THE HOUSE DOCTOR | B= | C | 08/31/2018 | All finals completed | NELIDA | NELIDA | | B= | C | 5952110 |
THE HOUSE DOCTOR | B= | P | 08/17/2018 | Temp CO: pending mech and building finals ( Expires: 9/16/2018 12:00:00 AM) | NELIDA | NELIDA | | B= | P | 5938030 |
THE HOUSE DOCTOR | B= | P | 08/15/2018 | corrections from previous inspection are okay / pending other final inspections / Training with PPRBD inspector Lonny / A-2 occupancy / reviewed accessible elements including restrooms. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), M W MECHANICAL INC Mechanical Final Inspection is not Completed yet. | BRIANB | BRIANB | | B= | P | 5935643 |
THE HOUSE DOCTOR | BSP | P | 08/15/2018 | training with inspector Brian B / reviewed all accessible elements for bathrooms | LONNYS | LONNYS | | BSP | P | 5935628 |
THE HOUSE DOCTOR | B= | P | 08/14/2018 | 18" vertical grab installed in men's and women's restroom exceed 39" - 41" off of the floor / flush control for men's toilet not on open side of water closet / mirrors in men's and women's restroom installed over 40" / need to complete other final inspections -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), M W MECHANICAL INC Mechanical Final Inspection is not Completed yet. | BRIANB | BRIANB | | B= | P | 5933181 |
THE HOUSE DOCTOR | BFR | P | 08/14/2018 | plan splice complete 9JUL18 / pending other rough inspections | BRIANB | BRIANB | | BFR | P | 5933180 |
THE HOUSE DOCTOR | BFR | P | 04/04/2018 | insulation inspection requested - not ready and cancelled by rep Mario / changed to frame inspection onsite / met with rep Mario and reviewed U419 1hr rated assembly at demising wall - need to inspect 1hr rated demising walls per U419 on approved design and provide listings for all penetrations or have approved plan splice removing rated assembly / also need to attach mechanical to permit and have mechanical inspection for hood wall and complete other rough inspections / reviewed accessible elements with Mairo | BRIANB | BRIANB | | BFR | P | 5807522 |
THE HOUSE DOCTOR | BFR | P | 03/26/2018 | attach mechanical permit -- complete other roughs -- mechanical inspector to look at hood wall prior to covering -- Reviewed Accessible Elements -- need to see screw pattern on one sided demising wall per U419 on plans -- rest of frame ok | SCOTTS | SCOTTS | | BFR | P | 5799482 |
SPRINGS FAMILY ELECTRIC | E= | C | 07/25/2018 | | CRAIGS | CRAIGS | | E= | C | 5913721 |
SPRINGS FAMILY ELECTRIC | E= | P | 07/19/2018 | RTU 1 ---50 amp ----- RTU 2---50 amp -- MAU --- 20 amp ----OK---- pending kitchen lights | CRAIGS | CRAIGS | | E= | P | 5907921 |
SPRINGS FAMILY ELECTRIC | ER | P | 07/16/2018 | pending cut sheet on the lay in lights , how to hook to the grid | CRAIGS | CRAIGS | | ER | P | 5904008 |
