BRIGHT CONSTRUCTION & DEVELOPMENT, INC. | B= | C | 05/09/2018 | | BERTW | BERTW | | B= | C | 5839731 |
BRIGHT CONSTRUCTION & DEVELOPMENT, INC. | B= | P | 05/08/2018 | items corrected / final OK pending core shell final / please recall after core shell final has been completed -- Schedule a new Building Final when above items are complete. | DANE | DANE | | B= | P | 5838839 |
BRIGHT CONSTRUCTION & DEVELOPMENT, INC. | B= | P | 05/07/2018 | bathroom signs are too high / Tactile characters must be between 48" above the floor and 60" above the floor / grab bar behind the toilet at the mens room (must be measured from the center line of the toilet) must be 12" toward the corner measured from the center line of the toilet and 24" toward the open side of the toilet measured from the center line of the toilet / all other items completed -- Schedule a new Building Final when above items are complete. | DANE | DANE | | B= | P | 5837547 |
BRIGHT CONSTRUCTION & DEVELOPMENT, INC. | B= | R | 05/03/2018 | need to complete core shell permit to get final for interior finishes / need restroom signs on walls next to latch side of doors / side and rear grab bars at mens room are in wrong position - rear needs to be 12" from center line of toilet towards corner and 24" from center line towards open side and side wall needs to be max 12" out of corner and minimum 54" from corner / need thumb turn dead bolts at security door at inventory room / need access to janitorial room. Additional Inspections Required (computer generated): BRUNO'S MECHANICAL INC. Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | R | 5834875 |
BRIGHT CONSTRUCTION & DEVELOPMENT, INC. | BFR | P | 02/21/2018 | 2" gap at top of studs for roof deflection now OK | DANE | DANE | | BFR | P | 5770322 |
BRIGHT CONSTRUCTION & DEVELOPMENT, INC. | BFR | P | 02/12/2018 | need 2" of deflection space is needed at full height studs at inventory room as no slip track was used and studs are not cut 2" below bottom of roof / all other framing OK pending other rough inspections / discussed accessible elements with contractor | DANE | DANE | | BFR | P | 5763151 |
FOSTER ELECTRIC CORPORATION | E= | C | 04/03/2018 | | RANDY | RANDY | | E= | C | 5806820 |
FOSTER ELECTRIC CORPORATION | ER | P | 03/06/2018 | Rough in ok for all grid ceilings / | ROB | ROB | | ER | P | 5781699 |
FOSTER ELECTRIC CORPORATION | ES | C | 02/16/2018 | Commercial Service: 120/208 3 phase 200 amp----need meter for suite 130 | RANDY | RANDY | | ES | C | 5767613 |
FOSTER ELECTRIC CORPORATION | ER | P | 02/12/2018 | walls only | RANDY | RANDY | | ER | P | 5763122 |
FOSTER ELECTRIC CORPORATION | EUG | P | 02/02/2018 | this is slab work, 10 floor boxes | GARYL | GARYL | | EUG | P | 5756187 |
BRUNO'S MECHANICAL INC. | H= | C | 05/04/2018 | MECHANICAL FINAL OK. REVISED TEST AND BALANCE REPORT RECEIVED, OUTSIDE AIR READING OK. SEE IMAGES. | DUSTINS | DUSTINS | | H= | C | 5835817 |
BRUNO'S MECHANICAL INC. | H= | P | 05/03/2018 | RTU-6 STILL LACKS OUTSIDE AIR READING. | NANCY | NANCY | | H= | P | 5834569 |
BRUNO'S MECHANICAL INC. | H= | P | 05/02/2018 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5833956 |
BRUNO'S MECHANICAL INC. | H= | P | 05/02/2018 | TEST AND BALANCE REPORT LACKS OUTSIDE AIR READINGS. | NANCY | NANCY | | H= | P | 5833176 |
