ALEXANDHER BUILDING CO, INC. | B= | C | 07/24/2018 | final OK pending other finals | DANE | DANE | | B= | C | 5912355 |
ALEXANDHER BUILDING CO, INC. | B= | P | 07/13/2018 | Temp CO: pending bldg, mech, elect finals ( Expires: 8/12/2018 12:00:00 AM) | MINDY | MINDY | | B= | P | 5902734 |
ALEXANDHER BUILDING CO, INC. | B= | P | 07/13/2018 | final OK pending other finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), AIR TECH MECHANICAL INC Mechanical Final Inspection is not Completed yet, EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, GRANT DRUMMOND II Plumbing Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5902400 |
DRUMMOND PLUMBING LLC | BSP | T | 06/21/2018 | PAID (REC#1509635): ADDITIONAL PLAN REVIEW TIME: $50 From: DALEH gas pipe revisions | DALEH | DALEH | | BSP | T | 5881336 |
ALEXANDHER BUILDING CO, INC. | BFR | P | 05/18/2018 | plans show majority of walls as type A walls which are to go up to deck above but all walls were built as type B to above grid - need to splice in change of wall types / interior light gauge framing is OK pending change of wall types and all other roughs / discussed accessible elements and need for panic at rear doors at final | DANE | DANE | | BFR | P | 5849622 |
EL PASO ELECTRIC, LLC. | E= | C | 07/17/2018 | | BRET | BRET | | E= | C | 5904580 |
EL PASO ELECTRIC, LLC. | E= | P | 07/13/2018 | install factory cords or hard wire ice and dishwasher with disconnects, 15 amp max hood, mua, exhaust fan 20 amp breakers installed. gfci receptacle under hood, dishwasher if cord connected. back freezer gfci not accessible, breakers or circuits miss labeled on rtu, panel schedule | BRET | BRET | | E= | P | 5901798 |
EL PASO ELECTRIC, LLC. | ER | C | 07/11/2018 | fill un-used opening by hood , cover plate and fixture plate south ceiling | BRET | BRET | | ER | C | 5898817 |
EL PASO ELECTRIC, LLC. | ER | R | 07/10/2018 | ceiling covered prior to inspection , plug un-used opening in boxes, boxes not made, mc whip laying on ceiling, covers on boxes, plate not made for fixture whip to fixture . | BRET | BRET | | ER | R | 5897476 |
EL PASO ELECTRIC, LLC. | ES | C | 06/29/2018 | Commercial Service: 400 - amp 4 Wire new service, ok to set meter / | CRAIG | CRAIG | | ES | C | 5889735 |
EL PASO ELECTRIC, LLC. | ER | P | 05/22/2018 | remaining walls and bath lids | BRET | BRET | | ER | P | 5851841 |
EL PASO ELECTRIC, LLC. | ER | P | 05/18/2018 | Rough in ok for west wall in seating area, bathroom walls, and hall walls / Need PR's with 8/32 screw holes on sconces / Discussed accessibility requirements with general contractor / | ROB | ROB | | ER | P | 5850017 |
EL PASO ELECTRIC, LLC. | ER | R | 04/27/2018 | ground all boxes, existing receptacle needs to be removed or relocated (behind studs of wall) | BRET | BRET | | ER | R | 5829205 |
EL PASO ELECTRIC, LLC. | ESL | C | 04/17/2018 | | BRET | BRET | | ESL | C | 5818580 |
AIRTECH MECHANICAL, INC. | H= | C | 07/13/2018 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. CORRECTIONS IMAGES ATTACHED, SEE IMAGES. MECHANICAL FINAL OK. | DUSTINS | DUSTINS | | H= | C | 5902788 |
DRUMMOND PLUMBING LLC | H= | C | 07/13/2018 | GAS FINAL OK. | DUSTINS | DUSTINS | | H= | C | 5901871 |
DRUMMOND PLUMBING LLC | HV | C | 07/13/2018 | WATER HEATER VENT OK. | DUSTINS | DUSTINS | | HV | C | 5901870 |
AIRTECH MECHANICAL, INC. | H= | P | 07/13/2018 | INTERLOCKS CONFIRMED. FOR FINAL: LABEL EQUIPMENT ON ROOF, HIGH TEMP SEAL AROUND GREASE DUCT AT FAN, PROVIDE TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | H= | P | 5901866 |
