MARTINES PALMEIRO CONSTRUCTION | B= | C | 09/30/2020 | All finals complete | GITA | GITA | | B= | C | 6725503 |
MARTINES PALMEIRO CONSTRUCTION | B= | T | 06/26/2020 | PAID (REC#1691497): For TCO. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), LDI MECHANICAL, INC. Mechanical Final Inspection is not Completed yet, TEXAS FIREPLACE EXPRESS, LLC DBA FIREPLA Mechanical Final Inspection is not Completed yet. | RITA | RITA | | B= | T | 6618617 |
MARTINES PALMEIRO CONSTRUCTION | B= | P | 06/26/2020 | Temp CO: extension per Matt M, pending fianl inspections ( Expires: 7/26/2020 12:00:00 AM) | RITA | RITA | | B= | P | 6618616 |
MARTINES PALMEIRO CONSTRUCTION | B= | P | 06/09/2020 | Temp CO: extension pending required final inspections ( Expires: 7/9/2020 12:00:00 AM) | LONNYS | LONNYS | | B= | P | 6598057 |
MARTINES PALMEIRO CONSTRUCTION | B= | T | 06/09/2020 | PAID (REC#1687235): trip fee assessed for TCO extension. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), DIE HARD, INC Electrical Final Inspection is not Completed yet, LDI MECHANICAL, INC. Mechanical Final Inspection is not Completed yet, TEXAS FIREPLACE EXPRESS, LLC DBA FIREPLA Mechanical Final Inspection is not Completed yet. | LONNYS | LONNYS | | B= | T | 6598056 |
MARTINES PALMEIRO CONSTRUCTION | B= | T | 04/30/2020 | PAID (REC#1677122): Temp CO: Extension Pending all required finals ( Expires: 5/30/2020 12:00:00 AM)/ Trip fee assessed for TCO fee collection | MATTHEWM | MATTHEWM | | B= | T | 6556377 |
MARTINES PALMEIRO CONSTRUCTION | B= | P | 04/02/2020 | Temp CO: All finals are done or pending ( Expires: 5/2/2020 12:00:00 AM) | GITA | GITA | | B= | P | 6530162 |
MARTINES PALMEIRO CONSTRUCTION | B= | P | 03/02/2020 | Temp CO: Per Matt M pending finals on fire, zoning, mechanical and electrical ( Expires: 4/1/2020 12:00:00 AM) | RITA | RITA | | B= | P | 6497693 |
MARTINES PALMEIRO CONSTRUCTION | B= | P | 02/03/2020 | Temp CO: Per MM ( Expires: 3/4/2020 12:00:00 AM) | NELIDA | NELIDA | | B= | P | 6472816 |
MARTINES PALMEIRO CONSTRUCTION | B= | P | 01/02/2020 | Temp CO: Per BW ( Expires: 2/1/2020 12:00:00 AM) | NELIDA | NELIDA | | B= | P | 6441966 |
MARTINES PALMEIRO CONSTRUCTION | B= | P | 12/03/2019 | Temp CO: Per BW ( Expires: 1/2/2020 12:00:00 AM) | JANE | JANE | | B= | P | 6414060 |
MARTINES PALMEIRO CONSTRUCTION | B= | P | 11/22/2019 | Complete pending all other finals - All outstanding items corrected -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), DIE HARD, INC Electrical Final Inspection is not Completed yet, FRONT RANGE AQUATECH Mechanical Final Inspection is not Completed yet, HORIZON, LLC Mechanical Final Inspection is not Completed yet, HORIZON, LLC Plumbing Final Inspection is not Completed yet, LDI MECHANICAL, INC. Mechanical Final Inspection is not Completed yet, TEXAS FIREPLACE EXPRESS, LLC DBA FIREPLA Mechanical Final Inspection is not Completed yet. | TIMOTHYS | TIMOTHYS | | B= | P | 6408464 |
