ENCORE ELECTRIC, INC. | E= | C | 11/29/2018 | | JOHNN | JOHNN | | E= | C | 6037431 |
ENCORE ELECTRIC, INC. | E= | P | 11/14/2018 | transformer #4 needs 45 amp max fuse, has 50 amp, ok to upload pics, #3,ok, | JOHNN | JOHNN | | E= | P | 6025295 |
ENCORE ELECTRIC, INC. | EE | C | 10/18/2018 | | GITA | GITA | | EE | C | 5998638 |
ENCORE ELECTRIC, INC. | EP | P | 04/30/2018 | Elevator #1 & #2 ok | ROB | ROB | | EP | P | 5830851 |
ENCORE ELECTRIC, INC. | EP | P | 02/02/2018 | elevator #2, complete, | JOHNN | JOHNN | | EP | P | 5755632 |
ENCORE ELECTRIC, INC. | ER | C | 01/16/2018 | FIRE ALARM INSPECTION: | JOHNN | JOHNN | | ER | C | 5738052 |
ENCORE ELECTRIC, INC. | E= | C | 01/16/2018 | FIRE ALARM INSPECTION: | JOHNN | JOHNN | | E= | C | 5738053 |
ENCORE ELECTRIC, INC. | E16 | P | 01/12/2018 | Consultation for Elevator equipment room / | ROB | ROB | | E16 | P | 5736668 |
ENCORE ELECTRIC, INC. | EP | P | 01/02/2018 | elevator #5:ok, sump pump run to j box near pit,ok,pump not installed | JOHNN | JOHNN | | EP | P | 5726120 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | C | 11/19/2019 | Corrections made | ERIC | ERIC | | HE= | C | 6403922 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 03/12/2019 | NEED COLO SPRGS FIRE DEPARTMENT INSPECTION ON ELEVATORS, CAB CEILING FASTENERS ON ELEVATORS #2 AND #3 THAT PENETRATE CAB NEED TO BE TRIMMED AT CAR TOP. NEED CONTRACTOR THAT INSTALLED SUMP PUMP TO ATTACH TO PERMIT AND REQUEST INSPECTION, REST OK. | ROBERTV | ROBERTV | | HE= | P | 6131310 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 09/13/2018 | NEED INSTALLATION OF FIRE SPRINKLER, SUMP PUMP AND HEAT DETECTOR IN ELEVATOR PIT #5 COMPLETED. NEED CODE DATA TAGS FOR EACH ELEVATOR CONTROLLER. NEED TAC32T INSPECTORS GUIDE WITHIN TRACTION ELEVATORS MAINTENANCE CONTROL PROGRAM. NEED FIRE FINAL INSPECTION FROM COLORADO SPRINGS FIRE DEPARTMENT. | ROBERTV | ROBERTV | | HE= | P | 5964831 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 08/23/2018 | (Building Owner Responsibility) 1. Generator testing needs to be completed for all elevators. 2. Elevator #4 lobby and machine room fire initiating devices need to be tested individually and shall perform elevator recall as required. 3. Elevator #5 needs to have the Sump Pump and Fire Sprinkler installation completed. 4. Elevator Penthouse Machine Room door needs to be installed correctly to close completely. 5. Install cushion type protection around base of suspended cooling unit in elevator machine room. (Elevator Contractor Responsibility) 1. The Fire Command Center Elevator Panel installation needs completed. 3. Fire Command Center phone needs to provide two-way communication. 4. Elevator Controllers needs to have Code Data Tags installed. 5. Maintenance Control Programs and Unique Procedures needs to be with each elevator controller. 6. Generator testing. ------ Elevator #4 will be on 30 temporary operating permit and Elevator #5 will be on 60 day temporary operating permit | ROBERTV | ROBERTV | | HE= | P | 5943338 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 07/09/2018 | (ELEVATOR #1) - NEED ELECTRICAL IN PIT FINISHED, NEED ELEVATOR # SIGNAGE ON DOOR JAMB AT EGRESS LANDING, NEED ADDITIONAL LIGHTING ON CARTOP. NEED UPDATED CROSSHEAD DATA TAG REFLECTING NEW SUSPENSION MEANS. STILL NEED TO VERIFY EMERGENCY POWER OPERATION ON GENERATOR POWER AND VERIFY OPERATING PANEL WITH INSTRUCTIONS. SPRINKLERS AND MISSING FIRE ALARM INITIATING DEVICES AT TOP OF HOISTWAY WILL BE ADDRESSED BEFORE FINAL, MACHINE ROOM DOOR DOES NOT SELF CLOSE COMPLETELY. LOBBY AND MACHINE ROOM SMOKE DETECTORS HAVE BEEN TESTED WITH FIRE ALARM COMPANY AND THEY ARE WORKING CORRECTLY FOR ELEVATORS #1 THRU #3 ONLY IN BYPASS MODE AND NOT AUTO MODE. JEFF LOVELESS FROM CSFD IS TO DEEM APPROPRIATE ACTION | ROBERTV | ROBERTV | | HE= | P | 5897752 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 04/12/2018 | (ELEVATOR # 3) NEED FIRE FINAL, NEED MACHINE ROOM CONDITIONING TO BE OPERABLE, NEED ELECTRICAL IN PIT FINISHED, STILL NEED TO VERIFY EMERGENCY POWER OPERATION ON GENERATOR POWER AND VERIFY FIRE COMMAND CENTER WITH INSTRUCTIONS. REMOVE FIRE SPRINKLERS AND MISSING FIRE ALARM INITIATING DEVICES AT TOP OF HOISTWAY WILL BE ADDRESSED BEFORE FINAL. | ERIC | ERIC | | HE= | P | 5815744 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 02/15/2018 | (ELEVATOR #2) - NEED MACHINE ROOM COOLING TO BE OPERABLE, NEED ELECTRICAL IN PIT FINISHED, NEED ELEVATOR # SIGNAGE ON DOOR JAMB AT EGRESS LANDING, NEED ADDITIONAL LIGHTING ON CARTOP. NEED UPDATED CROSSHEAD DATA TAG REFLECTING NEW SUSPENSION MEANS. STILL NEED TO VERIFY EMERGENCY POWER OPERATION ON GENERATOR POWER AND VERIFY OPERATING PANEL WITH INSTRUCTIONS. SPRINKLERS AND MISSING FIRE ALARM INITIATING DEVICES AT TOP OF HOISTWAY WILL BE ADDRESSED BEFORE FINAL. | ROBERTV | ROBERTV | | HE= | P | 5766389 |
THYSSENKRUPP ELEVATOR CORPORATION | HE= | P | 01/19/2018 | HYDRO #5 MOD COMPLETE EXCEPT FOR PIT ELECTRICAL, SUMP SYSTEM, BACK UP GENERATOR TIE-IN AND TESTING, FIRE ALARM TESTING | ERIC | ERIC | | HE= | P | 5742068 |