BRIAN | BRIAN | | E= | P | 5734703 |
GREAT AMERICAN ELECTRIC LLC | E= | P | 01/09/2018 | DINING--OK ---------------KITCHEN NEEDS PROTECTION ON ISLAND SEALTIGHT ----1 GFCI NOT WORKING UNDER ISLAND---NEED GFCI ON SODA DISPENSER IN KITCHEN ---MOTION SEN IN BATHROOMS-----LABEL MAIN DISCONNECT----OUTSIDE NOT LOOKED AT | BRIAN | BRIAN | | E= | P | 5732846 |
GREAT AMERICAN ELECTRIC LLC | ER | P | 01/03/2018 | KITCHEN AND BACK OF HOUSE CEILINGS--OK | BRIAN | BRIAN | | ER | P | 5727624 |
GREAT AMERICAN ELECTRIC LLC | ES | C | 12/18/2017 | Commercial Service: 400 AMP 4-W ---OK TO SET METER--------------NOTE --NEED LABELS BY FINAL-------- | BRIAN | BRIAN | | ES | C | 5715670 |
GREAT AMERICAN ELECTRIC LLC | ER | P | 12/07/2017 | PANEL WALL---OK | BRIAN | BRIAN | | ER | P | 5706184 |
GREAT AMERICAN ELECTRIC LLC | ER | P | 12/05/2017 | front of store hard lid | BRET | BRET | | ER | P | 5702414 |
GREAT AMERICAN ELECTRIC LLC | ER | P | 11/27/2017 | MOST OF THE HARD LIDS---SEE PLANS---ALL EXCEPT THE DINING AREA-- | BRIAN | BRIAN | | ER | P | 5694768 |
GREAT AMERICAN ELECTRIC LLC | ER | P | 11/20/2017 | PARTIAL WALLS --SEE PLANS FOR APPROVED WALLS--- | BRIAN | BRIAN | | ER | P | 5690477 |
GREAT AMERICAN ELECTRIC LLC | ESL | C | 11/02/2017 | | BRIAN | BRIAN | | ESL | C | 5674308 |
REEVES SPECIALTY SERVICES, INC. | H= | C | 02/02/2018 | AFTER CONSULT WITH PLAN REVIEW ALL ITEMS HAVE BEEN ADDRESSED AND ALL COMPLETE | JERRYF | JERRYF | | H= | C | 5755247 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 02/01/2018 | FAN EXTENSION OK - STILL PLAN SPLICE FOR CO SENSORS | JERRYF | JERRYF | | H= | P | 5754204 |
DREAM CATCHER MECHANICAL | H= | C | 01/17/2018 | OK | JERRYF | JERRYF | | H= | C | 5739675 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 01/12/2018 | NEED GREASE FAN EXTENDED ABOVE PARAPET - CURRENTLY FAN IS 9/2" FROM WALL IMC CALLS FOR 10' - FAN EXHAUST OUTLET IS 1' 3" BELOW TOP OF WALL - NEED CO 2 SENSORS INSTALLED PER MECHANICAL PLAN NOTES ADDED AT 10:00 FAN EXTENSION WILL NEED TO FACTORY APPROVED EXTENSION | JERRYF | JERRYF | | H= | P | 5736481 |
DREAM CATCHER MECHANICAL | H= | P | 01/09/2018 | Missing trap for condensate drain line. ROOF OK . | LIDO | LIDO | | H= | P | 5733082 |
REEVES SPECIALTY SERVICES, INC. | H= | P | 01/09/2018 | Missing concentric vent cap for water heater on roof ( MISSING CO2 SENSORS IN DISH WASHER ROOM AND DINING . MISSING TRAP FOR ROOF TOPS 1 AND 2 NEED GREASE TRAP , NEED TO RESEARCH CLEARANCE FOR KEF ON ROOF .)--- INTERLOCKS FOR KITCHEN HOOD OK. ROOF TOPS LABELED ALL GRD S/A AND R/A FINAL CONNECTIONS OK . | LIDO | LIDO | | H= | P | 5733079 |
REEVES SPECIALTY SERVICES, INC. | HSP | P | 01/09/2018 | RECEIVED TEST AND BALANCE REPORT . | LIDO | LIDO | | HSP | P | 5732424 |
LANDMARK PLUMBING AND HEATING, INC. | H= | C | 01/03/2018 | ALL FINAL GAS CONNECTIONS AND TIE DOWNS AND WATER HEATER OK | JERRYF | JERRYF | | H= | C | 5727515 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 12/26/2017 | 2 nd LAYER OF GREASE WRAP OK. | LIDO | LIDO | | HD | P | 5722156 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 12/21/2017 | ABOVE CEILING SA / RA OK - STILL NEED GREASE WRAP INSPECTION | JERRYF | JERRYF | | HD | P | 5719763 |