SPRINGS FAMILY ELECTRIC | ES | C | 04/13/2018 | Commercial Service: unit 170 A -- 170 B ---4/W 200 amp each OK to set meters | CRAIGS | CRAIGS | | ES | C | 5816289 |
SPRINGS FAMILY ELECTRIC | ES | R | 04/12/2018 | Commercial Service: float the neutral in the meter by use of a floating kit --- float the neutral in the disconnects --- take the equipment ground to the case of the disconnect scrape paint and use a machine screw | CRAIGS | CRAIGS | | ES | R | 5815162 |
SPRINGS FAMILY ELECTRIC | ER | P | 04/04/2018 | walls ----- Discussed accessiblity requirements with contractor / | CRAIGS | CRAIGS | | ER | P | 5807524 |
SPRINGS FAMILY ELECTRIC | ESL | C | 03/09/2018 | | CRAIGS | CRAIGS | | ESL | C | 5784911 |
M W MECHANICAL INC | H= | C | 08/29/2018 | TEST AND BALANCE REPORT RECEIVED | MARKB | MARKB | | H= | C | 5949071 |
M W MECHANICAL INC | H= | P | 08/14/2018 | FINAL PENDING - Test And Balance Report. OTHER ITEMS CORRECTED | MARKB | MARKB | | H= | P | 5934206 |
CASEBIER MECHANICAL CONTRACTORS | H= | C | 08/03/2018 | Previous items addressed | MARKB | MARKB | | H= | C | 5923714 |
CASEBIER MECHANICAL CONTRACTORS | H= | P | 07/27/2018 | 2 PSI APPROVAL LETTER RECEIVED FROM CSU. FOR FINAL - Regulator on cook line lacks protection from being smashed by cook equipment. Need to complete condensate line for water heater. Gas flex can not run through ceiling, it must be in same room fully as the water heater. Gas piping on roof lacks medium pressure stickers before the regulators. | MARKB | MARKB | | H= | P | 5916672 |
M W MECHANICAL INC | HRP | C | 07/25/2018 | WALKIN COOLER - CONDENSATE LINE INSTALLED AND CONDENSERS MOUNTED ON TOP OF COOLER | MARKB | MARKB | | HRP | C | 5912943 |
M W MECHANICAL INC | HD | C | 07/25/2018 | FOR FINAL - Cap end wall with metal used for clearance reduction. Need to confirm hood interlocks. Seal holes in walkin cooler. Need equipment under hood pushed into it's final resting place. ABOVE CEILING DUCT - GREASE WRAP COMPLETE, HIGH TEMP GASKET INSTALLED AND SPLICE RECEIVED. | MARKB | MARKB | | HD | C | 5912940 |
M W MECHANICAL INC | HD | P | 07/02/2018 | GREASE DUCT LIGHT TEST COMPLETE - OK TO FINISH WRAP. ROOF - OK EXCEPT NEED HIGH-TEMP GASKET IN HOOD FAN. | MARKB | MARKB | | HD | P | 5891894 |
CASEBIER MECHANICAL CONTRACTORS | HC | C | 06/22/2018 | OK TO SET 2 LB METER. | NANCY | NANCY | | HC | C | 5883677 |
CASEBIER MECHANICAL CONTRACTORS | HI | C | 06/22/2018 | 10 LB TEST OK ON COOK LINE. INSTALLED AS PER PRINT. BY FINAL NEED LETTER FROM CSU APPROVING MEDIUM PRESSURE GAS FOR THIS ADDRESS. | NANCY | NANCY | | HI | C | 5883672 |
M W MECHANICAL INC | HD | P | 06/19/2018 | GREASE DUCT LIGHT TEST - HOLE BELOW PANTS ON RIGHT SIDE FIXED. STILL NEED - To light test Both hood connections from hood being moved and clearance reduction on left side of hood.