MARTINES PALMEIRO CONSTRUCTION | B= | R | 11/15/2019 | Need to complete fire final / Glass door to managers office with double cylinder needs a sign that says "THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED" / Office, Electrical room, Golf cart room, Gang restroom door locks need to be "Sinlge action" requiring no more than one action to open - No tight grasping, pinching, or turning of the wrist will be allowed / Seal holes in janitors closet ceiling / Cover open electrical box by yoga room roll up door / Pool on separate permit, not inspected at this time. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), DIE HARD, INC Electrical Final Inspection is not Completed yet, FRONT RANGE AQUATECH Mechanical Final Inspection is not Completed yet, HORIZON, LLC Mechanical Final Inspection is not Completed yet, HORIZON, LLC Plumbing Final Inspection is not Completed yet, LDI MECHANICAL, INC. Mechanical Final Inspection is not Completed yet, TEXAS FIREPLACE EXPRESS, LLC DBA FIREPLA Mechanical Final Inspection is not Completed yet. | TIMOTHYS | TIMOTHYS | | B= | R | 6400871 |
MARTINES PALMEIRO CONSTRUCTION | BIN | C | 11/15/2019 | Received insulation installers cert for blow in and spray foam - Received ER report for spray foam | TIMOTHYS | TIMOTHYS | | BIN | C | 6400848 |
MARTINES PALMEIRO CONSTRUCTION | BFN | C | 11/15/2019 | Received revised open hole | TIMOTHYS | TIMOTHYS | | BFN | C | 6400847 |
MARTINES PALMEIRO CONSTRUCTION | BSP | P | 11/08/2019 | ER Report for spray applied foam insulation on file | DANE | DANE | | BSP | P | 6392674 |
MARTINES PALMEIRO CONSTRUCTION | BSP | P | 10/29/2019 | Courtesy pre-final walk with contractor | TIMOTHYS | TIMOTHYS | | BSP | P | 6382830 |
MARTINES PALMEIRO CONSTRUCTION | BIN | P | 06/28/2019 | Spray foam installed in ceiling of atrium at common area - need ES/UES report to determine if thermal/ignition barrier required. Coverage of spray foam to be completed per plan by 3/4" T&G boards. / Training with Tony. | CHUCK | CHUCK | | BIN | P | 6247767 |
MARTINES PALMEIRO CONSTRUCTION | BSP | P | 05/30/2019 | WP3514 wall assembly in pool equipment room OK. | CHUCK | CHUCK | | BSP | P | 6214321 |
MARTINES PALMEIRO CONSTRUCTION | BSP | R | 05/28/2019 | Screw inspection for WP3514 rated wall to pool equipment room - need to seal opening through wall and wall in cart storage room to continue to deck - rest of assembly wall OK. | CHUCK | CHUCK | | BSP | R | 6211319 |
MARTINES PALMEIRO CONSTRUCTION | BIN | P | 05/28/2019 | Spray foam insulation installed in upper roof at social/entry way - need installers cert prior to final inspection. | CHUCK | CHUCK | | BIN | P | 6211315 |
MARTINES PALMEIRO CONSTRUCTION | BSP | P | 05/28/2019 | Connection inspection for plates to join 2-2x4 plates in the 2x8 fitness room walls - engineer's paperwork received. | CHUCK | CHUCK | | BSP | P | 6211313 |
MARTINES PALMEIRO CONSTRUCTION | BSP | R | 05/23/2019 | Rated ice maker box installed on pool equipment/breakroom rated wall OK / Need stamped paperwork for shear wall 2-2x4 plate connections - paperwork to be specific to spacing of connecting product used. | CHUCK | CHUCK | | BSP | R | 6208399 |
MARTINES PALMEIRO CONSTRUCTION | BIN | P | 05/08/2019 | Exterior blown in and rim spray foam insulation OK - need insulation installers cert for foam and blown in insulation prior to final inspection / Fire blocking OK - need to complete BFR inspection. | CHUCK | CHUCK | | BIN | P | 6192299 |
