REYNOLDS CONSTRUCTION | B= | C | 10/03/2018 | All other required Final inspections are complete. (This is a computer generated result) | DALE | DALE | | B= | C | 5984617 |
REYNOLDS CONSTRUCTION | B= | P | 09/28/2018 | insignia # 33586. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | DALE | DALE | | B= | P | 5980393 |
REYNOLDS CONSTRUCTION | B= | P | 09/27/2018 | need insulation at crawl space where taken down from plumbing / serial # 005-00P-H-A-002757AB -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | DALE | DALE | | B= | P | 5979019 |
REYNOLDS CONSTRUCTION | BFN | C | 08/08/2018 | Vapor barrier installed, ventilation requirements reduced, installed ventilation adequate | TIMOTHYS | TIMOTHYS | | BFN | C | 5928333 |
REYNOLDS CONSTRUCTION | BFN | R | 08/06/2018 | Masonry block skirt installed - 14.6 square feet of ventilation required, 10.2 provided - No vapor barrier visible | TIMOTHYS | TIMOTHYS | | BFN | R | 5924781 |
REYNOLDS CONSTRUCTION | BTD | C | 06/27/2018 | XI2 anchors inspected - Model and Serial # verified - Ridge and floor connections ok before cover | TIMOTHYS | TIMOTHYS | | BTD | C | 5887746 |
REYNOLDS CONSTRUCTION | BFD | C | 06/18/2018 | | SHAUN | SHAUN | | BFD | C | 5877370 |
REYNOLDS CONSTRUCTION | BFT | C | 06/18/2018 | Extended reinforced footing pads okay / Soils and foundation design okay per foundation notes on foundation plan Jesik report # 17-7351-6 | SHAUN | SHAUN | | BFT | C | 5877364 |
REYNOLDS CONSTRUCTION | BSP | P | 06/06/2018 | Received updated foundation plan | SHAUN | SHAUN | | BSP | P | 5865654 |
REYNOLDS CONSTRUCTION | BFD | P | 04/27/2018 | Drain full perimeter/ Drain gravity out fall to southeast / Complete BFT | SHAUN | SHAUN | | BFD | P | 5829803 |
REYNOLDS CONSTRUCTION | BFT | P | 03/26/2018 | Pad forms okay // please provide soils report // please provide foundation design with PSF requirement // pour at own risk. | NOAH | NOAH | | BFT | P | 5798654 |
WHITE RHINO ELECTRIC | E= | C | 07/31/2018 | Photos accepted | JOSEPH | JOSEPH | | E= | C | 5918699 |
WHITE RHINO ELECTRIC | EUG | C | 07/18/2018 | | JOSEPH | JOSEPH | | EUG | C | 5906460 |
WHITE RHINO ELECTRIC | E= | R | 07/18/2018 | Backfill trench --------- Protect cables on N. end of property from physical damage. (OK to cover with dirt / plywood) ------- Notes: No ac pre rough | JOSEPH | JOSEPH | | E= | R | 5906455 |
WHITE RHINO ELECTRIC | ES | C | 07/18/2018 | Residential Underground: 200 amp 3w new res need meter set | JOSEPH | JOSEPH | | ES | C | 5906447 |
WHITE RHINO ELECTRIC | E= | R | 07/17/2018 | See comments for service | JOSEPH | JOSEPH | | E= | R | 6089975 |
WHITE RHINO ELECTRIC | ES | R | 07/17/2018 | Permit is for temp service however this is a home so please attach to house permit & recall inspection under house permit. --------- Service neutral is loose in utility pedestal needs to be retightened. --------- Missing main bonding jumper. -------- Grounding electrode conductor to rods is loose in house panel. | JOSEPH | JOSEPH | | ES | R | 6089974 |
WHITE RHINO ELECTRIC | EUG | C | 07/16/2018 | 2 - service laterals from pedestal 4/0 to home & 1/0 to site 30 feet N.W. of home. Both URD | JOSEPH | JOSEPH | | EUG | C | 6089973 |
FALCON HEATING AND COOLING, INC. | H= | C | 09/19/2018 | NOTE: VENTED CRAWLSPACE, DIRECT VENT FURNACE, NO A/C, OUTSIDE AIR FROM ROOF LINE TO FURNACE CABINET, ELECTRIC WATER HEATER | BILLS | BILLS | | H= | C | 5969615 |
NASRALLAH PLUMBING & HEATING, INC. | HO+ | C | 08/27/2018 | 10LB TEST OK. 75' OF 1/2" POLY PIPE WITH TRACER WIRE FROM NEW TANK LOCATION TO REGULATOR LOCATION | BILLS | BILLS | | HO+ | C | 5946381 |
NASRALLAH PLUMBING & HEATING, INC. | HO | C | 08/22/2018 | 10LB TEST OK. 55' OF 1/2" POLY PIPE WITH TRACER WIRE FROM TANK TO REGULATOR LOCATION | BILLS | BILLS | | HO | C | 5942008 |
NASRALLAH PLUMBING & HEATING, INC. | HI | C | 08/22/2018 | 10LB TEST OK. 3/4" MAIN, 1 FURNACE | BILLS | BILLS | | HI | C | 5942003 |
ALLIED PLUMBING AND HEAT, LLC. | P= | C | 09/26/2018 | insulation in crawlspace to be inspected by build inspector at final, rest ok | JOSEPHD | JOSEPHD | | P= | C | 5977459 |
ALLIED PLUMBING AND HEAT, LLC. | PTO | C | 09/26/2018 | standing water test ok | JOSEPHD | JOSEPHD | | PTO | C | 5977456 |
ALLIED PLUMBING AND HEAT, LLC. | P= | P | 09/21/2018 | potable water certification sent to scanning | JOSEPHD | JOSEPHD | | P= | P | 5972061 |
ALLIED PLUMBING AND HEAT, LLC. | P= | P | 09/18/2018 | need standing water test on dwv below house, need potable water certification, need to patch the insulation in crawlspace water piping exposed, rest ok | JOSEPHD | JOSEPHD | | P= | P | 5968542 |
HOMEOWNER | PWO | C | 06/27/2018 | ok to cover note: at final will need potable water certification and to check for freeze protection at line under house, also check well tank connections in pit | JOSEPHD | JOSEPHD | | PWO | C | 5887505 |