ADVANTAGE HEATING AND COOLING | H= | C | 10/29/2019 | | JERRYF | JERRYF | | H= | C | 6382720 |
ADVANTAGE HEATING AND COOLING | H= | P | 10/24/2019 | WILL NEED ONSITE INSPECTION - REGULATOR RECEIVED | JERRYF | JERRYF | | H= | P | 6378651 |
ADVANTAGE HEATING AND COOLING | HE | L | 09/27/2019 | Renewed for No Fee at 9/27/2019 8:55:41 AM | JACK | JACK | | HE | L | 6350110 |
LANDMARK PLUMBING AND HEATING, INC. | H= | C | 09/04/2018 | | JERRYF | JERRYF | | H= | C | 5953402 |
ADVANTAGE HEATING AND COOLING | H= | L | 08/30/2018 | COULD LOCATE INSTALL MANUAL FOR GAS REGULATORS - STOPPED INSPECTION | JERRYF | JERRYF | | H= | L | 5951285 |
ADVANTAGE HEATING AND COOLING | H= | P | 04/30/2018 | NEW VENT SYSTEM IS OK. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), , , -- Schedule a new final inspection after these are complete. | JERRYF | JERRYF | | H= | P | 5830592 |
LANDMARK PLUMBING AND HEATING, INC. | HSP | P | 04/30/2018 | NEED INSTALLATION MANUAL FOR GAS REGULATORS TO VERIFY VENTING OF REGULATORS | JERRYF | JERRYF | | HSP | P | 5830465 |
ADVANTAGE HEATING AND COOLING | H= | P | 04/25/2018 | HAD CONSULT WITH JOE FROM ADVANTAGE ON VENTING - NEED CONSULT WITH SENIOR INSPECTOR ON LINER SYSTEM - APPEARS B VENT CONNECTION AT LINER IS INCORRECT | JERRYF | JERRYF | | H= | P | 5827153 |
LANDMARK PLUMBING AND HEATING, INC. | HI | P | 04/25/2018 | HAVE 2 GAS CONTRACTOR S LISTED ON PERMIT - DO NOT KNOW WHAT GAS WORK WAS DONE BY LANDMARK - PIPING IS OK PER PLAN SPLICE | JERRYF | JERRYF | | HI | P | 5827150 |
ADVANTAGE HEATING AND COOLING | H= | P | 04/24/2018 | SEE HI AND HD NOTES | JERRYF | JERRYF | | H= | P | 5825516 |
ADVANTAGE HEATING AND COOLING | HV | P | 04/24/2018 | APPEARS VENT IS NOT CONNECTED TO LINER SYSTEM CORRECTLY - NEED INSTALL MANUAL FOR LINER SYSTEM TO VERIFY VENTING - TOTAL LOAD OF 320000 BTU ON 6" | JERRYF | JERRYF | | HV | P | 5825507 |
ADVANTAGE HEATING AND COOLING | HI | P | 04/24/2018 | 2 GAS LEAKS ON 3/4" LINE TO WATER HEATER NOTIFIED CONTRACTOR - PLAN CALLS FOR 1" TO WATER HEATER - TIFFED ALL CONNECTIONS - NEED GAS REGULATOR INSTALL MANUAL TO VERIFY REG SIZING | JERRYF | JERRYF | | HI | P | 5825501 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 05/17/2018 | Corrections made | SHANEN | SHANEN | | P= | C | 5847565 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 04/25/2018 | still need to revise plans for aav at hand sink, rest ok. | TAYLOR | TAYLOR | | P= | P | 5826667 |
LANDMARK PLUMBING AND HEATING, INC. | P= | L | 04/23/2018 | call complete at 8:41, nobody onsite, building locked at 9:12. | TAYLOR | TAYLOR | | P= | L | 5823689 |
LANDMARK PLUMBING AND HEATING, INC. | P= | R | 03/27/2018 | undersized cold water piping after meter, need mixing valve at hand sink, after replacing water heater ( undersized common vent and vent connector ), revise plans to show aav at hand sink, install T&P drain, need clearances from pex to b- vent above water heater, note: need mechanical plans for gas and venting for new water heater. | TAYLOR | TAYLOR | | P= | R | 5799792 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 03/07/2018 | ok and per plan. note: waters looped under ground | JOHNS | JOHNS | | PB | C | 5782054 |
LANDMARK PLUMBING AND HEATING, INC. | XPS | P | 04/25/2018 | PLAN SPLICE: (No Fee) by: JOEL for Plumbing: Add aav for hand sink | JOEL | JOEL | | XPS | P | 5826803 |
LANDMARK PLUMBING AND HEATING, INC. | XMS | T | 04/06/2018 | PAID (REC#1492205) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: mechanical splice4-6-18 | TCRIPPEN | TCRIPPEN | | XMS | T | 5809903 |