MARTINES PALMEIRO CONSTRUCTION | BFR | P | 05/01/2019 | Need detail for W26 wall/S1 interior shear wall at Fitness Rm 180 - plan calls for 2x6 wall. 2x8 wall installed on 2-2x4 sill plates strapped together with HDU hold downs attached to only one plate. / Fire block all dead spaces, drop ceilings and penetrations / Ice maker installed in WP3514 fire barrier wall / Remaining framing OK. | CHUCK | CHUCK | | BFR | P | 6183974 |
MARTINES PALMEIRO CONSTRUCTION | BFD | C | 04/25/2019 | Drain not required per open hole | JEREMYA | JEREMYA | | BFD | C | 6177416 |
MARTINES PALMEIRO CONSTRUCTION | BFN | P | 04/25/2019 | Engineering on file // Pending completion of open hole | JEREMYA | JEREMYA | | BFN | P | 6177413 |
MARTINES PALMEIRO CONSTRUCTION | BFT | P | 04/25/2019 | Reinforcing steel observation on file // Open hole letter specifically states they were not on-site to verify the open excavation. Need to address this prior to completion. | JEREMYA | JEREMYA | | BFT | P | 6177412 |
MARTINES PALMEIRO CONSTRUCTION | BFR | R | 04/15/2019 | Unable to determine EW06 wall stud details in plan / W26 wall type listed for WP3514 rated assembly on G-501 and shear on S-101CH - need to specify assembly / Complete fire stopping/blocking / Need to complete BFT/BFN/BFI inspections. | CHUCK | CHUCK | | BFR | R | 6165557 |
MARTINES PALMEIRO CONSTRUCTION | BSP | P | 12/26/2018 | exterior shear OK | DANE | DANE | | BSP | P | 6063007 |
DIE HARD, INC | E= | C | 06/23/2020 | Awnings front and back complete - Ok | BRETC | BRETC | | E= | C | 6614416 |
DIE HARD, INC | ER | P | 05/28/2020 | front and back awnings ok | RANDY | RANDY | | ER | P | 6586519 |
DIE HARD, INC | ES | C | 03/10/2020 | Commercial Service: 600 amp ----no action needed | RANDY | RANDY | | ES | C | 6505552 |
DIE HARD, INC | E= | P | 03/06/2020 | light pole bonding, box conduits top and bottom of pool panel, clamps and seal at deck boxes | BRET | BRET | | E= | P | 6502755 |
DIE HARD, INC | EP | C | 03/06/2020 | panels ok | BRET | BRET | | EP | C | 6502754 |
DIE HARD, INC | EP | P | 02/19/2020 | neutrals nat identified with circuit number, missing handle ties, fault current label ,DATE CALCULATED AND BY WHOM, section two needs correct breaker number on dead front | BRET | BRET | | EP | P | 6485797 |
DIE HARD, INC | E= | P | 01/06/2020 | Bonding ok in pool equip. room / Conduits ok to enclose above and below panel / EPO ok for pool / | ROB | ROB | | E= | P | 6444517 |
DIE HARD, INC | E= | P | 12/23/2019 | pool equipment room ok | RANDY | RANDY | | E= | P | 6435413 |
DIE HARD, INC | E= | P | 11/06/2019 | interior only except pool equipment room, install gfci breaker for water cooler and disposal, breaker locks for heaters lobby and maintenance , nm cables hanging in l.v closet. | BRET | BRET | | E= | P | 6389829 |
COLORADO SECURITY, LLC | E= | C | 10/21/2019 | FIRE ALARM INSPECTION: see notes | RANDY | RANDY | | E= | C | 6374892 |
COLORADO SECURITY, LLC | ER | C | 10/21/2019 | FIRE ALARM INSPECTION: FA rough complete | RANDY | RANDY | | ER | C | 6374890 |
COLORADO SECURITY, LLC | E= | C | 10/21/2019 | FIRE ALARM INSPECTION: FA rough complete | RANDY | RANDY | | E= | C | 6374891 |
DIE HARD, INC | EUG | R | 10/09/2019 | not ready only 2 handrail cups made | BRET | BRET | | EUG | R | 6362793 |
DIE HARD, INC | ES | P | 10/01/2019 | Commercial Service: 600 amp service ok to energize made to main breaker only | BRET | BRET | | ES | P | 6353286 |
