THE WRIGHT GROUP, LLC | B= | C | 11/21/2018 | item corrected / final OK pending other finals | DANE | DANE | | B= | C | 6032278 |
THE WRIGHT GROUP, LLC | B= | R | 09/27/2018 | north gate is now on a latch that can not operated without a key / still need single action at north gate knob. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982). | DANE | DANE | | B= | R | 5978794 |
THE WRIGHT GROUP, LLC | B= | P | 09/26/2018 | need single action at north gate -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, PARKEY'S REFRIGERATION CO., INC Mechanical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5977391 |
THE WRIGHT GROUP, LLC | BSP | P | 09/07/2018 | Reviewed need for panic hardware at gates to pool per IBC 1008.1.10 with site superintendent as well as CSFD inspector | DAKOTAB | DAKOTAB | | BSP | P | 5958673 |
THE WRIGHT GROUP, LLC | BFT | C | 09/07/2018 | Engineer letter for reinforced steel received -- Open hole received -- 1500 PSF - No drain required | DAKOTAB | DAKOTAB | | BFT | C | 5958669 |
THE WRIGHT GROUP, LLC | BFT | R | 07/10/2018 | met on site with newest superintendent Brian and discussed need for open hole and engineer observations for all rebar as the pool has been poured and the last inspection was rejected / also discussed need for the plumber to attach a permit and have inspection / discussed all items that will be needed for final | DANE | DANE | | BFT | R | 5897853 |
THE WRIGHT GROUP, LLC | BFT | R | 04/23/2018 | not ready yet / still need minimum 3 ties at each lap / need minimum 12" lap at all bars / need open hole per plan - plan calls for all expansive soils to be removed | DANE | DANE | | BFT | R | 5824222 |
EMF ELECTRICAL CORPORATION | E= | C | 09/13/2018 | | BRET | BRET | | E= | C | 5964124 |
EMF ELECTRICAL CORPORATION | E= | R | 09/10/2018 | boilers not made up or bonded, gfci protections required for pump motors, could not located fence bonding point, missing required receptacle not less than 6' not more than 20' from pool. | BRET | BRET | | E= | R | 5959872 |
EMF ELECTRICAL CORPORATION | ESL | C | 08/09/2018 | equipotential bonding grid at pool deck ok | BRET | BRET | | ESL | C | 5928717 |
EMF ELECTRICAL CORPORATION | ESL | R | 08/08/2018 | use approved split bolts must be listed for direct burial contact with earth. | BRET | BRET | | ESL | R | 5927494 |
EMF ELECTRICAL CORPORATION | EUG | P | 06/22/2018 | eug from pool to building to cover, went over equipotential bonding requirements with contractor | BRET | BRET | | EUG | P | 5882569 |
EMF ELECTRICAL CORPORATION | ESL | C | 05/14/2018 | spa tub light bond | BRET | BRET | | ESL | C | 5843440 |
