JP COOPER CONSTRUCTION/INTERIOR FINISHES LLC | B= | C | 12/10/2018 | All other required Final inspections are complete. (This is a computer generated result) | DANE | DANE | | B= | C | 6048249 |
JP COOPER CONSTRUCTION/INTERIOR FINISHES LLC | B= | P | 12/07/2018 | final OK pending other finals. Additional Inspections Required (computer generated): CL SHARPER ELECTRIC Electrical Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 6046050 |
JP COOPER CONSTRUCTION/INTERIOR FINISHES LLC | BFR | C | 12/07/2018 | engineer letter received for truss repair / BFR now complete | DANE | DANE | | BFR | C | 6046048 |
JP COOPER CONSTRUCTION/INTERIOR FINISHES LLC | BE | L | 11/16/2018 | Renewed at 11/16/2018 4:13:41 PM | BECKYA | BECKYA | | BE | L | 6028756 |
JP COOPER CONSTRUCTION/INTERIOR FINISHES LLC | BFR | P | 05/18/2018 | interior light gauge framing OK pending other roughs / need to inspect truss repair after completed for CRAC unit / need to add mech permit / discussed accessible elements including pocket door handles | DANE | DANE | | BFR | P | 5849244 |
CL SHARPER ELECTRIC | ES | C | 12/10/2018 | Commercial Service: 200 amp service complete--No action required / | ROB | ROB | | ES | C | 6048263 |
CL SHARPER ELECTRIC | E= | C | 12/10/2018 | Corrections complete / | ROB | ROB | | E= | C | 6048248 |
CL SHARPER ELECTRIC | E= | P | 12/07/2018 | Electrical complete except grounding electrode conductor / | ROB | ROB | | E= | P | 6046714 |
CL SHARPER ELECTRIC | ER | C | 12/06/2018 | For Final: Need to look at service---RM 201 needs 2 blank plates--Rm 206 has recpts. not working---Ok to use breaker lockout for Nortec Unit---Need GFCI protection for recpts. within 6' of sink in Rm 208 and the Mech. room / | ROB | ROB | | ER | C | 6045288 |
CL SHARPER ELECTRIC | ER | R | 12/04/2018 | Plastic boxes with metallic cabling not code compliant-- Cannot use white wire in conduit for backfeeding switches--need disconnect for Nortec unit---ground switches, conduit to switches need full size ground in paitent care areas--will need to verify wiring above ceiling that it meets 517.13 for patient care areas / | ROB | ROB | | ER | R | 6042566 |
CL SHARPER ELECTRIC | ES | P | 11/29/2018 | Commercial Service: PRE RELEASE OK FOR CONTRACTOR TO SCHEDULE SWITCH OVER ----OK TO SET METER---- | GREGM | GREGM | | ES | P | 6037546 |
CL SHARPER ELECTRIC | ES | R | 11/21/2018 | Commercial Service: SEE ER NOTES--- | GREGM | GREGM | | ES | R | 6032324 |
CL SHARPER ELECTRIC | ER | R | 11/21/2018 | SEE ER NOTES--- | GREGM | GREGM | | ER | R | 6032318 |
CL SHARPER ELECTRIC | ES | R | 11/21/2018 | Commercial Service: LOCKED AT 9;50 CALL AHEAD AT 9:10----SEE ER NOTES---- | GREGM | GREGM | | ES | R | 6032030 |
CL SHARPER ELECTRIC | ER | L | 11/21/2018 | CALL AHEAD 9:10 LEFT AT 9:50---- WENT BACK FOR INSP PER MATT---LINE AND LOAD @ MAIN BREAKER REVERSED--- PENDING MANUFACTURES INFO----- | GREGM | GREGM | | ER | L | 6032029 |
CL SHARPER ELECTRIC | E= | R | 11/19/2018 | METER SOCKET NEEDS TO BE LEVER OPERATED ---ONE LINE NEEDS TO MATCH WHAT WAS INSTALLED------REMOVE NM CABLE | GREGM | GREGM | | E= | R | 6029255 |