DIE HARD, INC | ES | R | 09/30/2019 | not ready | BRET | BRET | | ES | R | 6351891 |
DIE HARD, INC | EUG | P | 08/23/2019 | car charger conduit ok | BRET | BRET | | EUG | P | 6311824 |
DIE HARD, INC | EUG | P | 08/19/2019 | 3 light pole locations closest to road | BRET | BRET | | EUG | P | 6305011 |
DIE HARD, INC | EUG | P | 08/01/2019 | conduits from building to four lights, one sign and fire pit west side of pool | BRET | BRET | | EUG | P | 6284752 |
DIE HARD, INC | ER | P | 05/10/2019 | 3 pole bases only from entry east | BRET | BRET | | ER | P | 6194664 |
DIE HARD, INC | ER | P | 04/12/2019 | walls and lid, pre rock pool equipment room, exterior soffit not ready | BRET | BRET | | ER | P | 6164246 |
DIE HARD, INC | ER | P | 03/01/2019 | pool shell bond ok | BRET | BRET | | ER | P | 6121883 |
DIE HARD, INC | ESL | P | 10/04/2018 | clubhouse floor boxes ok | RANDY | RANDY | | ESL | P | 5985542 |
DIE HARD, INC | ESL | P | 09/11/2018 | ok at electric room, need csu approval of secondary under slab. | BRET | BRET | | ESL | P | 5960829 |
DIE HARD, INC | ESL | P | 07/12/2018 | floor boxes and island stub | BRET | BRET | | ESL | P | 5900334 |
FIREPLACE WAREHOUSE | H= | C | 09/01/2020 | TIME CLOCK INSTALLED. FIREPLACE FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6692698 |
LDI MECHANICAL, INC. | H= | C | 07/16/2020 | REVISED TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. MECHANICAL FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6638967 |
FIREPLACE WAREHOUSE | H= | L | 07/15/2020 | CANCELLED AT CALL AHEAD BY KEVIN WITH MPC. TIMER NOT COMPLETED YET. | DUSTINS | DUSTINS | | H= | L | 6638316 |
FIREPLACE WAREHOUSE | H= | P | 07/14/2020 | SCOPE OF WORK CORRECTED. STILL MISSING TIME CLOCK FOR FIREPLACE PER PLANS. SPOKE WITH KEVIN WITH MPC AND HE STATED HE WILL DISCUSS WITH ENGINEER TO SEE IF TIME CLOCK CAN BE DELETED. | DUSTINS | DUSTINS | | H= | P | 6636776 |
FIREPLACE WAREHOUSE | H= | P | 03/23/2020 | FIREPLACE FINAL PENDING: NEED SCOPE OF WORK ADJUSTED TO CLAIM TWO FIREPLACES. PER PLAN PAGE M-103CH (BDA 488) NOTE 11 STATES TIME CLOCK NEEDS TO BE INSTALLED FOR FIREPLACE. | DUSTINS | DUSTINS | | H= | P | 6518513 |
FRONT RANGE AQUATECH | H= | C | 03/20/2020 | POOL AND SPA BOILER FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6517527 |
FRONT RANGE AQUATECH | H= | L | 03/19/2020 | NEED INSTALLATION INSTRUCTIONS ON SITE FOR INSPECTION AS PREVIOUSLY NOTED. | DUSTINS | DUSTINS | | H= | L | 6515864 |
LDI MECHANICAL, INC. | H= | P | 03/04/2020 | MECHANICAL FINAL PENDING: TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. TEST AND BALANCE REPORT HAS MULTIPLE READINGS FOR RTU-3 AND RTU-4 THAT ARE OUTSIDE +/- 10%. DESIGN READINGS ON TAB DIFFER FROM PLAN MAKING THE FINAL READINGS OUTSIDE +/- 10%. NEED REVISED TEST AND BALANCE REPORT OR ENGINEER TO STAMP AND APPROVE TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | H= | P | 6500110 |
LDI MECHANICAL, INC. | HV | C | 03/04/2020 | RECEIVED LETTER FROM METAL FAB APPROVING VENT TEE WITH CONDENSATE DRAIN LINE TO BE IN VERTICAL PIPING, SEE IMAGES. ALL POOL/SPA BOILER VENTING OK. | DUSTINS | DUSTINS | | HV | C | 6500103 |
HORIZON LLC OF SOUTH CAROLINA | H= | C | 02/27/2020 | GAS FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6495016 |