EMF ELECTRICAL CORPORATION | EUG | P | 04/25/2018 | pool shell , lights ok , hand rail and 4 point whips to ok deck | BRET | BRET | | EUG | P | 5826607 |
PARKEY'S REFRIGERATION CO., INC | H= | C | 09/26/2018 | MECHANICAL FINAL OK. | DUSTINS | DUSTINS | | H= | C | 5977496 |
PARKEY'S REFRIGERATION CO., INC | H= | L | 09/25/2018 | CONTRACTOR CANCELLED AT CALL AHEAD. | DUSTINS | DUSTINS | | H= | L | 5976660 |
PARKEY'S REFRIGERATION CO., INC | H= | P | 09/24/2018 | NEED CONTRACTOR THAT INSTALLED POOL BOILERS ATTACHED TO PERMIT AND CALL FOR INSPECTION. PROVIDE LETTER FROM ENGINEER APPROVING INSTALLATION OF EXHAUST FANS IN FIRST FLOOR GUEST ROOMS. FANS ARE BEING INSTALLED IN FRAMING BELOW RATED LID WITH NO DAMPERS. NEED PLAN SPLICE DELETING FIRE DAMPERS IN LAUNDRY IF THE WALL IS NOT RATED AND DAMPERS NOT REQUIRED. HAVE ENGINEER ADDRESS COMBUSTION AIR FOR POOL BOILERS. PLAN SHOWS DIRECT VENT BOILERS AND NON DIRECT VENT INSTALLED. NEED TO REVISE EQUIPMENT SCHEDULE FOR POOL BOILERS AS WELL. ENGINEER TO DRAW DETAIL FOR CLEARANCE REDUCTION FOR COMMERCIAL DRYER VENT. BRING 4" DRYER VENTS BELOW CEILING AND CAP VENT FOR FUTURE USE. | DUSTINS | DUSTINS | | H= | P | 5976659 |
PARKEY'S REFRIGERATION CO., INC | H= | L | 09/21/2018 | CONTRACTOR CANCELLED AT CALL AHEAD. | DUSTINS | DUSTINS | | H= | L | 5976658 |
PARKEY'S REFRIGERATION CO., INC | H= | P | 09/17/2018 | NEED CONTRACTOR THAT INSTALLED POOL BOILERS ATTACHED TO PERMIT AND CALL FOR INSPECTION. PROVIDE LETTER FROM ENGINEER APPROVING INSTALLATION OF EXHAUST FANS IN FIRST FLOOR GUEST ROOMS. FANS ARE BEING INSTALLED IN FRAMING BELOW RATED LID WITH NO DAMPERS. NEED PLAN SPLICE DELETING FIRE DAMPERS IN LAUNDRY IF THE WALL IS NOT RATED AND DAMPERS NOT REQUIRED. HAVE ENGINEER ADDRESS COMBUSTION AIR FOR POOL BOILERS. PLAN SHOWS DIRECT VENT BOILERS AND NON DIRECT VENT INSTALLED. NEED TO REVISE EQUIPMENT SCHEDULE FOR POOL BOILERS AS WELL. ENGINEER TO DRAW DETAIL FOR CLEARANCE REDUCTION FOR COMMERCIAL DRYER VENT. NEED DRYER INSTALLATION INSTRUCTIONS FOR GUEST DRYERS TO VERIFY VENT LENGTHS. NEED TO SEE THERMOSTATS INSTALLED IN ALL ROOMS. ROOF OK, JUST NEED TO LABEL ALL EQUIPMENT FOR AREA SERVED, INCLUDING EQUIPMENT ON GROUND. REPAIR ARMAFLEX ON SUCTION LINE IN PANTRY, ALSO NEED TO SEE EXHAUST FAN IN PANTRY ONCE DRY WALL INSTALLED. | DUSTINS | DUSTINS | | H= | P | 5976657 |
