GOETZMANN CUSTOM HOMES, INC. | B= | C | 04/18/2018 | finished basement / walkout deck - no stairs | LONNYS | LONNYS | | B= | C | 5820272 |
GOETZMANN CUSTOM HOMES, INC. | BLA | C | 01/30/2018 | | LONNYS | LONNYS | | BLA | C | 5751441 |
GOETZMANN CUSTOM HOMES, INC. | BIN | C | 01/23/2018 | Insulation OK / Check attic at final | NICK | NICK | | BIN | C | 5744938 |
GOETZMANN CUSTOM HOMES, INC. | BFR | C | 01/23/2018 | Frame items complete | NICK | NICK | | BFR | C | 5744932 |
GOETZMANN CUSTOM HOMES, INC. | BFR | P | 01/19/2018 | missing front door to dry in / 2nd garage door bracket missing backing / received engineer letter for altered great room windows and fire place | LONNYS | LONNYS | | BFR | P | 5742467 |
GOETZMANN CUSTOM HOMES, INC. | BSP | P | 01/12/2018 | Rear deck posts and 3 Piers OK | JUSTINL | JUSTINL | | BSP | P | 5737264 |
GOETZMANN CUSTOM HOMES, INC. | BSP | P | 01/03/2018 | Narrow braced walls at garage - Missing 3x3x 3/16 plate washers - OK / Rear porch lid OK / MSTC40 straps on rear of great room OK - will need copy of updated framing at great room rear wall by frame // Plans reviewed on site | JUSTINL | JUSTINL | | BSP | P | 5727959 |
GOETZMANN CUSTOM HOMES, INC. | BFI | C | 11/13/2017 | 2" R-10 Ridged foam OK | JUSTINL | JUSTINL | | BFI | C | 5682845 |
GOETZMANN CUSTOM HOMES, INC. | BFD | C | 11/13/2017 | Drain usable to daylight at East of foundation / Damp proofing OK | JUSTINL | JUSTINL | | BFD | C | 5682826 |
GOETZMANN CUSTOM HOMES, INC. | BFD | P | 11/13/2017 | Drain usable - Still need to inspect | JUSTINL | JUSTINL | | BFD | P | 5682104 |
GOETZMANN CUSTOM HOMES, INC. | BFN | C | 11/13/2017 | Engineer observation for foundation on file / Eufer noted / Foundation design on file | JUSTINL | JUSTINL | | BFN | C | 5682102 |
GOETZMANN CUSTOM HOMES, INC. | BFT | C | 11/13/2017 | Engineer observation for footers on file / Soils and open hole on file - 2400 PSF (Verified) / Drain usable / 5% | JUSTINL | JUSTINL | | BFT | C | 5682100 |
GOETZMANN CUSTOM HOMES, INC. | BFT | P | 11/01/2017 | AUTHORIZED INSPECTION BY ENGINEER | GITA | GITA | GITA | BFT | P | 5672881 |
GOETZMANN CUSTOM HOMES, INC. | BFN | P | 11/01/2017 | AUTHORIZED INSPECTION BY ENGINEER | GITA | GITA | GITA | BFN | P | 5672880 |
PORCH ELECTRIC, INC. | E= | C | 04/03/2018 | Corrections complete / | ROB | ROB | | E= | C | 5805856 |
PORCH ELECTRIC, INC. | E= | R | 04/02/2018 | Need plate on DW/DISP recpt--Lower bath fan making grinding noise / AC Installed--40/2 in panel--MOP 40--MCA 24.3 / | ROB | ROB | | E= | R | 5805001 |
PORCH ELECTRIC, INC. | ES | C | 01/18/2018 | Residential Underground: 200-amp 3 Wire service, ok to set meter / new res | JOHNN | JOHNN | | ES | C | 5741325 |
PORCH ELECTRIC, INC. | ER | C | 01/18/2018 | rough,ok--------------------------------rev ufer,no mcc, 100 amp sub in basement,ok | JOHNN | JOHNN | | ER | C | 5741323 |
OLYMPIA HEATING & COOLING INC. | H= | C | 04/05/2018 | | BILLS | BILLS | | H= | C | 5808980 |
OLYMPIA HEATING & COOLING INC. | H= | R | 03/30/2018 | NO CORRECTIONS MADE | BILLS | BILLS | | H= | R | 5803872 |
OLYMPIA HEATING & COOLING INC. | H= | P | 03/29/2018 | NEED TO WEATHER SEAL LINESET AT EXTERIOR, FURNACE SHUT OFF SWITCH NEEDS A COVER PLATE. OK TO ATTACH PICTURES AT NEXT INSPECTION REQUEST NOTE: FINISHED BASEMENT, INDIRECT VENT FURNACE, FULL A/C, NO OUTSIDE AIR, LOUVER DOOR AT MECHANICAL ROOM | BILLS | BILLS | | H= | P | 5802680 |
PLATINUM PLUMBING INC | HC | C | 01/18/2018 | RELEASE METER | DAVIDH | DAVIDH | | HC | C | 5741463 |
PLATINUM PLUMBING INC | HI | C | 01/18/2018 | 10 LB TEST OK NOTE 1 1/4" LINE 1 FURN,W/H,C/T AND 2 F/P | DAVIDH | DAVIDH | | HI | C | 5741460 |
OLYMPIA HEATING & COOLING INC. | HRR | C | 01/17/2018 | EQUIP CHECK OK NOTE FINISHED BASEMENT, A/C ROUGH | DAVIDH | DAVIDH | | HRR | C | 5740369 |
FRONTIER MECHANICAL SYSTEMS INC | P= | C | 04/09/2018 | pvb installed, finished basement. | TAYLOR | TAYLOR | | P= | C | 5811095 |
FRONTIER MECHANICAL SYSTEMS INC | PTO | C | 01/17/2018 | Corrections made. | DANR | DANR | | PTO | C | 5739456 |
FRONTIER MECHANICAL SYSTEMS INC | PTO | P | 01/16/2018 | s- trap left lav at north basement bath, support vent above ceiling and move hot water line forward for insulation at south basement lav, rest ok, aav's at both sinks at bar and double lavs at north basement bath, check meter at final. | TAYLOR | TAYLOR | | PTO | P | 5738140 |
FRONTIER MECHANICAL SYSTEMS INC | PB | C | 11/20/2017 | | TAYLOR | TAYLOR | | PB | C | 5689981 |