LDI MECHANICAL, INC. | HSP | P | 02/27/2020 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. TEST AND BALANCE REPORT HAS MULTIPLE READINGS FOR RTU-3 AND RTU-4 THAT ARE OUTSIDE +/- 10%. DESIGN READINGS ON TAB DIFFER FROM PLAN MAKING THE FINAL READINGS OUTSIDE +/- 10%. NEED REVISED TET AND BALANCE REPORT OR ENGINEER TO STAMP AND APPROVE TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | HSP | P | 6493996 |
FRONT RANGE AQUATECH | HSP | P | 01/13/2020 | PROVIDE INSTALLATION INSTRUCTIONS FOR POOL AND SPA BOILERS AT TIME OF INSPECTION. | DUSTINS | DUSTINS | | HSP | P | 6451327 |
LDI MECHANICAL, INC. | H= | P | 01/13/2020 | MECHANICAL FINAL PENDING: COMPLETE HV INSPECTION FOR POOL BOILERS, PROVIDE TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | H= | P | 6451324 |
LDI MECHANICAL, INC. | HV | P | 01/13/2020 | PER METAL-FAB VENTING INSTALLATION INSTRUCTIONS FOR POOL BOILER PAGE 4, FIGURE 4 THE CONDENSATE DRAIN LINE TEE MUST BE IN THE HORIZONTAL SECTION OF VENT PIPING. SEAL AROUND VENT PIPING AT PLATE TO EXTERIOR WITH HIGH TEMP SEALANT PER PAGE 5 NUMBER 9 AND FIGURE 7. | DUSTINS | DUSTINS | | HV | P | 6451321 |
HORIZON LLC OF SOUTH CAROLINA | H= | P | 01/02/2020 | GAS FINAL OK PENDING: NEED VENT LIMITERS INSTALLED IN REGULATORS FOR BOILERS. GAS REGULATOR FOR WATER HEATER NEEDS TO BE INSTALLED IN THE HORIZONTAL UPRIGHT POSITION PER INSTALLATION INSTRUCTIONS. NEED MEDIUM PRESSURE STICKERS INSTALLED ON ALL MEDIUM PRESSURE GAS PIPING | DUSTINS | DUSTINS | | H= | P | 6441645 |
HORIZON LLC OF SOUTH CAROLINA | HO | C | 01/02/2020 | ALL OUTSIDE GAS PIPING COMPLETE. | DUSTINS | DUSTINS | | HO | C | 6441630 |
LDI MECHANICAL, INC. | H= | P | 11/04/2019 | STILL NEED CONTRACTOR INSTALLING POOL AND SPA BOILERS TO ATTACH TO PERMIT. MECHANICAL FINAL PENDING: NEED TO SEE BOILER VENTS WHEN INSTALLED. PLUMBING VENT ON ROOF NEEDS TO BE 10' AWAY OR 3' ABOVE RTU ECONOMIZER. PROVIDE TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | H= | P | 6387474 |
HORIZON LLC OF SOUTH CAROLINA | HSP | P | 10/31/2019 | NEED TO INSPECT WATER HEATER VENT WITH HV INSPECTION. RTU GAS REGULATOR NEEDS TO BE 3' AWAY FROM FIREPLACE VENT TERMINATION ON ROOF. | DUSTINS | DUSTINS | | HSP | P | 6385082 |
LDI MECHANICAL, INC. | H= | P | 10/31/2019 | STILL NEED CONTRACTOR INSTALLING POOL AND SPA BOILERS TO ATTACH TO PERMIT. MECHANICAL FINAL PENDING: NEED TO SEE BOILER VENTS WHEN INSTALLED. LABEL ALL EQUIPMENT ON ROOF. INSTALL CONDENSATE TRAPS ON RTU'S. PLUMBING VENT ON ROOF NEEDS TO BE 10' AWAY OR 3' ABOVE RTU ECONOMIZER. PROVIDE TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | H= | P | 6385075 |
FIREPLACE WAREHOUSE | HSP | P | 10/31/2019 | PER PLAN PAGE M-103CH (BDA 488) THERE IS AN OUTDOOR FIREPLACE. IF THIS CONTRACTOR IS THE CONTRACTOR INSTALLING THE FIREPLACE, WILL NEED FIREPLACE INSTALLED AND INSPECTED AND SCOPE OF WORK ADJUSTED TO CLAIM OUTSIDE FIREPLACE. | DUSTINS | DUSTINS | | HSP | P | 6384196 |
FIREPLACE WAREHOUSE | H= | P | 10/30/2019 | STILL NEED CONTRACTOR INSTALLING POOL AND SPA BOILERS AND VENTS TO ATTACH TO PERMIT. // UNABLE TO LOAD PLANS IN THE FIELD. FURTHER RESEARCH REQUIRED ON CONTRACTORS SCOPE OF WORK REGARDING OUTSIDE FIREPLACE. WILL UPDATE AFTER FURTHER REVIEW. | DUSTINS | DUSTINS | | H= | P | 6383953 |
LDI MECHANICAL, INC. | H= | L | 09/09/2019 | CANCELLED AT CALL AHEAD BY JOSE WITH LDI. WRONG INSPECTION WAS CALLED. | DUSTINS | DUSTINS | | H= | L | 6328906 |