PARKEY'S REFRIGERATION CO., INC | H= | P | 09/13/2018 | NEED CONTRACTOR THAT INSTALLED POOL BOILERS ATTACHED TO PERMIT AND CALL FOR INSPECTION. PROVIDE LETTER FROM ENGINEER APPROVING INSTALLATION OF EXHAUST FANS IN FIRST FLOOR GUEST ROOMS. FANS ARE BEING INSTALLED IN FRAMING BELOW RATED LID WITH NO DAMPERS. NEED ENGINEER LETTER WILL BE ACCEPTABLE FOR THE OUTSIDE AIR DELETION FOR F-1, THE LETTER WILL ALSO NEED TO ADDRESS THE VENTILATION SCHEDULE ON THE PLAN. NEED PLAN SPLICE DELETING FIRE DAMPERS IN LAUNDRY IF THE WALL IS NOT RATED AND DAMPERS NOT REQUIRED. HAVE ENGINEER ADDRESS COMBUSTION AIR FOR POOL BOILERS. PLAN SHOWS DIRECT VENT BOILERS AND NON DIRECT VENT INSTALLED. NEED TO REVISE EQUIPMENT SCHEDULE FOR POOL BOILERS AS WELL. ENGINEER TO DRAW DETAIL FOR CLEARANCE REDUCTION FOR COMMERCIAL DRYER VENT. NEED DRYER INSTALLATION INSTRUCTIONS FOR GUEST DRYERS TO VERIFY VENT LENGTHS. FIRST FLOOR COMMON AREA MECHANICAL FINAL OK. NEED TO SEE ALL HOTEL ROOMS AND ROOF STILL. FURNACE VENT TERMINATIONS ON EAST SIDE NEED CORRECTED. | DUSTINS | DUSTINS | | H= | P | 5976656 |
PARKEY'S REFRIGERATION CO., INC | H= | P | 09/11/2018 | HAVE ENGINEER ADDRESS COMBUSTION AIR FOR POOL BOILERS. PLAN SHOWS DIRECT VENT BOILERS AND NON DIRECT VENT INSTALLED. NEED TO REVISE EQUIPMENT SCHEDULE FOR POOL BOILERS AS WELL. ENGINEER TO DRAW DETAIL FOR CLEARANCE REDUCTION FOR COMMERCIAL DRYER VENT. NEED DRYER INSTALLATION INSTRUCTIONS FOR GUEST DRYERS TO VERIFY VENT LENGTHS. | DUSTINS | DUSTINS | | H= | P | 5976655 |
PARKEY'S REFRIGERATION CO., INC | H= | P | 09/07/2018 | NEED PLAN SPLICE DELETING FIRE DAMPERS IN LAUNDRY IF THE WALL IS NOT RATED AND DAMPERS NOT REQUIRED. MISSING SUPPLY AIR FLEX AND DIFFUSERS IN BATHROOMS OK. CLEAR VINYL TUBING IN SOFFIT FOR CONDENSATE CORRECTED AND IS NOW OK. | DUSTINS | DUSTINS | | H= | P | 5976654 |
PARKEY'S REFRIGERATION CO., INC | HSP | P | 09/05/2018 | CONTRACTOR MENTIONED THE OUTSIDE AIR TO THE PTAC UNITS IS NOT GOING TO BE USED AND THE SHIPPING SCREW IS STILL IN THE VENT DOOR FOR ALL PTAC UNITS AND THERE WOULD NOT BE AN ISSUE FOR FURNACE VENT TERMINATIONS ON F1 AND F2 TO THE PTAC UNITS, HOWEVER, THE PLAN CALLS FOR 33 CFM OF TOTAL OUTSIDE AIR FOR EACH OF THE PTAC UNITS SO THE VENT DOORS WOULD NOT BE ABLE TO BE LEFT CLOSED AND UN OPERABLE. | DUSTINS | DUSTINS | | HSP | P | 5976653 |
PARKEY'S REFRIGERATION CO., INC | H= | P | 09/04/2018 | F1-MISSING SUPPLY AIR TO BOTH BATHROOMS NEAR WORKOUT AREA. F2, F3 AND F4 SUPPLY AND RETURN DUCTS AND OUTSIDE AIR COMPLETE, FLEX DIFFUSERS OK, F3- CAN NOT HAVE CLEAR VINYL TUBING IN SOFFIT SPACE FOR CONDENSATE AND F4 CONDENSATE IS OK . PLAN SHOWS FIRE DAMPER TRANSFER GRILLES FROM GUEST LAUNDRY TO COMMERCIAL LAUNDRY AND FIRE DAMPER FOR SUPPLY TO GUEST LAUNDRY AND IS NOT INSTALLED . NEED TO RESEARCH F1 AND F2 VENT TERMANTION CLEARANCES. | DUSTINS | DUSTINS | | H= | P | 5976652 |