DREAM CATCHER MECHANICAL | H= | P | 12/21/2017 | NOT READY - NEED DRAINS AND ROOF INSPECTION | JERRYF | JERRYF | | H= | P | 5719762 |
DREAM CATCHER MECHANICAL | HRP | C | 12/21/2017 | PRESSURE TEST AND PIPING OK | JERRYF | JERRYF | | HRP | C | 5719753 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 12/20/2017 | GREASE DUCT OK FOR 2 LAYERS - MUA DUCT OK TO WRAP | JERRYF | JERRYF | | HD | P | 5718819 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 12/18/2017 | NEED 2 HOLES WELDED AT LEFT DROP NEAR ELBOW - NEED GREASE DAM AT ELBOW TURN MAIN LINE FIXED - NEED PROPER GRADE AT RUN TO TEE | JERRYF | JERRYF | | HD | P | 5715769 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 12/14/2017 | GREASE DUCT LIGHT TEST OK FOR DUCT AND FITTINGS ON FLOOR - STILL NEED ALL CONNECTIONS INSPECTED - DO NOT WRAP | JERRYF | JERRYF | | HD | P | 5712534 |
LANDMARK PLUMBING AND HEATING, INC. | HC | C | 12/13/2017 | RELEASE METER | JERRYF | JERRYF | | HC | C | 5711470 |
LANDMARK PLUMBING AND HEATING, INC. | HI | C | 12/13/2017 | PRESSURE TEST AND PIPING OK PER PLAN - AT FUTURE INSPECTION VERIFY ALL REGS / LABELS AND VENTS NOTES: 2# LETTER IS IN SYSTEM | JERRYF | JERRYF | | HI | C | 5711462 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 12/11/2017 | NEED CONSULT WITH SENIOR INSPECTOR ON HOOD WALL CONSTRUCTION MAY NEED TO OPEN WALL - NOTES :ABOVE CEILING SA / RA / AND MUA DUCT RIGHT ABOVE HOOD AND RESTROOM EXHAUST OK TO INSULATE INCLUDING HARD LID AREA'S AT FRONT OF BUILDING - STILL NEED ALL - STILL NEED REST OF GREASE DUCT AND MUA DUCT | JERRYF | JERRYF | | HD | P | 5708936 |
REEVES SPECIALTY SERVICES, INC. | HD | P | 12/06/2017 | NEED PAGE M0.02 SPLICED INTO PPRBD PLAN SET - GREASE DUCT LIGHT TEST OK ON 4' OF DUCT INCLUDING CURB TRANSITION OK -OK FOR WRAP - NEED INSPECTION OF WASHABLE SURFACE BEHIND HOOD BEFORE IT SECURED TO THE WALL | JERRYF | JERRYF | | HD | P | 5704821 |
REEVES SPECIALTY SERVICES, INC. | HD | R | 12/05/2017 | AUTO CALL COMPLETE AT 9:55 - ARRIVED 10:20 - CONTRACTOR NOT ON SITE FOR GREASE DUCT LIGHT TEST -WILL NEED CONTRACTOR ON SITE FOR NEXT INSPECTION - NEED SHEET ROCK REMOVED ABOVE HOOD FOR INSPECTION OF HOOD WALL TO VERIFY ALL CLEARANCES - STOPPED INSPECTION | JERRYF | JERRYF | | HD | R | 5702496 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 01/05/2018 | Ok. | DANR | DANR | | P= | C | 5730492 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 11/21/2017 | corrections made, revise plans for relocation of hand sink by final. | TAYLOR | TAYLOR | | PTO | C | 5692100 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 11/20/2017 | undersized H2O at hot side, connect trap primer, re-grade vent for mop sink, rest ok, aav's in wall at bar, check water heater by final. | TAYLOR | TAYLOR | | PTO | P | 5690710 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 10/31/2017 | revise plans for relocation of hand sink by final. | TAYLOR | TAYLOR | | PB | C | 5672173 |
LANDMARK PLUMBING AND HEATING, INC. | XMS | P | 01/31/2018 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: added co2 sensor | JUSTINC | JUSTINC | | XMS | P | 5753512 |
GREAT AMERICAN ELECTRIC LLC | XES | T | 01/31/2018 | PAID (REC#1479488) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Add sensor | BERTHA | BERTHA | | XES | T | 5753469 |