HOMEOWNER | B= | C | 03/22/2019 | All other required Final inspections are complete. (This is a computer generated result) | RICHB | RICHB | | B= | C | 6141180 |
HOMEOWNER | B= | P | 03/21/2019 | Final OK / finished basement - AC installed - no deck. Additional Inspections Required (computer generated): External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977). | RICHB | RICHB | | B= | P | 6139685 |
HOMEOWNER | BSP | P | 01/08/2019 | Thermal insulation in attic and basement OK | RICHB | RICHB | | BSP | P | 6071501 |
HOMEOWNER | BLA | C | 09/14/2018 | Lath okay | TRENTP | TRENTP | | BLA | C | 5965914 |
HOMEOWNER | BIN | C | 09/12/2018 | Thermal in walls & vaulted ceilings OK | RICHB | RICHB | | BIN | C | 5962947 |
HOMEOWNER | BFR | C | 09/10/2018 | Framing OK | RICHB | RICHB | | BFR | C | 5959826 |
HOMEOWNER | BSP | P | 06/12/2018 | front gable over frame and garage portal frame okay | NATHAN | NATHAN | | BSP | P | 5872551 |
HOMEOWNER | BFN | C | 03/22/2018 | Engineers observation Letter on file / Eufer noted / Foundation design on file | NOAH | NOAH | | BFN | C | 5796712 |
HOMEOWNER | BFD | C | 03/22/2018 | Drain is usable / Day lighted to south and verified -- Damp proofing OK | NOAH | NOAH | | BFD | C | 5796700 |
HOMEOWNER | BFT | C | 03/22/2018 | Engineers observation Letter on file / Soils report on file / PSF - habitual drain- 5% grade | NOAH | NOAH | | BFT | C | 5796695 |
HOMEOWNER | BFT | P | 03/05/2018 | AUTHORIZED INSPECTION BY ENGINEER | MATTHEWM | MATTHEWM | MATTHEWM | BFT | P | 5779591 |
HOMEOWNER | BFN | P | 03/05/2018 | AUTHORIZED INSPECTION BY ENGINEER | MATTHEWM | MATTHEWM | MATTHEWM | BFN | P | 5779590 |
HOMEOWNER | E= | C | 03/08/2019 | Correction complete / | ROB | ROB | | E= | C | 6128638 |
HOMEOWNER | E= | R | 03/07/2019 | a/c 16.9 max 25 its on a 30 | CRAIGS | CRAIGS | | E= | R | 6126613 |
HOMEOWNER | ES | C | 08/31/2018 | Residential Underground: 200 amp 3/w new res | CRAIGS | CRAIGS | | ES | C | 5952364 |
HOMEOWNER | ER | C | 08/31/2018 | 1---15 mcc --- no central vac --- finished basement --- ac pre wire | CRAIGS | CRAIGS | | ER | C | 5952358 |
HOMEOWNER | H= | C | 03/20/2019 | Performance test received. | MARK | MARK | | H= | C | 6138478 |
HOMEOWNER | H= | P | 03/12/2019 | Correct form for equipment change received. Still need performance test completed to include all heat runs in the basement. Intake at furnace has been increased to 12". 3/13: Equipment change letter attached to this permit. | MARK | MARK | | H= | P | 6132314 |
HOMEOWNER | H= | P | 03/11/2019 | Need to research use of hand written documents will update in the am. Need to increase the furnace intake vertical pipe at the furnace, per mfg it must be 12". Note: Louver door to mechanical, a/c (Full) outside air to the furnace return. all me with questions Mark 719 327-2950 Note:3/12/19: Need to include all basement rooms for the performance test and use the RBD form on our website for the equipment change letter. Left phone message for mechanical contractor. | MARK | MARK | | H= | P | 6130814 |
HOMEOWNER | HC | C | 09/07/2018 | RELEASE METER | KYLEW | KYLEW | | HC | C | 5958369 |
HOMEOWNER | HRR | C | 09/07/2018 | BY FINAL NEED HOME OWNER OPTED PERFORMANCE TEST. Equipment installed does not match equipment listed on approved equipment cert . Home owner must fill out the Equipment Change Form (Residential) and attach form to an inspection request by final. Form can be found on the PPRBD website under Downloads, Residential Handouts, Equipment Change Residential Duct Design. / NOTES: FINISHED BASEMENT, OUTSIDE AIR TO RETURN, A/C ROUGH COIL AND LINE SET. | KYLEW | KYLEW | | HRR | C | 5958365 |
HOMEOWNER | HI | C | 09/05/2018 | 10# test ok. note: 1" main at 70' to 1- furnace, 1- water heater and 1- fire place. | PAULO | PAULO | | HI | C | 5955903 |
HOMEOWNER | HI | P | 08/28/2018 | need to complete blk iron pipe into fire place cabinet with pressure test. note: 1" main at 70' to 1- furnace, 1- water heater and 1- fire place. | PAULO | PAULO | | HI | P | 5948037 |
HOMEOWNER | P= | C | 03/08/2019 | Corrections made. See immages. | SAMH | SAMH | | P= | C | 6128895 |
HOMEOWNER | P= | P | 03/08/2019 | Need high loop and shock arrestor at kitchen sink. Rest OK. Note; No Irrigation. | SAMH | SAMH | | P= | P | 6128253 |
HOMEOWNER | PTO | C | 09/07/2018 | Correction made. | DANR | DANR | | PTO | C | 5957963 |
HOMEOWNER | PTO | P | 09/05/2018 | Cold water undersized, rest ok. | DANR | DANR | | PTO | P | 5955242 |
HOMEOWNER | PTO | P | 08/28/2018 | need nail protection missing multiple areas - top plate nail protection needs to extend 2" past plate, cold water piping under sized, glue and anchor basement toilet flange, set basement tub, install tub and overflow hall bathtub, rest ok, finished basement, no irrigation. Note: check water heater and expansion devise at final, | DANR | DANR | | PTO | P | 5947880 |
HOMEOWNER | PB | C | 04/02/2018 | 4" BLDG DRAIN, WILL REQUIRE AT LEAST (1) 2" VTR @ PTO | JOHNS | JOHNS | | PB | C | 5804711 |