PARKEY'S REFRIGERATION CO., INC | HV | P | 08/23/2018 | F-1, F-2, F-3 AND F-4 ALL COMBUSTION AIR PIPES AND EXHAUST VENTS NEED CORRECTED, CAN NOT HAVE THE 2" TO 3" REDUCER IN THE HORIZONTAL. | DUSTINS | DUSTINS | | HV | P | 5976651 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 08/23/2018 | UPDATED 8-24-18 DS: ENGINEER LETTER WILL BE ACCEPTABLE FOR THE OUTSIDE AIR DELETION FOR F-1, THE LETTER WILL ALSO NEED TO ADDRESS THE VENTILATION SCHEDULE ON THE PLAN. NEED TO CONSULT WITH SENIOR INSPECTOR ABOUT OUTSIDE AIR REMOVAL, CONTRACTOR ASKED IF ENGINEER LETTER WILL BE ACCEPTABLE FOR F-1. WILL UPDATE. SUPPLY AND RETURN DUCTS OK FOR F-3 AND F-4. STILL NEED TO COMPLETE F-1 AND F-2 STILL NEED TO SEE ALL FLEX AND DIFFUSERS. COMPLETE OUTSIDE AIR DUCT FOR F-4. F-1 AND F-2 CONDENSATE LINES OK. | DUSTINS | DUSTINS | | HD | P | 5976650 |
PARKEY'S REFRIGERATION CO., INC | HSP | P | 07/30/2018 | RANGE EXHAUST NOT REQUIRED PER RBC 304.4.6 | DUSTINS | DUSTINS | | HSP | P | 5976649 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 07/30/2018 | DUCTS IN SOFFIT SPACE OK. F-1: COMPLETE OUTSIDE AIR AND RETURN AIR DUCTS. F2: COMPLETE OUTSIDE AIR, RETURN AIR AND SUPPLY AIR DUCTS. F3: COMPLETE OUTSIDE AIR, RETURN AIR AND SUPPLY AIR DUCTS. F4: COMPLETE OUTSIDE AIR, RETURN AIR, AND THE 2 SUPPLY AIR DUCTS IN BREAKFAST AREA. WHEN VENTS FOR FURNACES ARE INSTALLED PLEASE CALL FOR INSPECTION. | DUSTINS | DUSTINS | | HD | P | 5976648 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 07/16/2018 | NEED CONTRACTOR INSTALLING POOL BOILER AND SPA BOILER TO ATTACH TO PERMIT. NEED TO CHECK ON IF THE OVEN NEEDS A RANGE EXHAUST. M2.1 (BDA 290) F-4 SUPPLY DUCT IN SOFFIT OK. | DUSTINS | DUSTINS | | HD | P | 5976647 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 05/30/2018 | PROVIDE LETTER FROM ENGINEER APPROVING INSTALLATION OF EXHAUST FANS IN FIRST FLOOR GUEST ROOMS. FANS ARE BEING INSTALLED IN FRAMING BELOW RATED LID WITH NO DAMPERS. FIRST FLOOR GUEST ROOM EXHAUST FANS ABOVE CEILING ALL OK. | NANCY | NANCY | | HD | P | 5976646 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 05/24/2018 | CANCELED AT CALL AHEAD. | NANCY | NANCY | | HD | P | 5976645 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 05/21/2018 | MAIN FLOOR GUEST ROOM BATH EXHAUST FANS ARE NOW BEING INSTALLED IN METAL FRAMED CEILING BELOW THE RATED LID. PRINTS SHOW FANS TO BE INSTALLED IN GYP BOARD CEILING WITH FIRE DAMPER. NEED REVISED/APPROVED PRINT OR LETTER FROM ENGINEER APPROVING THIS NEW INSTALLATION ON FIRST FLOOR. IF INSTALLING FAN BELOW RATING NO DAMPER REQUIRED BUT NEED ENGINEER TO ADDRESS PROTECTION OF EXHAUST DUCT AT RATED LID. | NANCY | NANCY | | HD | P | 5976644 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 05/14/2018 | EF-2 ON LEVELS 2, 3 AND 4 OK. OK TO COVER. | NANCY | NANCY | | HD | P | 5976643 |
