HOMEOWNER | B= | C | 06/29/2021 | | CHRISTINEH | CHRISTINEH | | B= | C | 7018432 |
HOMEOWNER | B= | P | 07/01/2019 | . Additional Inspections Required (computer generated): External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977). | BOBF | BOBF | | B= | P | 6249185 |
HOMEOWNER | BFT | C | 07/01/2019 | open hole and design on file, bearing capacity verified | BOBF | BOBF | | BFT | C | 6249183 |
HOMEOWNER | BE | L | 05/31/2019 | Renewed at 5/31/2019 2:23:43 PM | JANE | JANE | | BE | L | 6216627 |
HOMEOWNER | B= | P | 10/26/2018 | Final OK / slab on grade - no deck - no AC. Additional Inspections Required (computer generated): External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977), External Agency Inspection UBS by CSUREVIEW is not Completed yet (Contact: 668-3524), External Agency Inspection UWS by CSUREVIEW is not Completed yet (Contact: 668-3524). | RICHB | RICHB | | B= | P | 6007986 |
HOMEOWNER | BIN | C | 08/28/2018 | Previous item complete | RICHB | RICHB | | BIN | C | 5947393 |
HOMEOWNER | BFR | C | 08/28/2018 | Previous item complete | RICHB | RICHB | | BFR | C | 5947391 |
HOMEOWNER | BLA | C | 08/28/2018 | Stucco cutout & lath verification done by Inspector Parker M at same time as L33800 | RICHB | RICHB | | BLA | C | 5947386 |
HOMEOWNER | BFT | C | 08/28/2018 | Stamped foundation design received by Inspector Parker M on Aug 21, 2018 | RICHB | RICHB | | BFT | C | 5947382 |
HOMEOWNER | BSP | P | 08/17/2018 | Open hole and soils report received - Request copy of stamped foundation design prior to any further inspections : NOTE - No lath inspection performed - Expose 24" X 24" section for lath inspection | JUSTINL | JUSTINL | | BSP | P | 5938593 |
HOMEOWNER | BIN | R | 04/09/2018 | Reviewed field copy of Open Hole - 1500 psf bearing / need stamped copy of Open Hole and stamped copy of Foundation Design prior to any further inspections - spoke with personnel onsite about this / insulation OK but inspection is Rejected due to outstanding paperwork | RICHB | RICHB | | BIN | R | 5811922 |
HOMEOWNER | BFR | P | 04/03/2018 | BFR added at Homeowner request / framing OK pending other Roughs / plans reviewed onsite | RICHB | RICHB | | BFR | P | 5806736 |
HOMEOWNER | BFT | R | 04/03/2018 | Still need paperwork previously noted (and indicated on RBD plans) - spoke with Homeowner about this | RICHB | RICHB | | BFT | R | 5806730 |
HOMEOWNER | BFT | P | 02/27/2018 | Forms & excavation for 7' addition onto detached garage OK / plans reviewed onsite ///// UPDATED COMMENT - changed to partial - need stamped foundation design and open hole observation uploaded or on-hand at time of next inspection | RICHB | RICHB | | BFT | P | 5775739 |
P&L ELECTRIC INC. YOUR QUALITY CONNECTION | E= | C | 08/22/2018 | | CRAIGS | CRAIGS | | E= | C | 5942056 |
HOMEOWNER | E= | R | 08/20/2018 | MUST use an afci/gfci breaker -- the gfci can not go behind the washer !!!! | CRAIGS | CRAIGS | | E= | R | 5940056 |
HOMEOWNER | E= | R | 08/17/2018 | washer circuit has to be afci/gfci protected , must use a breaker , cant have the gfci behind the washer | CRAIGS | CRAIGS | | E= | R | 5938573 |
P&L ELECTRIC INC. YOUR QUALITY CONNECTION | ER | P | 03/16/2018 | walls only, service not ready | GARYL | GARYL | | ER | P | 5791715 |
P&L ELECTRIC INC. YOUR QUALITY CONNECTION | ER | R | 03/14/2018 | couldn't get in due to stuccoing | GARYL | GARYL | | ER | R | 5788964 |
P&L ELECTRIC INC. YOUR QUALITY CONNECTION | ER | R | 03/13/2018 | Not Ready | CRAIG | CRAIG | | ER | R | 5786937 |
ERNST ENTERPRISES | H= | C | 11/01/2018 | | JERRYF | JERRYF | | H= | C | 6012645 |
HOMEOWNER | H= | C | 10/25/2018 | TRANSFER GRILLE IS COMPLETE | JERRYF | JERRYF | | H= | C | 6005459 |
ERNST ENTERPRISES | H= | P | 10/24/2018 | HAS SOLID DOOR AT LAUNDRY ROOM - GRILLE IN DOOR IS TO SMALL - NEED MINIMUM 200 SQUARE INCH TRANSFER FOR 44000 FURNACE - 38000 WATER HEATER AND 100 SQUARE INCHES FOR DRYER NOTES: LOUVERED DOOR TO MECHANICAL ROOM FROM LAUNDRY ROOM | JERRYF | JERRYF | | H= | P | 6004611 |
ERNST ENTERPRISES | H= | P | 10/24/2018 | DUCT LEAKAGE REPORT RECEIVED | JERRYF | JERRYF | | H= | P | 6003982 |