BRUNO'S MECHANICAL INC. | H= | P | 05/01/2018 | PERMANENTLY LABEL RTU WITH SUITE NUMBER 130, BLACK MARKER NOT PERMANENT. STILL NEED TO VERIFY EXHAUST IS RUNNING, WILL NEED ON SITE INSPECTION. PER CONVERSATION WITH CONTRACTOR CANCELED ON SITE INSPECTION TODAY. | NANCY | NANCY | | H= | P | 5831929 |
BRUNO'S MECHANICAL INC. | HSP | P | 05/01/2018 | NO TEST AND BALANCE REPORT ATTACHED TO INSPECTION REQUEST. | NANCY | NANCY | | HSP | P | 5831925 |
BRUNO'S MECHANICAL INC. | H= | P | 04/26/2018 | NEED REVISED EQUIPMENT SCHEDULE TO SHOW WHAT THE NEW EQUIPMENT ON ROOF IS (CARRIER, MODEL, BTU'S ETC). PLUMBING VENT WITHIN 10 FEET OF RTU ECONOMIZER. PERMANENTLY LABEL RTU'S WITH SUITE NUMBER. EXHAUST FAN IS NOT RUNNING, SEE EXHAUST FAN SCHEDULE NOTE C. SUPPORT TWO FLEX DUCTS UP OFF OF GRID, OK TO TAKE PICTURES OF CORRECTION AND ATTACH TO INSPECTION REQUEST. PROVIDE CORRECTED TEST AND BALANCE REPORT, SEE PREVIOUS INSPECTION COMMENTS REGARDING BALANCE REPORT. | NANCY | NANCY | | H= | P | 5828006 |
BRUNO'S MECHANICAL INC. | HD | C | 04/26/2018 | | NANCY | NANCY | | HD | C | 5827998 |
BRUNO'S MECHANICAL INC. | H= | P | 04/25/2018 | INSTALL RETURN AIR GRILL IN CORRIDOR. INSTALL REMOTE INDICATORS FOR RTU SMOKE DETECTORS. PLUMBING VENT WITHIN 10 FEET OF RTU ECONOMIZER. PERMANENTLY LABEL RTU'S WITH #130. REVISED EQUIPMENT SCHEDULE STILL DOES NOT SHOW WHAT EQUIPMENT IS INSTALLED ON SITE. SEE PREVIOUS NOTES REGARDING TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 5826964 |
BRUNO'S MECHANICAL INC. | HD | P | 04/25/2018 | CEILING TILES IN FRONT HALF OF STORE ARE ALL IN PLACE PRIOR TO INSPECTION OF FLEX AND DIFFUSERS. | NANCY | NANCY | | HD | P | 5826959 |
BRUNO'S MECHANICAL INC. | H= | P | 04/25/2018 | NEED REVISED TEST AND BALANCE REPORT. REPORT DOES NOT SHOW UNIT DATA, MOTOR DATA OR OUTSIDE READINGS. | NANCY | NANCY | | H= | P | 5826619 |
BRUNO'S MECHANICAL INC. | HD | P | 03/01/2018 | CANCELED AT CALL AHEAD. | NANCY | NANCY | | HD | P | 5777172 |
BRUNO'S MECHANICAL INC. | HD | P | 02/28/2018 | Cancelled at call ahead by contractor. | JEFFL | JEFFL | | HD | P | 5775991 |
BRUNO'S MECHANICAL INC. | HD | P | 02/14/2018 | NEED REVISED/APPROVED EQUIPMENT SCHEDULE, RTU'S ARE CARRIER NOT TRANE. INSTALL REMOTE SMOKE INDICATORS BY FINAL. EXHAUST TRUNK LINE AND LATERALS OK, NO GRILLS YET. RTU-3 TRUNK LINES AND LATERALS OK. OK TO CLOSE UP WRAP. NO DIFFUSERS YET. RTU-6 TRUNK LINES OK, OK TO CLOSE UP WRAP. NO LATERALS OR DIFFUSERS. STILL NEED TO SEE ROOF. | NANCY | NANCY | | HD | P | 5765364 |
ALPHALETE MECHANICAL LLC | P= | C | 04/24/2018 | | JOHNS | JOHNS | | P= | C | 5825602 |
ALPHALETE MECHANICAL LLC | PTO | C | 02/12/2018 | by final need to splice plans, refer to Feb. 1, 2018 pb inspection notes, rest ok for test and design per plan. note: by final add support for 3" vtr @ base of vent, check water htr @ final, check vtr @ final | JOHNS | JOHNS | | PTO | C | 5763219 |
ALPHALETE MECHANICAL LLC | PB | C | 02/01/2018 | base ok, need plan splice to show breakroom sink dwv size change from 3" on plan to 2" by top out | JOSEPHD | JOSEPHD | | PB | C | 5754434 |
ALPHALETE MECHANICAL LLC | PB | P | 01/31/2018 | need approved plans on site, ok to drop test | JOSEPHD | JOSEPHD | | PB | P | 5752966 |
ALPHALETE MECHANICAL LLC | XPS | T | 04/18/2018 | PAID (REC#1494598) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 4-18-18 | TCRIPPEN | TCRIPPEN | | XPS | T | 5820416 |
ALPHALETE MECHANICAL LLC | XPS | P | 04/18/2018 | PLAN SPLICE: (No Fee) by: TCRIPPEN for Plumbing: plumbing splice 4-18-18 | TCRIPPEN | TCRIPPEN | | XPS | P | 5820397 |