PARKEY'S REFRIGERATION CO., INC | HV | P | 03/19/2018 | F-3 AND F-4 VENTS IN WALL OUT THROUGH ROOF OK. FOLLOW MANUFACTURERS INSTRUCTIONS FOR CORRECT TERMINATION OF VENTS ON ROOF. | NANCY | NANCY | | HV | P | 5976642 |
PARKEY'S REFRIGERATION CO., INC | HV | P | 03/15/2018 | AUTO CALL COMPLETE AT 2:01 - ARRIVED 2:40 - NO ON SITE PERSONNEL - CALLED CALLED AHEAD NUMBER TWICE / NO ANSWER - STOPPED INSPECTION - NEED FURNACE MANUAL TO VERIFY VENTING PER PREVIOUS NOTES | JERRYF | JERRYF | | HV | P | 5976641 |
PARKEY'S REFRIGERATION CO., INC | HV | R | 03/05/2018 | STOPPED INSPECTION NOT READY - NEED FURNACE INSTALL MANUAL TO VERIFY VENTING MATERIALS AND DISTANCE REQUIREMENTS / HAS 3 DIFFERENT TYPES OF PVC MATERIALS USED ON VENTING / USING F891 CELL CORE / ASTM 2665 / ASTM 1785 - NEED NAIL PROTECTION ON BOTH SIDES OF WALLS AT ALL FLOORS AND CEILINGS - NEED VERTICAL SUPPORT IN WALLS - NEED PLAN REVISION FOR RELOCATED FURNACE VENTS IN WALLS - HOW ARE VENTS TO BE CONCEALED IN WALLS VENTS ARE NOT IN WALLS COMPLETELY | JERRYF | JERRYF | | HV | R | 5976640 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 02/07/2018 | ITEMS FROM INSPECTION DATE 05/FEB/2018 CORRECTED | LIDO | LIDO | | HD | P | 5976639 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 02/05/2018 | SECOND FLOOR. 207: SEAL JOINT AT UPPER FLOOR. CHECK BACK DRAFT DAMPER, DOES NOT WANT TO CLOSE. 213: SEAL JOINT IN WALL. REST OF SECOND FLOOR GUEST ROOMS EXHAUST OK. | NANCY | NANCY | | HD | P | 5976638 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 02/01/2018 | SECOND FLOOR. 221: STRAP EXHAUST DUCT. 222: STRAP EXHAUST DUCT AND INSTALL DAMPER IN FAN. 223: SEAL MISSED JOINT AT FLOOR. 224: OK. 225: PROPERLY SECURE WOOD BLOCK TO STRUCTURE. 226: SCREWS DO NOT ALLOW BACK DRAFT DAMPER TO CLOSE. 228: OK. | NANCY | NANCY | | HD | P | 5976637 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 01/31/2018 | THIRD FLOOR GUEST ROOMS ABOVE CEILING ALL OK. | NANCY | NANCY | | HD | P | 5976636 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 01/30/2018 | ROOF CEILING ASSEMBLY NOW BEING INSTALLED IS THE UL-P545, WILL NEED LETTER FROM ENGINEER APPROVING INSTALLATION OF BATH EXHAUST FANS AND DAMPERS IN THIS ASSEMBLY. THIRD FLOOR. 317: REPAIR TWO BROKEN JOINTS ON BATH EXHAUST. 324: PROPERLY INSTALL FAN FROM STRUCTURE. REST OF THIRD FLOOR GUEST ROOMS OK. | NANCY | NANCY | | HD | P | 5976635 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 01/29/2018 | THIRD FLOOR. STOPPED INSPECTION. REINSPECT ALL ROOMS EXCEPT ONES PREVIOUSLY NOTED AS OK. | NANCY | NANCY | | HD | P | 5976634 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 01/26/2018 | THIRD FLOOR NORTH END GUEST ROOMS. 