PEAK PROFESSIONAL CONTRS INC | B= | C | 05/07/2018 | All other required Final inspections are complete. (This is a computer generated result) | BOBF | BOBF | | B= | C | 5837782 |
PEAK PROFESSIONAL CONTRS INC | B= | P | 05/07/2018 | pending completion of plumb and elec finals building okay/ letter for framing of water heater support spliced to plans. Additional Inspections Required (computer generated): LANDMARK PLUMBING & HEATING, INC. Mechanical Final Inspection is not Completed yet, SYSTEMS ELECTRIC, INC. Electrical Final Inspection is not Completed yet. | BOBF | BOBF | | B= | P | 5837273 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 04/09/2018 | letter for ceiling framing in restrooms of file, ceiling framing and wall framing for restrooms okay, reminded super about required clearances for fixtures in rest rooms , letter for water heater support was for wrong address | BOBF | BOBF | | BFR | P | 5811151 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 03/13/2018 | still need to complete bathrooms (no inspection done on restrooms) / all other interior light gauge framing OK pending other roughs / need stamped detail for how to build hard lids over bathrooms / discussed accessible elements | DANE | DANE | | BFR | P | 5787818 |
PEAK PROFESSIONAL CONTRS INC | BFR | P | 02/27/2018 | 6" demising wall between units OK pending other roughs / all other interior framing still to be installed / still need to attach a mechanical permit | DANE | DANE | | BFR | P | 5775550 |
SYSTEMS ELECTRIC, INC. | E= | C | 05/07/2018 | | CRAIG | CRAIG | | E= | C | 5837708 |
SYSTEMS ELECTRIC, INC. | E= | P | 05/04/2018 | panel ok -------- exterior plug ok --------------- everything else is not ready | CRAIG | CRAIG | | E= | P | 5836056 |
SYSTEMS ELECTRIC, INC. | E= | R | 05/03/2018 | need panel open for inspection, cannot use extension cords for permanent wiring , cannot use splitter at water cooler, install gfci breaker for washer, within 6' of mop sink, install disconnect for dishwasher (panel breaker lock is not within site), label all dead face gcfi with circuit and area served , gfci receptacle not readily accessible over west exterior door. | BRET | BRET | | E= | R | 5835397 |
SYSTEMS ELECTRIC, INC. | ER | P | 04/03/2018 | Existing panel relocated to adjacent wall--Need access for j box and 90 degree flex fittings / | ROB | ROB | | ER | P | 5806789 |
SYSTEMS ELECTRIC, INC. | ER | P | 03/16/2018 | walls | BRET | BRET | | ER | P | 5791344 |
SYSTEMS ELECTRIC, INC. | ER | P | 02/26/2018 | demising wall | BRET | BRET | | ER | P | 5774268 |
SYSTEMS ELECTRIC, INC. | ER | R | 02/23/2018 | need protection of cable front south east corner rest of wall ok | BRET | BRET | | ER | R | 5772875 |
LANDMARK PLUMBING AND HEATING, INC. | H= | C | 05/07/2018 | | BENH | BENH | | H= | C | 5837781 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | C | 05/02/2018 | | BENH | BENH | | H= | C | 5834124 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | C | 05/02/2018 | TRUNK LINE AND LATERALS OK | BENH | BENH | | HD | C | 5834117 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 05/02/2018 | TEST AND BALANCE RECEIVED,SEE IMAGES | BENH | BENH | | H= | P | 5833214 |
LANDMARK PLUMBING AND HEATING, INC. | HI+ | C | 04/13/2018 | 10 LB TEST OK | BENH | BENH | | HI+ | C | 5816095 |
LANDMARK PLUMBING AND HEATING, INC. | HC | C | 04/04/2018 | RELEASE METER FOR 2 LB SYSTEM THANKS | BENH | BENH | | HC | C | 5809799 |
LANDMARK PLUMBING AND HEATING, INC. | HI | C | 04/04/2018 | NEED REVISED PLANS FOR DELETED RADIANT HEATER, NEED TO CHANGE SCOPE OF WORK AND PUT WATER HEATER VENT ON MECHANICAL PERMIT AND WATER HEATER ON PLUMBING PERMIT, WILL ALSO NEED PRESSURE TEST FOR WHEN GAS LINE IS RAN TO WATER HEATER. 10 LB TEST OK, 1" MAIN, 1 WATER HEATER, 1 RTU | BENH | BENH | | HI | C | 5807197 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 05/07/2018 | Corrections made, see images | SHANEN | SHANEN | | P= | C | 5836978 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 05/03/2018 | Pipe water heater pan drain to mop sink per plans, rest OK | SHANEN | SHANEN | | P= | P | 5835064 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 03/21/2018 | Check water heater and VTR at final, AAV hand sink per plans | SHANEN | SHANEN | | PTO | C | 5795479 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 02/27/2018 | Underground DWV test OK, changed from P= to PB | SHANEN | SHANEN | | PB | C | 5775283 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 02/23/2018 | Vent in wall between units test OK | SHANEN | SHANEN | | PTO | P | 5772799 |
PEAK PROFESSIONAL CONTRS INC | XBS | P | 05/02/2018 | PLAN SPLICE: (No Fee) by: SHELLEY for Construction: letter for water heater weight over 700# | SHELLEY | SHELLEY | | XBS | P | 5833344 |
LANDMARK PLUMBING AND HEATING, INC. | XMS | T | 05/02/2018 | PAID (REC#1497639) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: mechanical splice 5-2-18 | TCRIPPEN | TCRIPPEN | | XMS | T | 5833267 |
NIELSEN MECHANICAL CONTRACTORS, INC. | XMS | T | 04/10/2018 | PAID (REC#1492963) PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised gas and layout to remove infared heat | JUSTINC | JUSTINC | | XMS | T | 5812977 |