SHARP GENERAL CONTRACTORS, INC | B= | C | 05/31/2018 | corrections complete | SCOTTS | SCOTTS | | B= | C | 5860125 |
SHARP GENERAL CONTRACTORS, INC | B= | P | 05/22/2018 | per ANSI 2003 803.4 a bench complying with section 903 shall be provided in the dressing room -- missing exit signs at rear door and above storage room door per electrical plan -- install accessible signage at bathrooms and dressing room -- still need sales counter installed to check for accessibility -- complete other finals -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): AIR TECH MECHANICAL INC Mechanical Final Inspection is not Completed yet, LANDMARK PLUMBING & HEATING, INC. Plumbing Final Inspection is not Completed yet, MARQUARDT ELECTRIC, INC Electrical Final Inspection is not Completed yet. | SCOTTS | SCOTTS | | B= | P | 5851953 |
SHARP GENERAL CONTRACTORS, INC | BFR | C | 05/22/2018 | 1 hour at under stairs ok -- rest of frame ok | SCOTTS | SCOTTS | | BFR | C | 5851915 |
SHARP GENERAL CONTRACTORS, INC | BFR | P | 03/26/2018 | provide splice showing deletion of counter and added walls -- Reviewed Accessible Elements for bathrooms and dressing room -- underside of stairs framing for 1 hour still to be inspected -- still need blocking for grab bars | SCOTTS | SCOTTS | | BFR | P | 5799512 |
MARQUARDT ELECTRIC, INC | E= | C | 05/31/2018 | | CRAIGS | CRAIGS | | E= | C | 5860050 |
MARQUARDT ELECTRIC, INC | ER | P | 04/02/2018 | 2 bathrooms and sales floor area | CRAIGS | CRAIGS | | ER | P | 5804942 |
MARQUARDT ELECTRIC, INC | EUG | C | 03/13/2018 | under slab conduits and floor boxes OK | CRAIGS | CRAIGS | | EUG | C | 5786954 |
AIRTECH MECHANICAL, INC. | H= | C | 05/23/2018 | Test And Balance Received | MARKB | MARKB | | H= | C | 5853091 |
AIRTECH MECHANICAL, INC. | H= | P | 05/10/2018 | FINAL PENDING - Test And Balance Report | MARKB | MARKB | | H= | P | 5841116 |
AIRTECH MECHANICAL, INC. | H= | P | 05/04/2018 | FINAL PENDING - Undercut doors, label thermostats and remote indicators for RTU served and provide Test And Balance report | MARKB | MARKB | | H= | P | 5836911 |
AIRTECH MECHANICAL, INC. | HD | C | 04/11/2018 | ABOVE CEILING DUCT - SUPPLY/RETURN/EXHAUST DUCT INSTALL PER PLAN EXCEPT MISSING 2 SUPPLY OUTLETS ALONG BACK WALL BY DRESSING AREA. FOR FINAL - Will need missing supplies installed, finish installing diffusers, both RTU's will require smoke shut down, if thermostats are installed above 48" they will be required to be in lock boxes, need to verify undercut doors and provide Test And Balance Report. | MARKB | MARKB | | HD | C | 5814085 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 05/29/2018 | correction made | TED | TED | | P= | C | 5857143 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 05/11/2018 | install bike washer, need 5 foot from side wall to edge of lav front bathroom | TED | TED | | P= | P | 5842711 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 03/28/2018 | test and design ok | TED | TED | | PTO | C | 5801007 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 03/09/2018 | test and design ok, need approval letter or plan splice for layout change and deleted floor drain and deleted floor cleanout, proceed at own risk | TED | TED | | PB | C | 5784557 |
SHARP GENERAL CONTRACTORS, INC | XBS | T | 05/21/2018 | PAID (REC#1501552) PLAN SPLICE FEE: $50 by: LBENNETT for Construction: Revised floor plan | LBENNETT | LBENNETT | | XBS | T | 5850419 |
LANDMARK PLUMBING AND HEATING, INC. | XPS | T | 03/12/2018 | PAID (REC#1486778) PLAN SPLICE FEE: $50 by: DALEH for Plumbing: relocated waste and water heater | DALEH | DALEH | | XPS | T | 5786502 |