ERNST ENTERPRISES | H= | P | 09/28/2018 | ADDED TO NOTES 10/1/18 (LM) NEED TO VERIFY MAKE UP AIR FOR LAUNDRY ROOM .NEED DUCT LEAKAGE REPORT . THERE IS NO COMBUSTION AIR TRANSFER BACK TO MECHANICAL ROOM / WENT OVER OPTIONS WITH HOME OWNER. NEED TO INSTALL A INSULATION SHIELD. NOTES: OUTSIDE AIR TO RETURN AIR. | LIDO | LIDO | | H= | P | 5979994 |
ERNST ENTERPRISES | HO | C | 05/04/2018 | PRESSURE TEST AND 11/4" PE WITH TRACER OK TO BURY - BEFORE METER RELEASE NEED APPLIANCES CAPPED OR CONNECTED | JERRYF | JERRYF | | HO | C | 5835878 |
ERNST ENTERPRISES | HI | C | 05/04/2018 | PRESSURE TEST AND PIPING OK - BEFORE METER RELEASE NEED LINES CAPPED OR CONNECTED AT APPLIANCES - 11/4" FURNACE AND WATER HEATER | JERRYF | JERRYF | | HI | C | 5835877 |
ERNST ENTERPRISES | HD | C | 04/02/2018 | BY FINAL, NEED DUCT LEAKAGE TEST, NEED TO CONFIRM OUTSIDE AIR. NOTE: FOR HD INSPECTION, OK TO COVER | BILLS | BILLS | | HD | C | 5804778 |
COPPER MINE PLUMBING AND HEATING INC. | P= | C | 09/21/2018 | Correction made, electrical done under permit L79358. | DANR | DANR | | P= | C | 5972044 |
COPPER MINE PLUMBING AND HEATING INC. | P= | P | 09/05/2018 | Need electrical permit and inspection for dedicated circuit for ejector pump, rest ok. | DANR | DANR | | P= | P | 5955044 |
COPPER MINE PLUMBING AND HEATING INC. | P= | P | 08/24/2018 | Vent needs to be properly terminated per IPC 903.6, must be 10' above ground level with proper support and rodent protection. Need electrical permit and inspection for designated outlet for ejector pump. Trip fee waived this time | DANR | DANR | | P= | P | 5944746 |
COPPER MINE PLUMBING AND HEATING INC. | P= | P | 08/23/2018 | New sewage ejector in existing house needs permit , ejector vent needs terminated properly, leak ejector pump line, pump needs dedicated electrical circuit - electrical permit and inspection. | DANR | DANR | | P= | P | 5943330 |
COPPER MINE PLUMBING AND HEATING INC. | P= | P | 08/22/2018 | Need access and escort to check tie ins main house, need trap guard, rest ok. | DANR | DANR | | P= | P | 5942014 |
COPPER MINE PLUMBING AND HEATING INC. | P= | P | 08/17/2018 | hot and cold flipped at tub, loose shower arm, need trap guard mechanical room floor drain, , need access and escort to look at drain and water tie ins at main house, rest ok. | DANR | DANR | | P= | P | 5937492 |
COPPER MINE PLUMBING AND HEATING INC. | PTO | C | 04/02/2018 | correction made, listing verified for tub valve | JOHNS | JOHNS | | PTO | C | 5805093 |
COPPER MINE PLUMBING AND HEATING INC. | PTO | P | 03/29/2018 | need listing for tub valve, (found no paper work on site) need to expose wrap @ kitchen water line (the one on right side,) rest ok. note: vtr (1) @ north side of house, aav @ mech room floor drain, @ lav, and @ washer box in wall @ right side w/ louver panel by final, no irrigation, BY FINAL NEED TO SEE DRAIN AND WATER TIE IN @ EXISTING HOUSE, BY FINAL NEED TO SUPPORT VERTICAL PEX @ MECH ROOM, BY FINAL NEED EXPANSION DEVICE | JOHNS | JOHNS | | PTO | P | 5802229 |
COPPER MINE PLUMBING AND HEATING INC. | PB | C | 03/05/2018 | corrections made, see images | JOHNS | JOHNS | | PB | C | 5779369 |
COPPER MINE PLUMBING AND HEATING INC. | PB | P | 03/02/2018 | ok for main water wrapped, still need images of lines through foundation, water closet, and lav lines wrapped | JOHNS | JOHNS | | PB | P | 5778313 |
COPPER MINE PLUMBING AND HEATING INC. | PB | R | 02/21/2018 | trip fee waived this time only, need arm a flex @ main water @ mech room, all the lines going through existing foundation, water closet line, and lav lines (all pex lines in or coming through the concrete) | JOHNS | JOHNS | | PB | R | 5770276 |
COPPER MINE PLUMBING AND HEATING INC. | PB | P | 02/20/2018 | need arm a flex @ all water pipes coming through / in concrete (duct tape not approved), ok for all other corrections | JOHNS | JOHNS | | PB | P | 5768767 |
COPPER MINE PLUMBING AND HEATING INC. | PB | P | 02/13/2018 | requires colo spgs utilities inspection for drain and water outside of structure, cant have water lines below bldg drain, need to wrap all pex lines coming through / in concrete, need bldg drain stubbed out of structure 2', need to see main water line stubbed into structure (42" min depth coming into the structure),**need to verify house tie in @ drain and water @ pto inspection** rest ok. note: domestic waters looped underground (to be tested @ pto) | JOHNS | JOHNS | | PB | P | 5764169 |