B & H CUSTOM BUILDING AND DESIGN | B= | C | 07/26/2018 | all other finals now completed | MINDY | MINDY | | B= | C | 5915588 |
B & H CUSTOM BUILDING AND DESIGN | B= | P | 03/02/2018 | Temp CO: pending finals ( Expires: 4/1/2018 12:00:00 AM) | RITA | RITA | | B= | P | 5778233 |
B & H CUSTOM BUILDING AND DESIGN | B= | P | 02/21/2018 | Interior remodel complete pending other Finals / NOTE - front door is pre-existing non-conforming (double-keyed without indicator) / plans reviewed onsite. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, ALLIED PLUMBING AND HEAT, LLC. Mechanical Final Inspection is not Completed yet, NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet, SYSTEMS ELECTRIC, INC. Electrical Final Inspection is not Completed yet. | RICHB | RICHB | | B= | P | 5770827 |
SYSTEMS ELECTRIC, INC. | BSP | T | 02/16/2018 | PAID (REC#1482448) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY test | SHELBY | SHELBY | | BSP | T | 5767243 |
B & H CUSTOM BUILDING AND DESIGN | BSP | P | 02/15/2018 | Space reviewed as Pre-Existing Non-Conforming V-A Type of Construction using 1-hour sprinkler substitution. (also in Permit Notes.) | JAY | JAY | | BSP | P | 5767040 |
B & H CUSTOM BUILDING AND DESIGN | BSP | P | 02/15/2018 | Inspector walked all units in plaza from 5655 to 5677 to document construction type and existence of fire sprinklers | RICHB | RICHB | | BSP | P | 5766591 |
B & H CUSTOM BUILDING AND DESIGN | BSP | P | 01/26/2018 | Construction type is listed as V-A which requires a rated roof ceiling assembly - none is listed or detailed - Building Inspector talked with Mechanical Inspector to verify lack of details for construction type / Contractor needs to change construction type or adjust construction details to match V-A | RICHB | RICHB | | BSP | P | 5749573 |
B & H CUSTOM BUILDING AND DESIGN | BFR | P | 01/26/2018 | Non-bearing non-rated framing OK pending other Roughs / bathroom ceiling framing OK pending other Roughs / GC not onsite at time of inspection - ensure accessible elements are being constructed per plans / plans reviewed onsite | RICHB | RICHB | | BFR | P | 5749204 |
SYSTEMS ELECTRIC, INC. | E= | C | 02/21/2018 | 2--- rtu's @25 amp --- 3 rtu's @20 ----coolers 20 amp OK | CRAIGS | CRAIGS | | E= | C | 5770872 |
SYSTEMS ELECTRIC, INC. | ER | C | 02/16/2018 | ceilings ok----completes rough | MIGUEL | MIGUEL | | ER | C | 5768184 |
SYSTEMS ELECTRIC, INC. | ER | P | 01/26/2018 | Front office walls, Bathroom walls, Pre sales walls rough inok / Discussed accessiblity requirements with contractor / | ROB | ROB | | ER | P | 5749446 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | C | 07/26/2018 | | JACK | JACK | | H= | C | 5915374 |
ALLIED PLUMBING AND HEAT, LLC. | H= | C | 07/19/2018 | | MARKB | MARKB | | H= | C | 5907369 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 03/21/2018 | TAB Received | MARKB | MARKB | | H= | P | 5794512 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 03/20/2018 | Remote smoke indicators installed | MARKB | MARKB | | H= | P | 5794446 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 02/20/2018 | FINAL PENDING - Plan splice for EF-2 & 3 changed duct (undersized from plan), remote indicators for smoke shutdown and TAB report. | MARKB | MARKB | | H= | P | 5769841 |
VICTORY AIR | H= | C | 02/20/2018 | | MARKB | MARKB | | H= | C | 5769839 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 02/16/2018 | ABOVE CEILING DUCT - Duct for EF-2 & EF-3 is undersized per plan. EF-1 duct lacks support. FLEX, DIFFUSERS AND SMOKE SHUTDOWN INSTALLED PER PLAN (cover at own risk). REACH IN COOLERS, WALK IN COOLER/FREEZER ARE ALL SELF-CONTAINED. FOR FINAL - Address building type, need remote indicators installed, address exhaust duct, need roof equipment inspected and provide Test And Balance Report. | MARKB | MARKB | | HD | P | 5768348 |
ALLIED PLUMBING AND HEAT, LLC. | H= | P | 02/08/2018 | CAN FINAL ONCE CONTRACTOR REQUEST INSPECTION | MARKB | MARKB | | H= | P | 5761310 |
ALLIED PLUMBING AND HEAT, LLC. | HC | C | 02/08/2018 | RELEASE METER - REPIPE TO SPLIT SUITES | MARKB | MARKB | | HC | C | 5761309 |
ALLIED PLUMBING AND HEAT, LLC. | HI | C | 02/08/2018 | 10 PSI PRESSURE TEST OK. PIPING PER PLAN. | MARKB | MARKB | | HI | C | 5761305 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 02/02/2018 | ABOVE CEILING DUCT - SUPPLY, RETURN MAINS AND RUN OUTS INSTALLED PER PLAN AND OK TO WRAP FOR RTU'S 1, 2, 3, 4, 5. EXHAUST DUCT NOT READY AT THIS TIME AND NO ROOF INSPECTION | MARKB | MARKB | | HD | P | 5755779 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | R | 02/01/2018 | Per previous notes - plan sticker is showing building as rated but plans are for non-rated building. This issue needs to be addressed before anymore inspections. Tried to call Dan (call ahead provided) and then licensee, but Dan did not answer and number for licensee on account is disconnected. | MARKB | MARKB | | HD | R | 5755039 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 01/26/2018 | ABOVE CEILING DUCT - SUPPLY MAINS FOR RTU'S 1 & 2 OK TO WRAP. ---PLAN STICKER RATES BUILDING AS A 5A BUT PLANS ARE FOR A 5B, THIS WILL NEED TO BE ADDRESSED BEFORE ANYMORE INSPECTIONS--- PROCEED AT OWN RISK | MARKB | MARKB | | HD | P | 5749602 |
ALLIED PLUMBING AND HEAT, LLC. | P= | C | 02/15/2018 | corrections made, see images | JOHNS | JOHNS | | P= | C | 5766078 |
ALLIED PLUMBING AND HEAT, LLC. | P= | P | 02/13/2018 | low drinking fountain does not meet accessible requirements, can complete with uploaded image of corrections (w/ tape measure in pic to show knee clearance @ 27" min and bubbler @ 36" maximum above floor), to next inspection request, rest ok. note: no back flow preventer installed, existing back flow @ main water entry | JOHNS | JOHNS | | P= | P | 5764318 |
ALLIED PLUMBING AND HEAT, LLC. | PTO | C | 01/31/2018 | no wh at this time, will need platform to access mixing valve above restrooms by final, trap primer access panel at final | JOEL | JOEL | | PTO | C | 5753227 |
ALLIED PLUMBING AND HEAT, LLC. | PB | C | 01/26/2018 | ok for test and design per plan. note water from above
| JOHNS | JOHNS | | PB | C | 5748672 |