301, 304 AND 314: NOT READY. 305, 306, 307, 308, 309, 310, 311, 312, 313: EXHAUST ABOVE CEILING OK. | NANCY | NANCY | | HD | P | 5976633 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 01/24/2018 | FOURTH FLOOR. BATH EXHAUST IN ALL ROOMS OK. | NANCY | NANCY | | HD | P | 5976632 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 01/23/2018 | FOURTH FLOOR. ROOMS 401, 403 AND 404 NOT READY. REST OF ROOMS ON FOURTH FLOOR OK. NO EF-2 OR PTAC'S YET. | NANCY | NANCY | | HD | P | 5976631 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 01/18/2018 | FOURTH FLOOR EXHAUST DROPS OK TO WRAP EXCEPT FOR ROOM # 424 MISSING END CAP . Need to square up exhaust fan in room # 410 Rooms 401,403,404,405 not ready . | LIDO | LIDO | | HD | P | 5976630 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 01/11/2018 | P-522 ASSEMBLY DOES NOT LIST THE BROAN RDM-1 AS AN APPROVED DAMPER, SEE PAGE FR-2. FOURTH FLOOR EXHAUST: PROPERLY INSTALL START COLLARS AT EXHAUST DROPS. BEND AND SEAL CORNERS ON EXHAUST DROPS. PROPERLY INSTALL EXHAUST FANS TO STRUCTURE PER MANUFACTURERS INSTRUCTIONS. OK TO WRAP ROUND EXHAUST DUCTS. | NANCY | NANCY | | HD | P | 5976629 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 01/05/2018 | GAS/WATER HEATER VENT CONTRACTOR MUST ATTACH TO PERMIT AND CALL FOR INSPECTION WHEN READY. WILL NEED REVISED/APPROVED PRINTS FOR CHANGES BEING MADE IN FIELD (VENT TERMINATION LOCATIONS, METER LOCATION, BATH EXHAUST ON ROOF ETC.). BATH EXHAUST IN ATTIC WILL REQUIRE INSULATION. | NANCY | NANCY | | HD | P | 5976628 |
PARKEY'S REFRIGERATION CO., INC | HD | P | 12/05/2017 | NEED REVISED/APPROVED PRINTS. CONTRACTOR IS WORKING OFF A SET OF PRINTS THAT HAS NOT BEEN APPROVED BY RBD. SET ON SITE HAS MULTIPLE CHANGES FROM THE STAMPED SET. REVISED PRINTS MUST SHOW ALL CHANGES SUCH AS THE ADDED KITCHEN, POOL BOILER ROOM AND POOL EQUIPMENT, NEW GAS INSTALLATION AND METER LOCATION, SIZING FOR GAS TO FIREPIT, CHANGES TO BATH EXHAUST FANS IN CEILINGS ETC. CONTRACTOR INSTALLING GAS LINES MUST ATTACH TO PERMIT. CONTRACTOR INSTALLING WATER HEATER VENTS MUST ATTACH TO PERMIT OR ADD VENTS TO SCOPE OF WORK AND CALL FOR INSPECTION WHEN READY. CONTRACTOR TO VERIFY ALL DAMPERS BEING INSTALLED IN RATED ASSEMBLIES ARE APPROVED FOR THAT ASSEMBLY TYPE. RELAYED INFORMATION TO BRANDON TO CALL FREQUENT INSPECTIONS FOR THIS PROJECT. | NANCY | NANCY | | HD | P | 5976627 |
THE WRIGHT GROUP, LLC | XPS | P | 07/17/2018 | PLAN SPLICE: (No Fee) by: TCRIPPEN for Plumbing: plumbing splice 7-17-18 | TCRIPPEN | TCRIPPEN | | XPS | P | 5905614 |