TRALON HOMES, LLC | B= | C | 06/11/2018 | All other required Final inspections are complete. (This is a computer generated result) | JUSTINL | JUSTINL | | B= | C | 5870979 |
TRALON HOMES, LLC | B= | P | 06/06/2018 | Unfinished basement / No deck / AC installed. Additional Inspections Required (computer generated): External Agency Inspection N= by EPCZONING is not Completed yet (Contact: Paul Wiggs at 520-6819). | JUSTINL | JUSTINL | | B= | P | 5866650 |
TRALON HOMES, LLC | BIN | C | 05/23/2018 | | JUSTINL | JUSTINL | | BIN | C | 5854015 |
TRALON HOMES, LLC | BFR | C | 05/23/2018 | Foundation repair OK per engineer detail - Other frame correction complete | JUSTINL | JUSTINL | | BFR | C | 5854002 |
TRALON HOMES, LLC | BSP | P | 05/04/2018 | Engineer detail for foundation repair on file - Still need to inspect for repair | JUSTINL | JUSTINL | | BSP | P | 5835809 |
TRALON HOMES, LLC | BIN | P | 05/02/2018 | Insulation OK pending frame | JUSTINL | JUSTINL | | BIN | P | 5834051 |
TRALON HOMES, LLC | BFR | P | 05/02/2018 | T post installed exceeds 3" of thread / Address item 5 / other frame corrections complete | JUSTINL | JUSTINL | | BFR | P | 5834033 |
TRALON HOMES, LLC | BIN | R | 05/01/2018 | Field canceled by contractor ( Chuck ) on site | JUSTINL | JUSTINL | | BIN | R | 5832441 |
TRALON HOMES, LLC | BFR | R | 05/01/2018 | Field canceled by contractor ( Chuck ) on site | JUSTINL | JUSTINL | | BFR | R | 5832431 |
TRALON HOMES, LLC | BIN | R | 04/30/2018 | Field canceled by contractor (Chuck) on site | JUSTINL | JUSTINL | | BIN | R | 5831376 |
TRALON HOMES, LLC | BFR | R | 04/30/2018 | Field canceled by contractor (Chuck) on site | JUSTINL | JUSTINL | | BFR | R | 5831371 |
TRALON HOMES, LLC | BFR | R | 04/26/2018 | 1. Nail narrow braced wall panel splice / 2. Missing roof pipe jacks / 3. Add stud at kitchen 2x bearing wall to align with joist below / 4. Stud in great room bearing wall spaced greater than 16" OC / 5. Request letter for hole in foundation and exposed rebar in beam pocket / 6. Missing T posts / 7. Missing point loads above steel beam in basement / Plans reviewed electronically / | JUSTINL | JUSTINL | | BFR | R | 5828323 |
TRALON HOMES, LLC | BSP | P | 04/25/2018 | Narrow braced wall panel splice within mid 24" of wall - Interior straps OK / Front porch posts and lid OK (UPDATE: changed from BFR to BSP ) JL 4/26 | JUSTINL | JUSTINL | | BSP | P | 5827564 |
TRALON HOMES, LLC | BSP | R | 04/18/2018 | Narrow braced wall missing 1000 LBS interior strap - Panel splice not within middle 24" of wall | JUSTINL | JUSTINL | | BSP | R | 5820576 |
TRALON HOMES, LLC | BFD | C | 03/28/2018 | | JUSTINL | JUSTINL | | BFD | C | 5800886 |
TRALON HOMES, LLC | BSP | P | 03/28/2018 | Foundation design | JUSTINL | JUSTINL | | BSP | P | 5800885 |
TRALON HOMES, LLC | BFN | C | 03/28/2018 | Engineer letter for foundation -- Eufer noted / Foundation design on file | JUSTINL | JUSTINL | | BFN | C | 5800883 |
TRALON HOMES, LLC | BFT | C | 03/28/2018 | Engineer letter for footing on file -- Open hole on file - 2000 PSF ( Verified ) / Drain usable / 10% | JUSTINL | JUSTINL | | BFT | C | 5800882 |