HORIZON LLC OF SOUTH CAROLINA | HO | P | 08/05/2019 | 10 LB TEST OK ON ALL OUTSIDE GAS PIPING. PIPING PER PLAN EXCEPT 3/4" HAS BEEN INCREASED TO 1". NEED TO SEE THE GAS LINE TO THE FIRE PIT COMPLETED AND SLEEVED IF COMING THROUGH CONCRETE. CHECK CONNECTIONS TO EQUIPMENT AT FINAL. | DUSTINS | DUSTINS | | HO | P | 6288708 |
HORIZON LLC OF SOUTH CAROLINA | HC | C | 07/25/2019 | OK TO SET 2 LB METER AT THIS ADDRESS. | DUSTINS | DUSTINS | | HC | C | 6277357 |
HORIZON LLC OF SOUTH CAROLINA | HI | C | 07/25/2019 | FIREPLACE INSTALLED, INSIDE GAS COMPLETE. CHECK MEDIUM PRESSURE STICKERS AND REGULATORS AT FINAL. CONTRACTOR HAD QUESTIONS ABOUT OUTSIDE GAS LINES, WENT THROUGH PLANS AND DISCUSSED WHAT WAS NEEDED FOR INSPECTION. | DUSTINS | DUSTINS | | HI | C | 6277349 |
FIREPLACE WAREHOUSE | HV | C | 05/28/2019 | FIREPLACE FRAME AND VENT OK. AT FINAL NEED TO SEE NON COMBUSTIBLE FINISHING MATERIAL AROUND FIREPLACE AND RE-VERIFY CLEARANCES FOR TERMINATION ON ROOF. | DUSTINS | DUSTINS | | HV | C | 6212093 |
LDI MECHANICAL, INC. | HD | P | 05/13/2019 | CONTRACTOR CALLED FOR WRONG INSPECTION. THIS WAS FOR: 1- LINE SET ABOVE CEILING AND IN WALL OK IN MAIL KIOSK. 4- LINE SETS ABOVE CEILING AND IN WALL OK AND EXHAUST FAN AND DUCT ABOVE CEILING OK IN AMENITY BUILDING. 4- LINE SETS ABOVE CEILING AND IN WALL OK AND EXHAUST FAN AND DUCT ABOVE CEILING OK IN PARCEL BUILDING. NEED TO REVIEW PLANS FOR ALL THREE BUILDINGS AND HAVE MECHANICAL CONTRACTOR TO ATTACH TO ALL THREE PERMITS. WILL TRANSFER NOTES AFTER CONTRACTOR ATTACHED. | DUSTINS | DUSTINS | | HD | P | 6197209 |
FIREPLACE WAREHOUSE | HV | P | 04/19/2019 | FIREPLACE VENT OK. NEED TO SEE FRAMING FINISHED TO CHECK FOR CLEARANCES TO FIREPLACE AND VENT. AT FINAL NEED TO SEE NON COMBUSTIBLE FINISHING MATERIAL AROUND FIREPLACE AND RE-VERIFY CLEARANCES FOR TERMINATION ON ROOF. | DUSTINS | DUSTINS | | HV | P | 6171315 |
LDI MECHANICAL, INC. | HD | P | 04/12/2019 | ALL SUPPLY/RETURN DUCT OK EXCEPT RTU-4 EXPOSED DUCT IN CH100 AREA NEEDS INSPECTED. ALL EXHAUST DUCTS OK. NO FLEX AND DIFFUSERS YET. | DUSTINS | DUSTINS | | HD | P | 6163739 |
FIREPLACE WAREHOUSE | HSP | P | 04/12/2019 | ON SITE CONSULTATION FOR FIREPLACE VENT TERMINATION. | DUSTINS | DUSTINS | | HSP | P | 6163728 |
FIREPLACE WAREHOUSE | HSP | L | 04/10/2019 | JOB SITE CLOSING FOR INCOMING WEATHER. PLEASE RESCHEDULE WHEN READY. | DUSTINS | DUSTINS | | HSP | L | 6161585 |
LDI MECHANICAL, INC. | HD | L | 04/10/2019 | JOB SITE CLOSING FOR INCOMING WEATHER. PLEASE RESCHEDULE WHEN READY. | DUSTINS | DUSTINS | | HD | L | 6161583 |
HORIZON LLC OF SOUTH CAROLINA | HI | P | 02/05/2019 | NEED FIREPLACE CONTRACTOR ATTACHED TO PERMIT. NEED CONTRACTOR INSTALLING POOL AND SPA BOILERS AND VENTS TO ATTACH TO PERMIT. FIREPLACE NEEDS TO BE INSTALLED BEFORE COMPLETING GAS INSPECTION. 10 LB TEST OK. PIPING PER PLAN SPLICE (BDA 489) NEED TO SEE MEDIUM PRESSURE STICKERS AND REGULATORS INSTALLED AT FINAL. CHECK CONNECTIONS TO EQUIPMENT. | DUSTINS | DUSTINS | | HI | P | 6098656 |
