PUNCH LIST PRO'S OF COLORADO LLC | B= | C | 03/18/2022 | All other required Final inspections are complete. (This is a computer generated result) | ADAML | ADAML | | B= | C | 7307302 |
PUNCH LIST PRO'S OF COLORADO LLC | BE | L | 03/16/2022 | Renewed for No Fee at 3/16/2022 9:04:45 AM | ROSITAV | ROSITAV | | BE | L | 7303068 |
PUNCH LIST PRO'S OF COLORADO LLC | B= | P | 05/07/2021 | Building final complete pending electric final. Additional Inspections Required (computer generated): APACHE ELECTRIC AND MAINTENACE INC Electrical Final Inspection is not Completed yet. | ADAML | ADAML | | B= | P | 6961740 |
PEAK VIEW REMODELING | BE | L | 04/17/2020 | Renewed online for 1/2 Fee at 4/17/2020 7:00:24 AM (RECEIPT #: 1674333) | WEBSITE | WEBSITE | | BE | L | 6543321 |
PEAK VIEW REMODELING | BE | L | 04/19/2019 | Renewed for 1/2 Fee at 4/19/2019 12:32:34 PM (Receipt#1591890) | JANE | JANE | | BE | L | 6171733 |
PEAK VIEW REMODELING | BE | C | 10/16/2018 | | TERRI | TERRI | | BE | C | 5995527 |
PEAK VIEW REMODELING | BFR | P | 03/22/2018 | need to complete other roughs / reviewed spliced in plans on site / all framing OK | LONNYS | LONNYS | | BFR | P | 5796245 |
PEAK VIEW REMODELING | BSP | T | 03/16/2018 | PAID (REC#1487798) ADDITIONAL PLAN REVIEW TIME: $50 From: LBENNETT fill basement planter w/ conc; revised main lvl floor plan | LBENNETT | LBENNETT | | BSP | T | 5790998 |
PEAK VIEW REMODELING | BSP | P | 03/16/2018 | ADDITIONAL PLAN REVIEW TIME: $0 From: JUSTINC rEVISED FOR RELOCATED SUPPLY AIR AND RETURN AIR LOCATIONS | JUSTINC | JUSTINC | | BSP | P | 5790963 |
HOMEOWNER | E= | C | 03/18/2022 | hot tub,ok/ rest ok/ | JOHNN | JOHNN | | E= | C | 7307301 |
APACHE ELECTRIC AND MAINTENANCE INC | E= | R | 09/13/2021 | EC had to re schedule. | JOHNN | JOHNN | | E= | R | 7104609 |
APACHE ELECTRIC AND MAINTENANCE INC | E= | R | 08/20/2021 | add hot tub to permit or get new permit/ need inspector Rob to do next inspection/ I looked at service and basement/ service: need load calc/ several SER cables with grd cut off?/ bond riser and meter nipple to can with #4cu,need 2 rods/ jump prv/ sub panel: several awg14 on 20 amp cb's, group neutrals in pipe/flex/ may need handle ties/ would be best to wait for Rob to inspect before EC goes back out. | JOHNN | JOHNN | | E= | R | 7080291 |
APACHE ELECTRIC AND MAINTENANCE INC | E= | L | 07/07/2021 | Nobody home / Left door tag | BRETC | BRETC | | E= | L | 7027303 |
LUMEN ELECTRICAL SERVICES | ES | P | 04/19/2018 | Residential Underground: pre release ok / | MIGUEL | MIGUEL | | ES | P | 5821074 |
LUMEN ELECTRICAL SERVICES | ER | C | 03/15/2018 | Rough in complete--Remodel work through out house / Discussed AFCI/GFCI/TR requirements with contractor. / | ROB | ROB | | ER | C | 5790146 |
BILLS PLUMBING & DRAIN | H= | C | 03/26/2018 | NOTE: NO DOOR AT MECHANICAL ROOM AT TIME OF INSPECTION | BILLS | BILLS | | H= | C | 5799145 |
BILLS PLUMBING & DRAIN | P= | C | 09/19/2019 | Corrections made. | SAMH | SAMH | | P= | C | 6340851 |
BILLS PLUMBING & DRAIN | P= | L | 09/12/2019 | back grade @ veggie sink drain, need high loop @ d,w, drain, need hammer arrestor @ d.w. supply, set temp @ mstr tub, bfp @ hand held, set temp @ left shwr head, crossed waters @ main shwr head, need proper access to under shwr seat aav, expose aav @ w.b., need steamer drain ran to f.d. w/ proper air gap, need install instructions for steamer unit, re inspect all @ steamer unit, rest ok | JOHNS | JOHNS | | P= | L | 6332713 |
BILLS PLUMBING & DRAIN | PE | L | 09/11/2019 | Renewed for $33.25 at 9/11/2019 8:20:16 AM (Receipt#1628934) | JLANE | JLANE | | PE | L | 6330917 |
BILLS PLUMBING & DRAIN | PTO | C | 03/26/2018 | aav's at washer, under shower seat, and bar sink, check steam generator by final, need floor joist inspection before covering floor at master toilet, note; need mechanical permit for kitchen hood, exhaust fan, and dryer vent. | TAYLOR | TAYLOR | | PTO | C | 5799041 |
BILLS PLUMBING & DRAIN | PTO | P | 03/23/2018 | missing nail protection through out, need to test DWV and H2O, provide installation instructions for steam generator, need freeze protection for rain head at master shower, add steam generator to scope of work, need mechanical permit attached and permit for water heaters. | TAYLOR | TAYLOR | | PTO | P | 5797294 |