RAINE BUILDING LLC. | B= | C | 01/17/2018 | All other required Final inspections are complete. (This is a computer generated result) | RICHB | RICHB | | B= | C | 5739556 |
RAINE BUILDING LLC. | B= | P | 12/08/2017 | Previous items completed. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982). | RICHB | RICHB | | B= | P | 5707227 |
RAINE BUILDING LLC. | B= | R | 12/07/2017 | Need front egress door corrections made (see IBC 1008.1.9.1) - discussed these items with Contractor / need under-sink pipe protection in all restrooms / complete other Finals / plans & IBC reviewed onsite. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), GREINER ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, JOHNSON BROTHERS PLUMBING & HEATING Mechanical Final Inspection is not Completed yet. | RICHB | RICHB | | B= | R | 5706167 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | BSP | T | 11/27/2017 | PAID (REC#1467809) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 11-27-2017 | TCRIPPEN | TCRIPPEN | | BSP | T | 5695150 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | BSP | P | 11/21/2017 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical: splice to revise return air | DALEH | DALEH | | BSP | P | 5691385 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | BSP | T | 11/17/2017 | PAID (REC#1466505) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 11-17-2017 | TCRIPPEN | TCRIPPEN | | BSP | T | 5688751 |
RAINE BUILDING LLC. | BFR | P | 11/16/2017 | Interior non-rated non-bearing framing OK pending other roughs / reviewed accessible elements / reviewed paths of egress and door hardware / reviewed existing 3-hr fire-rated wall (UL V489) between units - wall is not going to be altered or opened up / plans reviewed onsite | RICHB | RICHB | | BFR | P | 5687519 |
GREINER ELECTRIC, LLC. | E= | C | 12/07/2017 | | CRAIGS | CRAIGS | | E= | C | 5706203 |
GREINER ELECTRIC, LLC. | ER | C | 12/06/2017 | above ceiling OK | CRAIGS | CRAIGS | | ER | C | 5704939 |
GREINER ELECTRIC, LLC. | ER | P | 11/20/2017 | Discussed accessiblity requirements with contractor / the rest of the walls | CRAIGS | CRAIGS | | ER | P | 5690071 |
GREINER ELECTRIC, LLC. | ER | P | 11/16/2017 | walls marked on the drawings | CRAIGS | CRAIGS | | ER | P | 5687636 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | H= | C | 12/08/2017 | Test And Balance received | MARKB | MARKB | | H= | C | 5707081 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | H= | P | 12/05/2017 | FINAL PENDING TAB REPORT. | MARKB | MARKB | | H= | P | 5702512 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | HD | C | 12/05/2017 | SPLICE OK, ALL FLEX, DIFFUSERS, RETURNS AND TRANSFER AIRS INSTALLED. | MARKB | MARKB | | HD | C | 5702510 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | HD | P | 11/20/2017 | ABOVE CEILING DUCT AND EF 1-4 INSTALLED PER PLAN EXCEPT NEED ENGINEER TO ADDRESS TRANSFER AIR OPENINGS AND ABOVE CEILING RETURN. Still need flex, diffusers and TAB report. | MARKB | MARKB | | HD | P | 5690188 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | P= | C | 12/06/2017 | | JOHNS | JOHNS | | P= | C | 5704756 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | P= | P | 12/05/2017 | need flush handle @ water closet (x2) on open side, caulk d.f., hard cap @ future d.f., need t&p @ water htr, rest ok. | JOHNS | JOHNS | | P= | P | 5703022 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | PTO+ | C | 11/28/2017 | ok for future use d.f. @ fitness room area, NOTE: VTR ( EXISTING) ROUGH IN ONLY @ THIS TIME | JOHNS | JOHNS | | PTO+ | C | 5695762 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | PTO | C | 11/20/2017 | ok for dwv / water test and design per plan, water htr in and inspected. note: vtr (1) new 3", need to verify water htr pan drain down to mop sink @ final | JOHNS | JOHNS | | PTO | C | 5690051 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | PB | C | 11/09/2017 | GC TO ATTACH ELEC PERMIT, rest ok for PB, test and design per plan. note: water pre existing @ water entry room, will tie in above ceiling
**WATER UNDER SIZED ON PLANS FOR WATER CLOSETS, PLANS SHOW 3/4, NEEDS TO BE 1"** | JOHNS | JOHNS | | PB | C | 5681067 |