LDI MECHANICAL, INC. | HD | P | 02/05/2019 | NEED FIREPLACE CONTRACTOR ATTACHED TO PERMIT. NEED CONTRACTOR INSTALLING POOL AND SPA BOILERS AND VENTS TO ATTACH TO PERMIT. RTU-1 RETURN AIR DUCT OK, NO SUPPLY YET. RTU-2 RETURN AIR DUCT OK, SUPPLY AIR DUCT OK EXCEPT MISSING 2 SUPPLY IN FITNESS HALL. RTU-3 RETURN AIR DUCT OK, SUPPLY DUCT OK EXCEPT NOT COMPLETE IN OFFICE CH40. RTU-4 RETURN AIR DUCT OK, SUPPLY AIR OK ONLY IN BILLIARDS CH110. OK TO WRAP WHAT IS INSTALLED. EF-1 EXHAUST DUCTS OK EXCEPT MISSING ONE DUCT FOR MENS RESTROOM. | DUSTINS | DUSTINS | | HD | P | 6098653 |
HORIZON LLC OF SOUTH CAROLINA | P= | C | 12/26/2019 | | TAYLOR | TAYLOR | | P= | C | 6436854 |
HORIZON LLC OF SOUTH CAROLINA | P= | P | 12/03/2019 | install hub drain for pool, rest ok. | TAYLOR | TAYLOR | | P= | P | 6414122 |
HORIZON LLC OF SOUTH CAROLINA | P= | P | 11/13/2019 | install backflow for pool and trap guards at mech room, check valve needs be installed on the proper side at water heater. | TAYLOR | TAYLOR | | P= | P | 6397268 |
HORIZON LLC OF SOUTH CAROLINA | P= | P | 11/12/2019 | no hot water, re- inspect all. | TAYLOR | TAYLOR | | P= | P | 6395957 |
HORIZON LLC OF SOUTH CAROLINA | PTO | C | 04/12/2019 | corrections made. NOTE: engineers letter addressing freeze pro received and sent to scanning | JOHNS | JOHNS | | PTO | C | 6163772 |
HORIZON LLC OF SOUTH CAROLINA | PTO | P | 03/12/2019 | corrections made @ water closets **STILL NEED to address freeze pro @ out side water lines | JOHNS | JOHNS | | PTO | P | 6131104 |
HORIZON LLC OF SOUTH CAROLINA | PRD | C | 02/26/2019 | ok for prd and ord | JOHNS | JOHNS | | PRD | C | 6117532 |
HORIZON LLC OF SOUTH CAROLINA | PTO | P | 02/26/2019 | *NEED to add roof drains to scope of work, rest ok for dwv and water corrections, MINUS freeze pro @ outside water lines, and secure all flanges | JOHNS | JOHNS | | PTO | P | 6117531 |
HORIZON LLC OF SOUTH CAROLINA | PTO | P | 02/22/2019 | **NEED engineer letter allowing cpvc in lieu of copper and pvc in lieu of cast, rest ok for test / design @ waters only, MINUS shut offs @ all hose bibs (x3), hammer aerestor @ urinals. NOTE: water htrs on mech scope, VTR, aav @ ep lounge sink, hammer aerestor in wall @ right urinal, verify access panel @ hose bibs (x3), unit shut off @ women's bath hallway @ back left side, check pool bfp, ENGINEERS letter received and sent to scanning
**NEED to consult w/ senior about freeze protection on outside wall water lines **STILL need dwv and roof drains inspected | JOHNS | JOHNS | | PTO | P | 6114873 |
HORIZON LLC OF SOUTH CAROLINA | PB | C | 08/01/2018 | | TAYLOR | TAYLOR | | PB | C | 5920231 |
HORIZON LLC OF SOUTH CAROLINA | PB | P | 07/02/2018 | all ok, minus water service. | TAYLOR | TAYLOR | | PB | P | 5890814 |
HORIZON LLC OF SOUTH CAROLINA | PRD | P | 07/02/2018 | underground roof drains ok. | TAYLOR | TAYLOR | | PRD | P | 5890813 |
HORIZON LLC OF SOUTH CAROLINA | PB | P | 06/29/2018 | need 3 inch drain for service sink. | TAYLOR | TAYLOR | | PB | P | 5889541 |
MARTINES PALMEIRO CONSTRUCTION | XBS | T | 02/24/2020 | PAID (REC#1667003): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revise details | MICHAELA | MICHAELA | | XBS | T | 6490828 |
COLORADO SECURITY, LLC | XES | T | 02/24/2020 | PAID (REC#1714212): PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised lighting for awnings. | BERTHA | BERTHA | | XES | T | 6490780 |
COLORADO SECURITY, LLC | XES | P | 12/11/2019 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: Add exit light | SHELBY | SHELBY | | XES | P | 6423615 |
