JR WILDER CONSTRUCTION LLC | B= | C | 08/03/2018 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 5923599 |
JR WILDER CONSTRUCTION LLC | B= | P | 06/25/2018 | drains corrected. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, COLORADO COMMERCIAL SYSTEMS Mechanical Final Inspection is not Completed yet, DENHAM ELECTRIC Electrical Final Inspection is not Completed yet, M.D. SERVICE PLUMBING Plumbing Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5884462 |
JR WILDER CONSTRUCTION LLC | B= | P | 06/25/2018 | need drain pan holes grouted from garage side remaining okay -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection HD= by HEALTHDEPT is not Completed yet, COLORADO COMMERCIAL SYSTEMS Mechanical Final Inspection is not Completed yet, DENHAM ELECTRIC Electrical Final Inspection is not Completed yet, M.D. SERVICE PLUMBING Plumbing Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 5884051 |
JR WILDER CONSTRUCTION LLC | BFR | C | 06/15/2018 | partial above ceiling inspection prior to dropped tile installation okay with completed required inspections / floor sink penetrations remaining | NATHAN | NATHAN | | BFR | C | 5876569 |
JR WILDER CONSTRUCTION LLC | BFR | P | 05/21/2018 | frame at walls okay with completed required inspections. | NATHAN | NATHAN | | BFR | P | 5850518 |
JR WILDER CONSTRUCTION LLC | BFR | P | 05/14/2018 | Inspection for back wall per detail #7 / Frame for fir wall OK / Still need to inspect all other walls for frame inspection, need to install 45% bracing for all other walls / Need to attach mechanical permit / Need all MEP's complete | NICK | NICK | | BFR | P | 5844266 |
DENHAM ELECTRIC | E= | C | 06/26/2018 | | CRAIG | CRAIG | | E= | C | 5885626 |
DENHAM ELECTRIC | E= | R | 06/21/2018 | 1) label panel 2) identify disconnect to water heater 3) panel fillers | GARYL | GARYL | | E= | R | 5881453 |
DENHAM ELECTRIC | EP | P | 06/21/2018 | panel okay, | GARYL | GARYL | | EP | P | 5881440 |
DENHAM ELECTRIC | ER | P | 06/15/2018 | ceilings okay | GARYL | GARYL | | ER | P | 5876099 |
DENHAM ELECTRIC | ER | P | 05/23/2018 | all walls | GARYL | GARYL | | ER | P | 5853717 |
DENHAM ELECTRIC | ER | P | 05/17/2018 | one wall only, west service wall | GARYL | GARYL | | ER | P | 5847996 |
COLORADO COMMERCIAL SYSTEMS, LLC | H= | C | 06/27/2018 | TAB REPORT / PLAN REVISION AND MISSING RA GRILLE ARE COMPLETE | JERRYF | JERRYF | | H= | C | 5886430 |
COLORADO COMMERCIAL SYSTEMS, LLC | H= | P | 06/19/2018 | NEED THE FOLLOWING - TAB REPORT - PLAN REVISION TO MATCH INSTALLED - AND PICTURE OF MISSING RETURN GRILLE ABOVE COOLER ATTACH PICTURES TO NEXT INSPECTION REQUEST NOTES: ALL OTHER GRILLES ARE COMPLETE | JERRYF | JERRYF | | H= | P | 5878425 |
COLORADO COMMERCIAL SYSTEMS, LLC | HD | C | 06/19/2018 | ABOVE CEILING RUN OUTS AND GRILLES ARE COMPLETE | JERRYF | JERRYF | | HD | C | 5878423 |
MD SERVICE PLUMBING, INC. | PTO | C | 06/26/2018 | Revisions made for grease waste | SHANEN | SHANEN | | PTO | C | 5885307 |
MD SERVICE PLUMBING, INC. | P= | C | 06/26/2018 | | SHANEN | SHANEN | | P= | C | 5885302 |
MD SERVICE PLUMBING, INC. | PTO | P | 06/21/2018 | Plans reflect 4" grease waste to 4" tie-in 3" installed, correct and re-test, 3" DWV to where plans show 4" OK | SHANEN | SHANEN | | PTO | P | 5881118 |
MD SERVICE PLUMBING, INC. | PTO | P | 06/15/2018 | Overhead domestic water OK | SHANEN | SHANEN | | PTO | P | 5875772 |
MD SERVICE PLUMBING, INC. | PTO | P | 05/25/2018 | In wall waterlines to island in engine area test OK | SHANEN | SHANEN | | PTO | P | 5855748 |
MD SERVICE PLUMBING, INC. | PTO | P | 05/23/2018 | Back of house in-wall DWV and water distribution test OK | SHANEN | SHANEN | | PTO | P | 5853111 |
MD SERVICE PLUMBING, INC. | PTO | P | 05/14/2018 | Revise plans or submit letter to reflect 2" drains in lieu of 3" drains at engine area, In wall water distribution and DWV test OK at engine area | SHANEN | SHANEN | | PTO | P | 5843478 |
MD SERVICE PLUMBING, INC. | XPS | T | 06/22/2018 | PAID (REC#1510216): PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 6-22-18 | TCRIPPEN | TCRIPPEN | | XPS | T | 5883183 |