KENNY ELECTRIC SERVICE, INC. | E= | C | 09/12/2022 | | BRIAN | BRIAN | | E= | C | 7513200 |
KENNY ELECTRIC SERVICE, INC. | E= | P | 09/08/2022 | will need site inspection / | BRIAN | BRIAN | | E= | P | 7509640 |
KENNY ELECTRIC SERVICE, INC. | E= | P | 04/23/2022 | from city xfmr to fire pump disconnect 2 sets of 500 mc cu ------------- from fire pump disconnect to fire pump 2 set 500mcm with 500 mcm grd wire ok -------------- gec ok -------------------- jockey is feed from panel B circuits 13, 15, 17 on 30 amp to fused disconnect ok ---------------- need to verify new set of plans are approved | CRAIG | CRAIG | | E= | P | 7349895 |
KENNY ELECTRIC SERVICE, INC. | ES= | T | 04/20/2022 | PAID (REC#1860227) AFTER-HOURS INSPECTION: $200 From: MATTHEW April 23rd Craig Knox will do inspection | MATTHEW | MATTHEW | | ES= | T | 7345361 |
KENNY ELECTRIC SERVICE, INC. | E= | R | 04/05/2022 | cancelled by contractor / | BRIAN | BRIAN | | E= | R | 7325798 |
KENNY ELECTRIC SERVICE, INC. | EE | L | 03/24/2022 | Renewed online for Full Fee at Mar 24 2022 12:21PM (RECEIPT #: 1853127) | WEBSITE | WEBSITE | | EE | L | 7313350 |
KENNY ELECTRIC SERVICE, INC. | EE | C | 03/09/2021 | | BRITNEY | BRITNEY | | EE | C | 6892857 |
KENNY ELECTRIC SERVICE, INC. | EE | P | 10/05/2020 | Renewed for No Fee at 10/5/2020 11:49:04 AM | DEAN | DEAN | | EE | P | 6729543 |
KENNY ELECTRIC SERVICE, INC. | E= | R | 12/02/2019 | see service | BRIAN | BRIAN | | E= | R | 6412767 |
KENNY ELECTRIC SERVICE, INC. | ES | R | 12/02/2019 | Commercial Service: need to sch inspection to open the gear for inspection / need to choke the raceway for the GEC on both ends / complete reinspect / labels / splice the plans to reflect the work done / | BRIAN | BRIAN | | ES | R | 6412765 |
KENNY ELECTRIC SERVICE, INC. | EE | L | 08/15/2019 | Renewed for $50.00 at 8/15/2019 1:59:14 PM (Receipt#1622594) | TERRI | TERRI | | EE | L | 6302466 |
KENNY ELECTRIC SERVICE, INC. | E= | P | 06/19/2018 | need to go over prints with Mr, Shelby | GARYL | GARYL | | E= | P | 5878947 |
KENNY ELECTRIC SERVICE, INC. | ES | P | 05/11/2018 | Commercial Service: Pre release ok. ------------One Saturday shutdown to remove 2 of the existing parallel runs, and re-energize. Second shutdown Sunday to pull new parallel conductors to new FP disconnect and re-energize. | DEAN | DEAN | | ES | P | 5842407 |
KENNY ELECTRIC SERVICE, INC. | EE | L | 05/11/2018 | Renewed at 5/11/2018 11:50:15 AM | DEAN | DEAN | | EE | L | 5842401 |
KENNY ELECTRIC SERVICE, INC. | XES | T | 09/02/2022 | PAID (REC#1896512): PLAN SPLICE FEE: $50 by: DANIELG for Electrical: Revised one-line. Sheet E.101 | DANIELG | DANIELG | | XES | T | 7505113 |