MARTINES PALMEIRO CONSTRUCTION | XBS | T | 11/19/2019 | PAID (REC#1645798): PLAN SPLICE FEE: $50 by: DANM for Construction: Converting some exits to "Pool Access" only | DANM | DANM | | XBS | T | 6403731 |
MARTINES PALMEIRO CONSTRUCTION | XBS | T | 08/01/2019 | PAID (REC#1623676): PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Revised wall detail. | SHELLEY | SHELLEY | | XBS | T | 6284518 |
MARTINES PALMEIRO CONSTRUCTION | XBS | T | 06/24/2019 | PAID (REC#1609330): PLAN SPLICE FEE: $50 by: SHELLEY for Construction: Glulam exposure on section | SHELLEY | SHELLEY | | XBS | T | 6241895 |
MARTINES PALMEIRO CONSTRUCTION | XBS | T | 05/07/2019 | PAID (REC#1596337): PLAN SPLICE FEE: $50 by: DANM for Construction: Updated Code Plan sheet (G-101CH1) showing revisions to Pool Equipment/Mechanical and added Electrical Room (Note: this revisions had been approved previously but Code Plan was never updated); added fire rating details | DANM | DANM | | XBS | T | 6190368 |
DIE HARD, INC | XES | T | 04/25/2019 | PAID (REC#1593381): PLAN SPLICE FEE: $50 by: BERTHA for Electrical: RFI 1254 ONLY - revised lighting - clubhouse. | BERTHA | BERTHA | | XES | T | 6177585 |
MARTINES PALMEIRO CONSTRUCTION | XBS | P | 04/24/2019 | PLAN SPLICE: (No Fee) by: DANM for Construction: Minor reflected ceiling plan revisions | DANM | DANM | | XBS | P | 6176828 |
MARTINES PALMEIRO CONSTRUCTION | XBS | P | 11/21/2018 | PLAN SPLICE: (No Fee) by: DANM for Construction: RedBuilt joists are industry accepted engineered wood products that do not require unique engineered designs such as pre-manufactured trusses - Splice is for Reference Only | DANM | DANM | | XBS | P | 6031921 |
LDI MECHANICAL, INC. | XMS | T | 11/02/2018 | PAID (REC#1555208): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Layout and gas revisions | JUSTINC | JUSTINC | | XMS | T | 6014960 |
DIE HARD, INC | XES | T | 10/22/2018 | PAID (REC#1555209): PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Revised transformer location/fault current | SHELBY | SHELBY | | XES | T | 6002139 |
MARTINES PALMEIRO CONSTRUCTION | XBS | T | 10/19/2018 | PAID (REC#1555210): PLAN SPLICE FEE: $50 by: DANM for Construction: Revisions throughout architectural sheets | DANM | DANM | | XBS | T | 6000507 |
MARTINES PALMEIRO CONSTRUCTION | XBS | T | 08/21/2018 | PAID (REC#1530468): PLAN SPLICE FEE: $50 by: DANM for Construction: Minor foundation revisions | DANM | DANM | | XBS | T | 5940220 |
DIE HARD, INC | XES | P | 08/09/2018 | PLAN SPLICE: (No Fee) by: SHELBY for Electrical: Add pool panel and update pool mechanical room detail | SHELBY | SHELBY | | XES | P | 5928619 |
MARTINES PALMEIRO CONSTRUCTION | XMS | P | 08/07/2018 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised pool equipment room | JUSTINC | JUSTINC | | XMS | P | 5926126 |
HORIZON LLC OF SOUTH CAROLINA | XPS | T | 08/07/2018 | PAID (REC#1525820): PLAN SPLICE FEE: $50 by: TCRIPPEN for Plumbing: plumbing splice 8-7-18 | TCRIPPEN | TCRIPPEN | | XPS | T | 5925557 |
MARTINES PALMEIRO CONSTRUCTION | XBS | T | 08/06/2018 | PAID (REC#1525821): PLAN SPLICE FEE: $50 by: DANM for Construction: Addition of an electrical room causing minor building footprint change - revised structural and architectural sheets | DANM | DANM | | XBS | T | 5925408 |