| MARKB | MARKB | | HD | P | 5879295 |
M W MECHANICAL INC | HD | P | 06/05/2018 | Still need engineered splice to continue with inspections. GREASE DUCT LIGHT TEST COMPLETE FROM ROOF CURB DOWN TO HOODS EXCEPT FOR 1 HOLE ON RIGHT SIDE BELOW PANTS AND HOODS WILL PROBABLY BE MOVED AND WILL NEED NEW LIGHT TEST AT EACH HOOD. | MARKB | MARKB | | HD | P | 5865447 |
M W MECHANICAL INC | HD | P | 06/01/2018 | In addition to engineer addressing RTU ducts, equipment changes and grease duct changes with a plan splice, engineer also needs to address HOOD Mart hood and clearance to combustible cooler walLs on LEFT side of hood and cook line. GREASE DUCT LIGHT TEST - STARTED WITH DUCT ON RIGHT SIDE AT HOOD CONNECTION AND HAD 10 HOLES MOSTLY IN CORNERS UP TO BOTTOM OF PANTS. STOPPED INSPECTION. | MARKB | MARKB | | HD | P | 5862417 |
M W MECHANICAL INC | HD | R | 05/30/2018 | Call ahead at 10:41, no mechanical contractor found on site at 11:26. Type 1 hood wall closed up without inspection for combustibles, grease hoods/grease fan/grease duct do not match equipment schedule or plans. Hoods are currently tied into one rectangle duct and plans call for each hood to have its own round duct and exhaust fan. Only one hood fan is installed instead on two. Hood is hung with 3/8" all thread and plans call for 1/2". Duct for RTU'S # 1 & 2 does not match plans. Will need grease duct light test for welded duct. Re inspect all. | MARKB | MARKB | | HD | R | 5858896 |
CASEBIER MECHANICAL CONTRACTORS | HI | P | 04/12/2018 | 10 PSI PRESSURE TEST OK. PIPING PER PLAN SPLICE. Can release meter once gas stub is tagged with suite number. Still need pressure test on cook line. | MARKB | MARKB | | HI | P | 5815359 |
CASEBIER MECHANICAL CONTRACTORS | HI | R | 04/11/2018 | Install still does not match splice - see previous inspection notes. | MARKB | MARKB | | HI | R | 5813413 |
CASEBIER MECHANICAL CONTRACTORS | HI | R | 04/09/2018 | GAS PIPING NOT PER PLAN - Plan shows gas piping on roof and all is installed inside. Piping to RTU's is undersized and water heater is oversized per plan. No medium pressure stickers, need 2 psi approval letter from CSU. Will need a plan splice for gas piping and new pressure test once piping is corrected. | MARKB | MARKB | | HI | R | 5811777 |
CASEBIER MECHANICAL CONTRACTORS | P= | C | 07/26/2018 | correction made | TED | TED | | P= | C | 5914744 |
CASEBIER MECHANICAL CONTRACTORS | P= | P | 07/17/2018 | no hot water for inspection, rest ok | TED | TED | | P= | P | 5905190 |
CASEBIER MECHANICAL CONTRACTORS | PTO | C | 04/03/2018 | test and design ok | TED | TED | | PTO | C | 5806059 |
CASEBIER MECHANICAL CONTRACTORS | PB | C | 03/09/2018 | sanitary test and design ok | TED | TED | | PB | C | 5784613 |
CASEBIER MECHANICAL CONTRACTORS | PB | P | 03/08/2018 | grease line test and design ok | TED | TED | | PB | P | 5783267 |
M W MECHANICAL INC | XMS | T | 07/18/2018 | PAID (REC#1519999) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: chnaged manuf. of hoods | DALEH | DALEH | | XMS | T | 5906733 |
SPRINGS FAMILY ELECTRIC | XES | T | 07/09/2018 | PAID (REC#1516679) PLAN SPLICE FEE: $50 by: SHELBY for Electrical | SHELBY | SHELBY | | XES | T | 5897090 |
THE HOUSE DOCTOR | XBS | T | 07/09/2018 | PAID (REC#1516677) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Clarify rating of waal - add wall at hood | MICHAELA | MICHAELA | | XBS | T | 5896027 |
CASEBIER MECHANICAL CONTRACTORS | XPS | T | 04/11/2018 | PAID (REC#1493165) PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: mechanical splice 4-11-18 | TCRIPPEN | TCRIPPEN | | XPS | T | 5813697 |
M W MECHANICAL INC | XMS | T | 04/04/2018 | PAID (REC#1493167) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: mechanical splice 4-4-18 | TCRIPPEN | TCRIPPEN | | XMS | T | 5808015 |