MAHLER GC GENERAL CONTRACTING COMPANY | B= | C | 01/17/2019 | All other required Final inspections are complete. (This is a computer generated result) | DANE | DANE | | B= | C | 6080706 |
NIELSEN MECHANICAL CONTRACTORS, INC. | BSP | P | 11/16/2018 | ADDITIONAL PLAN REVIEW TIME: From: DALEH delta 2 | DALEH | DALEH | | BSP | P | 6027994 |
MAHLER GC GENERAL CONTRACTING COMPANY | B= | P | 09/27/2018 | all items completed / final OK pending other finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet, PRESTIGE MECHANICAL CONTRACTORS,INC Plumbing Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5978754 |
MAHLER GC GENERAL CONTRACTING COMPANY | B= | P | 07/12/2018 | need to install all doors and door hardware / need to install all new grab rails in both existing bathrooms / need to install bathroom signs at both bathrooms / new stairs on south side of exterior are on separate permit / training with inspector Dakota B -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), INTERMOUNTAIN POWER SERVICES INC Electrical Final Inspection is not Completed yet, NIELSEN MECHANICAL CONTRACTORS, INC. Mechanical Final Inspection is not Completed yet, PRESTIGE MECHANICAL CONTRACTORS,INC Plumbing Final Inspection is not Completed yet. | DANE | DANE | | B= | P | 5900526 |
MAHLER GC GENERAL CONTRACTING COMPANY | BSP | P | 07/12/2018 | Training with Dane S. on building finals on commercial projects -- Reviewed accessibility as well as life safety requirements | DAKOTAB | DAKOTAB | | BSP | P | 5900492 |
MAHLER GC GENERAL CONTRACTING COMPANY | BFR | P | 06/01/2018 | new interior framing OK pending other roughs / discussed accessible elements | DANE | DANE | | BFR | P | 5861588 |
INTERMOUNTAIN POWER SERVICES INC | E= | C | 09/25/2018 | | BRET | BRET | | E= | C | 5975524 |
INTERMOUNTAIN POWER SERVICES INC | E= | P | 07/11/2018 | Need hospital grade/GFCI recpts for chairs--Need to check lobby recpts./circuit off---Fireplace needs dedicated ckt. or plan splice--Missing recpt in sterilization room cabinet / | ROB | ROB | | E= | P | 5899927 |
INTERMOUNTAIN POWER SERVICES INC | ER | P | 07/09/2018 | all ceilings EXCEPT small area marked on prints for air handler, check working clearance when installed | GARYL | GARYL | | ER | P | 5896138 |
INTERMOUNTAIN POWER SERVICES INC | ER | P | 07/06/2018 | Rough ok for recess can and exit fixture in entry / | ROB | ROB | | ER | P | 5895599 |
INTERMOUNTAIN POWER SERVICES INC | ER | P | 05/31/2018 | Electrical wall rough ok, / HCF in patient areas and pipe stubbed up at switches / Discussed accessibility requirements with contractor / | ROB | ROB | | ER | P | 5861214 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | C | 11/20/2018 | MECHANICAL FINAL OK. | DUSTINS | DUSTINS | | H= | C | 6031410 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 11/20/2018 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. PER PLAN SPLICE FPB-1 IS ONLY 580 CFM AND READINGS ARE WITHIN 10% | DUSTINS | DUSTINS | | H= | P | 6030337 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 07/27/2018 | NEED REVISED APPROVED PLAN SHOWING DELETED FIREPLACE AND ENGINEER TO ADDRESS EXHAUST IN BREAK ROOM TIED INTO EXISTING BUILDING EXHAUST AND NOT TERMINATING THROUGH ROOF AS SHOWN ON PLANS .NEED REVISED APPROVED PLAN DELETING FIREPLACE, GAS, VENT, SHOWING FPB-1 NOT BEING INSTALLED AND USING EXISTING FAN POWER BOX .NEED TO VERIFY IF FPB-2 WAS INSTALLED , LOWER THERMOSTATS TO 48" OFF FLOOR .WAS PVC ISOLATED IN RETURN AIR PLENUM ? ALL TILLS ARE DROPPED NOT ABLE TO SEE ABOVE CEILING . NEED TEST AND BALANCE REPORT. ((CONTRACTOR WILL NEED TO MEET INSPECTOR ON SITE TO REMOVE CEILING TILLS )) | LIDO | LIDO | | H= | P | 5916766 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HSP | P | 07/03/2018 | NEED REVISED APPROVED PLAN DELETING FIREPLACE, GAS, VENT, SHOWING FPB-1 NOT BEING INSTALLED AND USING EXISTING FAN POWER BOX AND EXHAUST FOR BREAK ROOM BEING TIED INTO BUILDING EXHAUST AND NOT THROUGH ROOF AS SHOWN. | DUSTINS | DUSTINS | | HSP | P | 5892098 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 07/02/2018 | NEED REVISED APPROVED PLAN SHOWING DELETED FIREPLACE AND ENGINEER TO ADDRESS EXHAUST IN BREAK ROOM TIED INTO EXISTING BUILDING EXHAUST AND NOT TERMINATING THROUGH ROOF. NEED TO CONSULT WITH SENIOR INSPECTOR ABOUT FPB-1 NOT BEING INSTALLED AND KEEPING EXISTING FAN POWER BOX. NEED TO ISOLATE ALL PVC FROM RETURN AIR PLENUM. NEED TO INSTALL FPB-2, ALL OTHER FAN POWER BOXES AND VAV'S OK. NEED TO SEE THERMOSTATS, INSTALL AT 48" OR NEED TO PUT LOCK BOXES ON. FLEX AND DIFFUSERS OK. FOR FINAL PROVIDE TEST AND BALANCE REPORT. | DUSTINS | DUSTINS | | HD | P | 5891755 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 06/13/2018 | NEED FIREPLACE CONTRACTOR AND GAS CONTRACTOR ATTACHED TO PERMIT. INSTALLING FAN POWER BOX 1? EXISTING IS STILL IN THE CEILING. ISOLATE ALL PVC IN RETURN AIR PLENUM. MEDIUM PRESSURE AND LOW PRESSURE SUPPLY TRUNKS AND LATERALS OK. OK TO WRAP. NO EXHAUST, FAN POWER BOXES OR VAV'S YET. BY FINAL NEED A ROOF INSPECTION. | DUSTINS | DUSTINS | | HD | P | 5873986 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | C | 11/13/2018 | Corrections made, images from contractor uploaded. | DANR | DANR | | P= | C | 6023360 |
PRESTIGE MECHANICAL CONTRACTORS,INC | P= | P | 07/10/2018 | Dishwasher high loop and hammer arrestor, engineer letter for wrapped pvc in plenum, Pictures ok for plenum pipe wrap and dishwasher, rest ok. | DANR | DANR | | P= | P | 5897605 |
PRESTIGE MECHANICAL CONTRACTORS,INC | PTO | C | 06/01/2018 | Test ok. Note: at final check vtr connections - floor below waste connections, need engineer approval letter for wrapped pvc in plenum. | DANR | DANR | | PTO | C | 5861935 |
NIELSEN MECHANICAL CONTRACTORS, INC. | XMS | T | 11/16/2018 | PAID (REC#1557080) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: delta 3 | DALEH | DALEH | | XMS | T | 6027992 |