DRUMMOND PLUMBING LLC | H= | P | 07/10/2018 | WATER HEATER VENT NEEDS CORRECTED BEFORE FINAL CAN BE COMPLETED. | DUSTINS | DUSTINS | | H= | P | 5897783 |
DRUMMOND PLUMBING LLC | HV | P | 07/10/2018 | NEED PROPER WATER HEATER VENT TERMINATION AND TO BE 10' AWAY FROM INTAKES. | DUSTINS | DUSTINS | | HV | P | 5897780 |
AIRTECH MECHANICAL, INC. | HD | P | 07/06/2018 | ABOVE CEILING OK. GREASE DUCT FIRE WRAP OK. NEED TO SEE INTERLOCKS, SMOKE DETECTOR WITH REMOTE INDICATOR FOR RTU-7, THERMOSTATS AND ROOF. ISOLATE PVC FROM RETURN AIR PLENUM. PROVIDE TEST AND BALANCE REPORT FOR FINAL. | DUSTINS | DUSTINS | | HD | P | 5895461 |
DRUMMOND PLUMBING LLC | HC | C | 06/22/2018 | OK TO SET 2 LB METER. | NANCY | NANCY | | HC | C | 5882680 |
DRUMMOND PLUMBING LLC | HI | C | 06/22/2018 | SPLICE APPROVED 6/21/18. HARD COPY NOT ON SITE TODAY, NOT SCANNED INTO ELECTRONIC COPY YET. WILL NEED TO SEE SPLICE BEFORE FINAL. 10 LB TEST OK. | NANCY | NANCY | | HI | C | 5882672 |
DRUMMOND PLUMBING LLC | HI | P | 06/12/2018 | LOW TEST. NEED REVISED/APPROVED PRINTS SHOWING NEW GAS LAYOUT FOR WATER HEATER, COOK LINE TIE IN ON ROOF AND SIZING. WILL RELEASE METER AFTER PRINTS HAVE BEEN REVISED/APPROVED. | NANCY | NANCY | | HI | P | 5872590 |
AIRTECH MECHANICAL, INC. | HD | P | 05/09/2018 | GREASE DUCT OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 5840137 |
AIRTECH MECHANICAL, INC. | HD | P | 05/07/2018 | REPAIR MARKED HOLES IN GREASE DUCT. DROP OK, OK TO WRAP. BUTT WELDS THAT STILL NEED INSPECTION MARKED IN RED PAINT. | NANCY | NANCY | | HD | P | 5837211 |
AIRTECH MECHANICAL, INC. | HD | P | 05/01/2018 | CONTRACTOR INSTALLING WATER HEATER VENT NEEDS TO ADD IT TO THE SCOPE OF WORK AND CALL FOR INSPECTION WHEN READY. DOES THE DISHWASHER REQUIRE A HOOD? KITCHEN EXHAUST FAN IS WITHIN 10' OF ECONOMIZER FOR RTU#7, NEED TO VERIFY IF FAN DISCHARGE WILL BE 10' AWAY OR 3' ABOVE ECONOMIZER. HOOD WALL OK TO COVER PER MECHANICAL ONLY. NOTE: SEE M1 FOR INTERLOCKS. SEE M2 NO REFRIGERATION LEAKAGE ALARM REQUIRED. | BILLS | BILLS | | HD | P | 5832323 |
AIRTECH MECHANICAL, INC. | HD | P | 05/01/2018 | NEED ONSITE INSPECTION OF HOOD WALL. PICTURE OF HOOD WALL FROM CONTRACTOR RECEIVED, SEE IMAGES | BILLS | BILLS | | HD | P | 5831859 |
DRUMMOND PLUMBING LLC | P= | C | 07/23/2018 | revised plans ok. | TAYLOR | TAYLOR | | P= | C | 5910397 |
DRUMMOND PLUMBING LLC | P= | P | 07/11/2018 | still need to revise plans, rest ok. | TAYLOR | TAYLOR | | P= | P | 5898710 |
DRUMMOND PLUMBING LLC | P= | P | 07/10/2018 | toilet handle needs to be on the open side at mens restroom, can not have slip joint fitting on the horizontal, still need to revise plans, rest ok. | TAYLOR | TAYLOR | | P= | P | 5898186 |
DRUMMOND PLUMBING LLC | PTO | C | 05/18/2018 | aav at hand sink, check water heater by final, note: need to revise plans for 3 - 2 inch vents, 1 inch DCW to restrooms and kitchen area, type M copper. | TAYLOR | TAYLOR | | PTO | C | 5849178 |
DRUMMOND PLUMBING LLC | PB | C | 04/11/2018 | DWV test OK | SHANEN | SHANEN | | PB | C | 5814697 |
DRUMMOND PLUMBING LLC | XPS | T | 07/19/2018 | PAID (REC#1519550): PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 7-19-18 | TCRIPPEN | TCRIPPEN | | XPS | T | 5908214 |
ALEXANDHER BUILDING CO, INC. | XBS | P | 07/11/2018 | PLAN SPLICE: (No Fee) by: SHELLEY for Construction: revised wall types | SHELLEY | SHELLEY | | XBS | P | 5899443 |
DRUMMOND PLUMBING LLC | XMS | T | 04/19/2018 | PAID (REC#1494878) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: plumbing splice 4-19-18 | TCRIPPEN | TCRIPPEN | | XMS | T | 5821856 |