TRALON HOMES, LLC | BFD | P | 03/26/2018 | Drain entire and usable to sump pit / Damp proof OK / Request all foundation paperwork | JUSTINL | JUSTINL | | BFD | P | 5798882 |
TRALON HOMES, LLC | BFD | R | 03/22/2018 | Field canceled by contractor (Devin) | JUSTINL | JUSTINL | | BFD | R | 5796270 |
TRALON HOMES, LLC | BFT | P | 02/16/2018 | AUTHORIZED INSPECTION BY ENGINEER | MATTHEWM | MATTHEWM | MATTHEWM | BFT | P | 5767468 |
TRALON HOMES, LLC | BFN | P | 02/16/2018 | AUTHORIZED INSPECTION BY ENGINEER | MATTHEWM | MATTHEWM | MATTHEWM | BFN | P | 5767467 |
J2D ELECTRIC, INC. | E= | C | 06/05/2018 | a/c installed--20 amp | TIMA | TIMA | | E= | C | 5864945 |
J2D ELECTRIC, INC. | E= | R | 06/04/2018 | need 30 amp recept for dryer and 50 amp recept for range | TIMA | TIMA | | E= | R | 5863452 |
J2D ELECTRIC, INC. | ER | C | 04/25/2018 | | TOMC | TOMC | | ER | C | 5826954 |
J2D ELECTRIC, INC. | ER | R | 04/24/2018 | wire and box in air returns main level ( check entire main level),nail plates in garage at coach light feeds | TIMA | TIMA | | ER | R | 5825232 |
J2D ELECTRIC, INC. | ES | C | 04/24/2018 | Residential Underground: 150 amp 3/w new res. needs meter seal | TIMA | TIMA | | ES | C | 5825230 |
J2D ELECTRIC, INC. | EUG | C | 04/20/2018 | 2/0 urd | TOMC | TOMC | | EUG | C | 5822849 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | H= | C | 06/01/2018 | | BILLS | BILLS | | H= | C | 5861988 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | H= | R | 05/31/2018 | Properly connect water heater vent. Provide furnace filter. A/C Condensate to dispose at floor drain. NOTES: Unfinished basement, 2 supplies, 1 return. Outside air to furnace return. A/C Complete. | RANDYB | RANDYB | | H= | R | 5860210 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | HC | C | 04/24/2018 | RELEASE METER | JEFFB | JEFFB | | HC | C | 5825553 |
CAPITAL VIEW GENERAL CONSTRUCTION, INC. | HRR | C | 04/24/2018 | NEED ALL ACCURATE EQUIPMENT SPECS BY THE FINAL. NOTES: UNFINISHED BASEMENT, OUTSIDE AIR TO THE RETURN DUCT AND A/C ROUGH - LINES AND COIL. | JEFFB | JEFFB | | HRR | C | 5825544 |
CARRICK GAS PIPING | HI | C | 04/23/2018 | 10# test ok, 1" main, 1- furnace, 1- water heater. | DANR | DANR | | HI | C | 5824503 |
TRADITIONAL PLUMBING AND HEATING LLC | P= | C | 06/05/2018 | corrections made | JOHNS | JOHNS | | P= | C | 5864971 |
TRADITIONAL PLUMBING AND HEATING LLC | P= | P | 06/04/2018 | complete hall tub trim, no water @ mstr shwr, draft divertor not centered over flue exhaust @ water htr, draft divertor not properly secured to top of water htr, leak @ 3" clean out behind water htr, rest ok. note: pvb ok, aav @ pwdr lav | JOHNS | JOHNS | | P= | P | 5863151 |
TRADITIONAL PLUMBING AND HEATING LLC | PTO | C | 04/23/2018 | Test ok, 3-vtr, temp valve by left master lav, unfinished basement (aav lav), irrigation stub. | DANR | DANR | | PTO | C | 5824511 |
TRADITIONAL PLUMBING AND HEATING LLC | PB | C | 03/27/2018 | Test ok. | DANR | DANR | | PB | C | 5800325 |
TRADITIONAL PLUMBING AND HEATING LLC | PB | P | 03/26/2018 | No test gauge, rest ok | DANR | DANR | | PB | P | 5799387 |