MERRITT GENERAL CONTRACTORS, INC. | B= | C | 07/27/2018 | All other required Final inspections are complete. (This is a computer generated result) | NICK | NICK | | B= | C | 5915709 |
MERRITT GENERAL CONTRACTORS, INC. | B= | P | 06/01/2018 | . Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982). | NICK | NICK | | B= | P | 5861364 |
MERRITT GENERAL CONTRACTORS, INC. | B= | P | 05/11/2018 | Building final OK pending all other finals complete. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, ARTISAN PIPE SYSTEMS, INC. Plumbing Final Inspection is not Completed yet. | NICK | NICK | | B= | P | 5842651 |
MERRITT GENERAL CONTRACTORS, INC. | BFR | P | 05/11/2018 | Letter on file from architect stating framing OK to under side of existing ceiling | NICK | NICK | | BFR | P | 5842648 |
MERRITT GENERAL CONTRACTORS, INC. | BFR | P | 03/26/2018 | wall type on plan calls for WT1 and WT2 wall types to be above ceiling and braced 32" oc to structure, remaining okay. Reviewed Accessible Elements / | NATHAN | NATHAN | | BFR | P | 5798916 |
RCS ELECTRIC | E= | C | 05/02/2018 | | BRIAN | BRIAN | | E= | C | 5833427 |
RCS ELECTRIC | E= | P | 04/26/2018 | NEED TO PULL EGC INTO THE DISCONNECT FROM SERVICE AND FLOAT NEUTRAL IN SERVICE DISCONNECT---LABEL AIC AND UNIT# ON DISCONNECT----LABEL PANEL---MOVE GFCI DOWN TO 6,5' AT WATER HEATER----NEED LARGER ACCESS HOLE IN CASH WRAP FOR ACCESS TO OUTLETS---- | BRIAN | BRIAN | | E= | P | 5828338 |
RCS ELECTRIC | ER | P | 03/12/2018 | REST OF THE WALLS AND BATH HARD LID-----------------NOTE ---WILL NEED ACCESS DOOR IN BATHROOM HARD LID FOR J BOX-----VERIFY ON FINAL--- | BRIAN | BRIAN | | ER | P | 5786098 |
RCS ELECTRIC | ER | P | 03/07/2018 | COFFEE COUNTER WALL --OK | BRIAN | BRIAN | | ER | P | 5782595 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | C | 05/03/2018 | OK | JERRYF | JERRYF | | H= | C | 5834955 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 05/03/2018 | TAB REPORT RECEIVED | JERRYF | JERRYF | | H= | P | 5834347 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 03/19/2018 | ABOVE CEILING SA / RA OK | JERRYF | JERRYF | | HD | P | 5792423 |
ARTISAN PIPE SYSTEMS, INC. | P= | C | 05/17/2018 | Correction made | SHANEN | SHANEN | | P= | C | 5847589 |
ARTISAN PIPE SYSTEMS, INC. | P= | P | 05/09/2018 | Need revisions, rest OK | SHANEN | SHANEN | | P= | P | 5839724 |
ARTISAN PIPE SYSTEMS, INC. | PTO | C | 04/11/2018 | above ceiling ok, revise plans for aav's at sinks in service area and existing 2 inch vent. | TAYLOR | TAYLOR | | PTO | C | 5814459 |
ARTISAN PIPE SYSTEMS, INC. | PTO | P | 03/30/2018 | DWV and H2O ok in walls, revise plans for 3/4 inch to water closet and remove water piping to existing restroom by final. | TAYLOR | TAYLOR | | PTO | P | 5803998 |
ARTISAN PIPE SYSTEMS, INC. | PB | C | 03/28/2018 | | TAYLOR | TAYLOR | | PB | C | 5801839 |
ARTISAN PIPE SYSTEMS, INC. | PB | P | 03/16/2018 | need to install G.I, drains for mop sink and floor sink for 3 comp, note: need to revise plans for ABS piping. | TAYLOR | TAYLOR | | PB | P | 5791794 |
ARTISAN PIPE SYSTEMS, INC. | XPS | T | 05/15/2018 | PAID (REC#1500411) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 5-15-18 | TCRIPPEN | TCRIPPEN | | XPS | T | 5845356 |