HOMEOWNER | B= | C | 05/16/2019 | All other required Final inspections are complete. (This is a computer generated result) | NICK | NICK | | B= | C | 6201758 |
HOMEOWNER | B= | P | 05/15/2019 | . Additional Inspections Required (computer generated): External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977). | NICK | NICK | | B= | P | 6199629 |
HOMEOWNER | BIN | C | 01/15/2019 | | NICK | NICK | | BIN | C | 6078534 |
HOMEOWNER | BFR | C | 01/15/2019 | | NICK | NICK | | BFR | C | 6078515 |
HOMEOWNER | BFR | P | 01/07/2019 | Complete HRR / Remove foam blocks from bottom of floating walls, Okay to check at insulation inspection | SHAUN | SHAUN | | BFR | P | 6070759 |
HOMEOWNER | BFI | C | 05/15/2018 | 2" R-10 rigid OK at entire foundation perimeter | LONNYS | LONNYS | | BFI | C | 5844771 |
HOMEOWNER | E= | C | 05/14/2019 | corrections made | BRIAN | BRIAN | | E= | C | 6198065 |
HOMEOWNER | E= | R | 05/13/2019 | need the correct breaker locks for oven / cook top / can not use square D breaker in GE panel / install the blank covers on the oven , cook top / | BRIAN | BRIAN | | E= | R | 6196808 |
HOMEOWNER | E= | R | 03/08/2019 | j boxes for cooktop and range need to be accessible, leave open for inspection, need TR outlets thru out, need WR/TR outlet outside front, add outlet at left of cook top per spacing req, dryer outlet needs to be 4 wire, and needs 30 amp cb, oven needs 20 amp cb, a/c disco needs to be relocated for proper clearance, cable to a/c head needs to changed to proper cable, can run UF and sleeve at condenser, pvc to a/c disco needs to be supported every 3', need cb lockouts on oven and cook top cb's, need complete re inspect. | JOHNN | JOHNN | | E= | R | 6128324 |
HOMEOWNER | ES | C | 01/11/2019 | Residential Overhead: 200-amp 3-wire , new service on existing detached garage, ok to energize. | JOHNN | JOHNN | | ES | C | 6075900 |
HOMEOWNER | ES | R | 01/10/2019 | need #4 cu to bond bushing. | JOHNN | JOHNN | | ES | R | 6074459 |
HOMEOWNER | ES | R | 01/09/2019 | 1) need re/washers on meter side, 2) need grd bushing same side, 3) need to seal meter | GARYL | GARYL | | ES | R | 6073032 |
HOMEOWNER | ER | C | 12/18/2018 | NOTE! need a service | GARYL | GARYL | | ER | C | 6057227 |
HOMEOWNER | ER | R | 11/27/2018 | advised HO of future trip fees, suggested getting a licensed EC, grd all driver boxes, bath outlet circuit has outlets outside the bath rm on it, 240v dryer line needs green grd screw with #10 grd connected and nm connecter is installed backwards, smoke detectors need 12/3 nm cable, outside lights and outlets need boxes and grds connected, complete reinspect,---------------------------will have gas HWH,needs service inspection, check connections on cooktop and oven on final, | JOHNN | JOHNN | | ER | R | 6035506 |
HOMEOWNER | ER | R | 06/12/2018 | make up all grds with 1 tail for each device, need proper boxes for 240 v lines in kitchen, nm connectors in lights and panel, outdoor outlets front and back, panel grds made up, float neutrals, wiring for smokes, calculate hwh load, complete re inspect,----------------no d/w,will need trench inspection,1 grd rod, | JOHNN | JOHNN | | ER | R | 5872153 |
HOMEOWNER | H= | C | 05/13/2019 | corrections made | DAVIDH | DAVIDH | | H= | C | 6196989 |
HOMEOWNER | H= | R | 03/08/2019 | needs proper condenser pad installed | DAVIDH | DAVIDH | | H= | R | 6128314 |
HOMEOWNER | HC | C | 01/07/2019 | RELEASE METER | TREVORH | TREVORH | | HC | C | 6070952 |
HOMEOWNER | HRR | C | 01/07/2019 | At final will verify condensate drain for surface mounted mini spit and condensing unit.. NOTE; MINI SPIT, DIRECT VENTED ON DEMAND WATER HEATER, MOUNTED ON THE EXTERIOR. | TREVORH | TREVORH | | HRR | C | 6070931 |
HOMEOWNER | HO | C | 09/25/2018 | 10 lb test ok still need hrr inspection before gas can be turned on | DAVIDH | DAVIDH | | HO | C | 5975819 |
HOMEOWNER | HO | P | 09/24/2018 | LOW TEST AT 7LBS , NEEDS TO BE AT 10LBS | DAVIDH | DAVIDH | | HO | P | 5974297 |
HOMEOWNER | HO | P | 09/21/2018 | pipe is ok but needs 10 lb test | DAVIDH | DAVIDH | | HO | P | 5972997 |
HOMEOWNER | HO | R | 06/19/2018 | NOTHING DONE | DAVIDH | DAVIDH | | HO | R | 5878454 |
HOMEOWNER | P= | C | 05/09/2019 | corrections made | JOSEPHD | JOSEPHD | | P= | C | 6193755 |
HOMEOWNER | P= | P | 03/08/2019 | need to hard pipe drain to kitchen sink, check master shower valves at next inspection, rest ok | JOSEPHD | JOSEPHD | | P= | P | 6128874 |
HOMEOWNER | PTO | C | 11/09/2018 | Check water heater at final, VTR | SHANEN | SHANEN | | PTO | C | 6021585 |
HOMEOWNER | PB | C | 10/09/2018 | Test OK | SHANEN | SHANEN | | PB | C | 5990060 |
HOMEOWNER | PB | P | 10/08/2018 | No test, design OK | SHANEN | SHANEN | | PB | P | 5988607 |
HOMEOWNER | PB | P | 06/14/2018 | Water service and drain stub-in OK, need to complete, test and inspect all plumbing under concrete slab to complete base inspection | SHANEN | SHANEN | | PB | P | 5874480 |
HOMEOWNER | PB | R | 06/12/2018 | Need waste water dept. inspection for building sewer, cannot glue PVC fittings to ABS pipe, need drain stack inside of structure, | SHANEN | SHANEN | | PB | R | 5872015 |
HOMEOWNER | PWO | P | 06/12/2018 | Depth and tie-in OK, needs CSU inspection, may require separate water service | SHANEN | SHANEN | | PWO | P | 5872003 |
HOMEOWNER | XMS | P | 04/26/2018 | PLAN SPLICE FEE: $0 by: JUSTINC for Mechanical: Revised from electric heat to mini split | JUSTINC | JUSTINC | | XMS | P | 5828561 |
HOMEOWNER | XBS | T | 04/26/2018 | PAID (REC#1496439) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Revised window sizes | SHELLEY | SHELLEY | | XBS | T | 5828493 |