GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 12/27/2017 | All other required Final inspections are complete. (This is a computer generated result) | BERTW | BERTW | | B= | C | 5722721 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 12/22/2017 | . Additional Inspections Required (computer generated): MECH ONE, INC. Mechanical Final Inspection is not Completed yet. | BERTW | BERTW | | B= | P | 5721194 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 12/19/2017 | need damper installed per mechanical inspection, remaining penetrations and framing are per attached UL listings | NATHAN | NATHAN | | BSP | P | 5717770 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 12/12/2017 | attached letters to images for frame items listed on inspection from 11-29 by Bert, no inspection done. Letters appear to address all listed corrections. | NATHAN | NATHAN | | BSP | P | 5709632 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/29/2017 | need all trades attached/framing inspection for wall and ceiling ok/ listings need to be used properly or revised-UL V489 calls for AGX-1 American or Georgia Pacific rock where usg is going to be used-headwall HW-D-0624 won t work with this field condition its a proprietary listing with listed tracks etc,need revised headwall detail and inspection for sheetrocking and also have a spinkler pipe that needs detail for penetrating item/IBC tabled listing 720-1,13-1.3 ok on revised plan sheet for scanning for horizontal lid portion | BERTW | BERTW | | BFR | P | 5697067 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 12/22/2017 | | CRAIGS | CRAIGS | | E= | C | 5720974 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | C | 12/07/2017 | | CRAIGS | CRAIGS | | ER | C | 5705910 |
MECHONE, INC. | H= | C | 12/27/2017 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 5722720 |
MECHONE, INC. | H= | P | 12/21/2017 | PARTIAL PENDING TAB REPORT - FIRE DAMPER GAP AND RETAINAGE OK - ALL GRILLES ARE COMPLETE | JERRYF | JERRYF | | H= | P | 5720220 |
MECHONE, INC. | HD | P | 12/20/2017 | FIRE DAMPER FRAMING OK | JERRYF | JERRYF | | HD | P | 5718416 |
MECHONE, INC. | H= | L | 12/19/2017 | NOT READY NEED FRAMING INSPECTED AND DAMPER INSTALLED - DAMPER WILL NEED TO MEET UL489 | JERRYF | JERRYF | | H= | L | 5717736 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 12/22/2017 | dwv and water ok for test and design per plan. note: vtr (existing) | JOHNS | JOHNS | | PTO | C | 5720945 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 12/22/2017 |
| JOHNS | JOHNS | | P= | C | 5720943 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 12/11/2017 | gc needs to attach mech permit, ok for dwv in wall and under belly, test and design per plan, ok for in wall water design only per plan, still need water test. note: hammer aerestor @ clinical sink above ceiling **still need above ceiling inspection** | JOHNS | JOHNS | | PTO | P | 5708614 |