CL SHARPER ELECTRIC | ES | R | 10/24/2018 | Aluminum used instead of copper, used SER instead of raceway, changes will need to be submitted and spliced---need water pipe ground, (no steel or ufer available per contractor ), 2- ground rods installed but need to remove from meter base and route straight to service disconnect---Service disconnect needs correct AIC rating--Line side to meter is not per print, had bore and utilized 4/0 AL URD, told contractor to also get CSU approval / | ROB | ROB | | ES | R | 6005152 |
CL SHARPER ELECTRIC | ER | P | 05/18/2018 | Rough in for walls ok--All HCF cacable except lobby and reception area--Pipe stubs up for switches / | ROB | ROB | | ER | P | 5849330 |
THE FURNACE GUY HEATING & COOLING | H= | C | 11/02/2018 | CORRECTIONS MADE / TEST AND BALANCE REPORT RECEIVED ( SEE IMAGES ) | LIDO | LIDO | | H= | C | 6013922 |
THE FURNACE GUY HEATING & COOLING | H= | P | 10/29/2018 | PARTIAL PENDING FOR - NEED REVISED TEST AND BALANCE REPORT, NEED CONDENSATE LINE FROM STEAM DISTRIBUTER INSULATED PER NOTE 1 ON THE M2.0 PLAN. CONTRACTOR TO CONFIRM 1/4 COPPER INSTALLED TO HUMIDIFIER BEHIND SHEET ROCK. OK FOR CONTRACTOR TO ATTACH PICTURES TO NEXT INSPECTION REQUEST. | LIDO | LIDO | | H= | P | 6009345 |
THE FURNACE GUY HEATING & COOLING | H= | P | 10/29/2018 | EXISTING OUTSIDE AIR READING ARE NOT CORRECT, REFER TO PLAN PAGE M2.0 FOR THE CORRECT REQUIRED EXISTING OUTSIDE AIR ( 175 CFM,) MISSING OUTSIDE AIR READINGS FOR CRAC UNIT, REFER TO PLAN PAGE M1.0. | LIDO | LIDO | | H= | P | 6008427 |
THE FURNACE GUY HEATING & COOLING | H= | P | 10/23/2018 | THERMOSTAT IS OVER 48" ABOVE FINISHED FLOOR , NOTE 1 ON THE PLANS SHOWS 1/4" COPPER CONDENSATE LINE FROM STEAM DISTRIBUTER / PLASTIC TUBING WAS INSTALLED , PLASTIC TUBING IS NOT PERMITTED TO BE INSTALLED IN CONCEALED LOCATION / ATTIC , A TRAP IS ALSO REQUIRED PER INSTALLATION INSTRUCTIONS PAGE # 5. DOES THE CRAC UNIT HAVE INTERNAL SECONDARY PROTECTION IF CONDENSATE GETS BLOCKED ? SUPPORT LINE SET UP OF CRAC UNIT IN ATTIC . NEED CONTROL WIRES PROTECTED WERE THEY ENTER THE CRAC UNIT .NEED TEST AND BALANCE REPORT .
| LIDO | LIDO | | H= | P | 6003668 |
THE FURNACE GUY HEATING & COOLING | HD | P | 07/31/2018 | DUCT ROUGH ABOVE HARD LID IN TREATMENT ROOM 208 OK - OK TO WRAP . NEED INSTALLATION INSTRUCTIONS FOR HUMIDIFIER AND CRAC UNIT. LINE SET IN ATTIC OK. | LIDO | LIDO | | HD | P | 5919526 |
AMERICAN PRIDE PLUMBING | P= | C | 11/06/2018 | Correction made. | DANR | DANR | | P= | C | 6017999 |
AMERICAN PRIDE PLUMBING | P= | P | 10/22/2018 | Need PTO completed. | DANR | DANR | | P= | P | 6001951 |
AMERICAN PRIDE PLUMBING | PE | C | 10/02/2018 | | TERRI | TERRI | | PE | C | 5982968 |
AMERICAN PRIDE PLUMBING | PTO | P | 05/10/2018 | Need plans spliced showing added sink, need engineer approval for aav P1.0 shows vtr, need engineer approval for pex piping drawing P1.0 shows L copper, rest ok. | DANR | DANR | | PTO | P | 5841295 |
CL SHARPER ELECTRIC | XES | T | 11/16/2018 | PAID (REC#1557091) PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revise conductor size | BERTHA | BERTHA | | XES | T | 6028751 |
AMERICAN PRIDE PLUMBING | XPS | T | 10/30/2018 | PAID (REC#1553232): PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 10-30-18 | TCRIPPEN | TCRIPPEN | | XPS | T | 6010321 |