HASELDEN CONSTRUCTION,LLC | B= | C | 12/17/2019 | | BOBF | BOBF | | B= | C | 6429521 |
HASELDEN CONSTRUCTION,LLC | B= | P | 09/12/2019 | need to complete elec and mech finals / need revised smoke barrier listing using American type x -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): BERWICK ELECTRIC CO Electrical Final Inspection is not Completed yet, MECH ONE, INC. Mechanical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 6332681 |
HASELDEN CONSTRUCTION,LLC | BFR | P | 07/09/2019 | pending other required inspections new walls and wall infills okay , will need to revised listing for 1 hour smoke barrier between rooms 510K and 460 D, currently is a a U 419, requiring USG drywall, american drywall stocked | BOBF | BOBF | | BFR | P | 6256919 |
HASELDEN CONSTRUCTION,LLC | BE | C | 01/29/2019 | Renewed at 1/29/2019 8:04:31 AM | BECKYA | BECKYA | | BE | C | 6090600 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 11/06/2019 | phase 2 | BRIAN | BRIAN | | E= | C | 6390369 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 09/09/2019 | phase 1 complete / phase 2 is light change out in the other half if area / | BRIAN | BRIAN | | E= | P | 6328311 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | P | 09/04/2019 | still need 15 amp breakers on the FFA units / have power hanging through the header of the door ways in room 0510T / | BRIAN | BRIAN | | E= | P | 6323229 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 09/04/2019 | FIRE ALARM INSPECTION: | BRIAN | BRIAN | | E= | C | 6323213 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | R | 08/21/2019 | FIRE ALARM INSPECTION: no plans on site / do not know scope of work ?? | BRIAN | BRIAN | | E= | R | 6309716 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | R | 08/21/2019 | NEED FIRE ALARM INSPECTION and plans for fire alarm on site / open j boxes / wires hanging out of emt room 0510T / support ceiling mounted smokes / support the emt FFA#4 / max 15 amp ocp on FFA units / | BRIAN | BRIAN | | ER | R | 6309715 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 07/08/2019 | Electrical wall rough ok, FA not complete,-------- do not close walls-------------- / | JOSEPH | JOSEPH | | ER | P | 6255364 |
MECHONE, INC. | H= | C | 10/21/2019 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | C | 6374360 |
MECHONE, INC. | H= | P | 09/26/2019 | PARTIAL PENDING TAB REPORT NOTES: ROOF DUCT AND EXHAUST FANS OK | JERRYF | JERRYF | | H= | P | 6349072 |
MECHONE, INC. | H= | P | 09/25/2019 | RETAINING ANGLE PICTURE RECEIVED - STILL NEED OTHER ITEMS ADDRESSED | JERRYF | JERRYF | | H= | P | 6346882 |
MECHONE, INC. | HD | P | 08/16/2019 | ABOVE CEILING SA / RA AND EXHAUST MAINS AND RUN OUTS AND SHAFT FROM BASEMENT THROUGH TO ROOF OK - STILL NEED ROOF DUCT COMPLETED | JERRYF | JERRYF | | HD | P | 6303822 |
MECHONE, INC. | HD | P | 07/19/2019 | ANTE-ROOM # 0150R : UNIT DD-05 -10 FEET OF 20 X 12 SUPPLY DUCT WITH 4 - 12" SPINS WITH DAMPERS OK / OK TO WRAP /NEED TO COMPLETE INSTALL. ROOM # 0510S : DD - 07 - 7 FEET OF 14 X 10 SUPPLY IN ROOM ONLY OK / OK TO WRAP / NEED TO COMPLETE INSTALL. ((ROOM # 0510T: DD-09 EXISTING UNIT - DUCT ROUGH COMPLETE / OK TO WRAP. NEED TO SEE FIRE DAMPER ANGLES AND ACCESS DOOR IN ROOM # 0422 FOR THIS DUCT)) | LIDO | LIDO | | HD | P | 6269727 |
MECHONE, INC. | HD | P | 07/05/2019 | SHAFT DUCT ROUGH FOR 34 X 14 DUCT PASSING THROUGH ROOM # 510K,0460D, 0460C. STOPPED BEFORE DOUBLE ELBOWS OK. | LIDO | LIDO | | HD | P | 6254155 |
MECHONE, INC. | HD | P | 06/26/2019 | FIRE SMOKE DAMPER FRAME OK . | LIDO | LIDO | | HD | P | 6244878 |
MECHONE, INC. | HD | P | 06/25/2019 | FIRE / SMOKE DAMPER OPENING IS NOT FRAMED PER INSTALLATION INSTRUCTIONS / RE-INSPECT FRAMING. | LIDO | LIDO | | HD | P | 6243106 |
MECHONE, INC. | HD | P | 06/24/2019 | NEED TO FRAME FIRE/SMOKE DAMPER OPENING PER THE INSTALLATION INSTRUCTIONS/ NEED TO RE-INSPECT DAMPER FRAMING. | LIDO | LIDO | | HD | P | 6241302 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 08/27/2019 | Ok. | DANR | DANR | | P= | C | 6315140 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 08/27/2019 | Ok. | DANR | DANR | | PTO | C | 6315137 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 07/08/2019 | Ok to insulate domestic water pipe (picture of in wall ok), rest ok. Note: discussed accessible elements, check over head insulation and rec. balance valve at final. | DANR | DANR | | PTO | P | 6255487 |
HASELDEN CONSTRUCTION,LLC | XES | P | 03/25/2019 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: As builts for circuiting and hoods | SHELBY | SHELBY | | XES | P | 6143954 |
HASELDEN CONSTRUCTION,LLC | XMS | T | 03/25/2019 | PAID (REC#1611748): PLAN SPLICE FEE: $50 by: DALEH for Mechanical: delta2 | DALEH | DALEH | | XMS | T | 6142673 |
HASELDEN CONSTRUCTION,LLC | XPS | T | 03/22/2019 | PAID (REC#1611753): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Plumbing splice 3/22/19: New wall hung pharmacy sink detail and schedules | SHANEN | SHANEN | | XPS | T | 6141783 |
HASELDEN CONSTRUCTION,LLC | XBS | T | 03/22/2019 | PAID (REC#1611755): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Clarification of scope of work | MICHAELA | MICHAELA | | XBS | T | 6141699 |