BRIGHT CONSTRUCTION & DEVELOPMENT, INC. | B= | C | 11/02/2018 | All other required Final inspections are complete. (This is a computer generated result) | BRIANB | BRIANB | | B= | C | 6013842 |
BRIGHT CONSTRUCTION & DEVELOPMENT, INC. | B= | P | 10/18/2018 | pending other final inspections including required external inspections / corrections from previous inspection are okay - note - panic hardware has been installed and thumb turn and double keyed locks removed from doors noted from previous inspection. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), ROCKY MOUNTAIN ELECTRICAL SERV Electrical Final Inspection is not Completed yet. | BRIANB | BRIANB | | B= | P | 5998664 |
BRIGHT CONSTRUCTION & DEVELOPMENT, INC. | B= | R | 10/16/2018 | need to complete other final inspections including required external inspections / missing address posted / double keyed locks installed at front exit door 101 and exit door 108 to deck - approved design reflects single action at door 108 and panic hardware for front exit door 101(main exit door 100 has double keyed lock with lock indicator and signage) / missing exit sign at outdoor deck gate (no latch installed at time of inspection) / thumb-turn locks installed at both rear doors 102 & 103 - approved design reflects panic hardware / rear grab bar in men's and women's restroom does not measure min 24" from the centerline of the water closet on the transfer side / missing restroom signage / mirrors in men's and women's restroom measures over 40" to reflective surface off of floor / went over items found at final inspection with site rep. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), Exte | BRIANB | BRIANB | | B= | R | 5996077 |
BRIGHT CONSTRUCTION & DEVELOPMENT, INC. | BFR | P | 07/05/2018 | Framing OK pending other Roughs / hood wall framing OK pending Mechanical / discussed accessible elements / plans reviewed onsite | RICHB | RICHB | | BFR | P | 5894012 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | E= | C | 11/02/2018 | splice in prints---final okay | CHIPO | CHIPO | | E= | C | 6013841 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | E= | P | 09/21/2018 | all corrections made-----pending trip fee for plan splice | CHIPO | CHIPO | | E= | P | 5972828 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | E= | R | 09/20/2018 | need lights in the attic as per 210.70 3 | CRAIGS | CRAIGS | | E= | R | 5971016 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | E= | R | 09/13/2018 | Checked Roasting room,Dining Area, Restrooms, Coffee Bar, No attic items checked in dining area------Reversed polarity on bathroom recpts., Outside recpts. reading mis wired, All panels need to be labeled with calculated AIC and date of calculation, Missing fixtures in dining room that mount on 4" oct boxes, Roaster not connected in roaster room, Need LED dimmer and fixed wiring for coffee bar lights / | ROB | ROB | | E= | R | 5964876 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | ER | P | 08/22/2018 | Rough in ok for coffee bar area / | ROB | ROB | | ER | P | 5942572 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | ES | C | 08/22/2018 | Commercial Service: okay to set meter | CHIPO | CHIPO | | ES | C | 5942387 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | ES | R | 08/21/2018 | Commercial Service: Need to bond neutral to can in CT cabinet / | ROB | ROB | | ES | R | 5941462 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | ES | R | 07/19/2018 | GRC nipples between Disconnect and CT Cabinet need double locknuts and bond one side / Need to install conductors from CT Cabinet to Disconnect----Bond CT Cabinet per CSU Specs------Meyers Hubs need to be service rated / | ROB | ROB | | ES | R | 5907746 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | E= | R | 06/28/2018 | not ready | CRAIGS | CRAIGS | | E= | R | 5888533 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | ER | P | 06/28/2018 | only thing left for rough is the center area | CRAIGS | CRAIGS | | ER | P | 5888532 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | E= | R | 06/22/2018 | not ready | CRAIGS | CRAIGS | | E= | R | 5882905 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | ER | P | 06/22/2018 | walls -- switches and receptacles have been lowered | CRAIGS | CRAIGS | | ER | P | 5882889 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | ER | P | 06/19/2018 | Partial rough for walls and ceilings--Bathrooms need switches and recpts. lowered to meet ADA requirements--Wall that panelboard goes on not to be rocked up to loft ceiling and ceiling to be left open in loft where homeruns are not complete / Discussed accessibility requirements with contractor / | ROB | ROB | | ER | P | 5878611 |
WILLIAMS MECHANICAL | H= | C | 10/15/2018 | HOOD/OVEN/FURNACE INTERLOCK CONFIRMED | MARKB | MARKB | | H= | C | 5995279 |
WILLIAMS MECHANICAL | HSP | P | 10/12/2018 | Test And Balance Report Received - see images | MARKB | MARKB | | HSP | P | 5992917 |
WILLIAMS MECHANICAL | H= | P | 10/11/2018 | EF-1 STILL NEEDS TO BE INTERLOCKED WITH FURNACE AND OVEN PER PLAN. CONFIRMED INTERLOCK WITH ROASTER AND FURNACE | MARKB | MARKB | | H= | P | 5992765 |
MARTINSON MECHANICAL, INC | H= | C | 10/03/2018 | Contractor scope complete | MARKB | MARKB | | H= | C | 5985316 |
WILLIAMS MECHANICAL | H= | P | 10/03/2018 | Transfer grills confirmed | MARKB | MARKB | | H= | P | 5983871 |
WILLIAMS MECHANICAL | H= | P | 10/02/2018 | FINAL PENDING - Provide Test And Balance report, Need to confirm interlocks with F-1/F-2 and confirm transfer grills to roasting room. | MARKB | MARKB | | H= | P | 5982362 |
WILLIAMS MECHANICAL | H= | P | 09/28/2018 | FINAL PENDING - Cut drywall back 2" around grease duct per manufacturer requirements and provide Test And Balance report. | MARKB | MARKB | | H= | P | 5980894 |
WILLIAMS MECHANICAL | HD | C | 09/28/2018 | GREASE DUCT INSPECTION - MANUFACTURED GREASE DUCT FOR COFFEE ROASTER INSTALLED PER PLAN AND MANUFACTURER INSTRUCTIONS. FLEX AND DIFFUSERS COMPLETE | MARKB | MARKB | | HD | C | 5980893 |
WILLIAMS MECHANICAL | HD | P | 09/17/2018 | Need a contractor to claim coffee roaster and call inspections when ready. ABOVE CEILING DUCT - SUPPLY/RETURN/EXHAUST MAINS/ BRANCHES INCLUDING TYPE 2 HOOD AND EXPOSED INSTALLED PER PLAN OK TO WRAP. No diffusers installed at this time. | MARKB | MARKB | | HD | P | 5967734 |
MARTINSON MECHANICAL, INC | HC | C | 09/05/2018 | RELEASE METER - TOTAL METER LOAD OF 455K | MARKB | MARKB | | HC | C | 5956190 |
MARTINSON MECHANICAL, INC | HI | C | 09/05/2018 | BY FINAL - Will need existing meter stub tagged with address and suite number. Coffee roaster will need to be a Listed appliance per code. 10 PSI PRESSURE TEST OK. PIPING PER PLAN. | MARKB | MARKB | | HI | C | 5956188 |
MARTINSON MECHANICAL, INC | P= | C | 10/03/2018 | Corrections made. | DANR | DANR | | P= | C | 5984667 |
MARTINSON MECHANICAL, INC | P= | P | 10/01/2018 | Backflow ice maker, vacuum breaker dishwasher, S-2 sinks need direct connect drain, strainers floor sinks, lav restroom 104 over 34" (at 34-1/2"), water heater pan drain in loft needs run to quad drain and water heater condensate line needs grade, rest ok. | DANR | DANR | | P= | P | 5981585 |
MARTINSON MECHANICAL, INC | PTO | C | 06/22/2018 | Test ok, aav at pony wall. Note: at final check water tie in - water heater.
| DANR | DANR | | PTO | C | 5883473 |
MARTINSON MECHANICAL, INC | PB | C | 05/10/2018 | Test ok. | DANR | DANR | | PB | C | 5841422 |
ROCKY MOUNTAIN ELECTRICAL SERVICES INC | XES | T | 09/28/2018 | PAID (REC#1548201) PLAN SPLICE FEE: $50 by: SHELBY for Electrical: As builts | SHELBY | SHELBY | | XES | T | 5979878 |