TRI-STAR MASONRY, INC. | B= | C | 11/01/2019 | Address posted | JEREMYA | JEREMYA | | B= | C | 6386422 |
TRI-STAR MASONRY, INC. | B= | P | 07/01/2019 | missing address / need to complete other final inspections -- Schedule a new Building Final when above items are complete. | BRIANB | BRIANB | | B= | P | 6249593 |
TRI-STAR MASONRY, INC. | BFT | C | 03/13/2019 | Interior pad observation received | RICHB | RICHB | | BFT | C | 6132626 |
TRI-STAR MASONRY, INC. | BSP | P | 02/27/2019 | Bolt & Weld Observation received | RICHB | RICHB | | BSP | P | 6118489 |
TRI-STAR MASONRY, INC. | BFN | C | 02/26/2019 | Foundation wall observations received | RICHB | RICHB | | BFN | C | 6117081 |
TRI-STAR MASONRY, INC. | BBB | C | 02/26/2019 | Bond beam observations received | RICHB | RICHB | | BBB | C | 6117077 |
TRI-STAR MASONRY, INC. | BSP | P | 02/26/2019 | Overex and open hole received - 2200 psf // bond beam observation received | RICHB | RICHB | | BSP | P | 6117073 |
TRI-STAR MASONRY, INC. | BFT | P | 02/26/2019 | Footing observation received - interior pads not observed | RICHB | RICHB | | BFT | P | 6117069 |
TRI-STAR MASONRY, INC. | BFI | P | 05/29/2018 | 2" R-10 vertical OK / discussed third party inspection to complete BFN | RICHB | RICHB | | BFI | P | 5857321 |
TRI-STAR MASONRY, INC. | BFN | R | 05/24/2018 | Concrete placement occurring during inspection - portions of forms already filled on East & South elevations / formwork OK in all areas / reinforcement at wall steps not per plan - diagonals missing (see Detail F on S-2) / OK to use third party for observation / plans reviewed onsite | RICHB | RICHB | | BFN | R | 5855417 |
TRI-STAR MASONRY, INC. | BFT | P | 05/22/2018 | Formwork & reinforcement for continuous footer & integrated pads OK / need to inspect interior pads / need stamped copy of Open Hole / plans reviewed onsite | RICHB | RICHB | | BFT | P | 5852251 |
ELECTRIC TECH INC. | E= | C | 06/27/2019 | all 3 RTU ' s ok all 30 amp fuses at disconnect | CRAIG | CRAIG | | E= | C | 6247341 |
ELECTRIC TECH INC. | ER | R | 06/24/2019 | called in on wrong permit | CRAIG | CRAIG | | ER | R | 6241555 |
ELECTRIC TECH INC. | EP | C | 03/25/2019 | 400 amp 4/w to fed through panel ok | CRAIG | CRAIG | | EP | C | 6143391 |
ELECTRIC TECH INC. | ES | C | 03/25/2019 | Commercial Service: 400 amp 4/w ok to set meter | CRAIG | CRAIG | | ES | C | 6143387 |
AIRTECH MECHANICAL, INC. | H= | C | 07/01/2019 | FINAL FOR MECHANICAL CONTRACTOR ON CORE AND SHELL | BILLS | BILLS | | H= | C | 6249774 |
AIRTECH MECHANICAL, INC. | HD | C | 06/25/2019 | SPLICE ON FILE AND LADDER CORRECTED. | MARKB | MARKB | | HD | C | 6243442 |
DRUMMOND PLUMBING LLC | H= | C | 05/22/2019 | SPLICE FOR RTU'S ON FILE, NO GAS PIPING CHANGES. | MARKB | MARKB | | H= | C | 6207005 |
AIRTECH MECHANICAL, INC. | H= | P | 04/15/2019 | Wrong size RTU'S installed per equipment schedule (80k called for 130k installed). Building ladder lacks required 6" toe spacing at gutter. | MARKB | MARKB | | H= | P | 6166208 |
DRUMMOND PLUMBING LLC | HC | C | 04/12/2019 | RELEASE METER | MARKB | MARKB | | HC | C | 6164385 |
DRUMMOND PLUMBING LLC | HI | C | 04/12/2019 | 10 PSI PRESSURE TEST OK AND PIPING PER PLAN. ALL CONNECTIONS TO ROOFTOP EQUIPMENT COMPLETE. | MARKB | MARKB | | HI | C | 6164369 |
DRUMMOND PLUMBING LLC | P= | C | 05/30/2019 | Correction made, image from contractor uploaded. | DANR | DANR | | P= | C | 6214001 |
DRUMMOND PLUMBING LLC | P= | P | 05/22/2019 | Need 10ft away or 3ft above air intake for floor drain vtr (picture ok), rest ok. | DANR | DANR | | P= | P | 6207135 |
DRUMMOND PLUMBING LLC | PTO | C | 05/22/2019 | Ok. | DANR | DANR | | PTO | C | 6207134 |
DRUMMOND PLUMBING LLC | PTO | R | 02/06/2019 | field cancel | TED | TED | | PTO | R | 6099041 |
DRUMMOND PLUMBING LLC | PB | C | 08/14/2018 | water stub to images | TED | TED | | PB | C | 5932778 |
DRUMMOND PLUMBING LLC | PB | P | 07/11/2018 | deep base ok to cover, water to be run at future date | TED | TED | | PB | P | 5898831 |
DRUMMOND PLUMBING LLC | PB | P | 07/10/2018 | lost test /no test, no water run in | TED | TED | | PB | P | 5897453 |
DRUMMOND PLUMBING LLC | XMS | T | 04/18/2019 | PAID (REC#1600444): PLAN SPLICE FEE: $50 by: SHANEN for Mechanical: Revised gas and schedule | SHANEN | SHANEN | | XMS | T | 6170660 |
TRI-STAR MASONRY, INC. | XBS | T | 03/19/2019 | PAID (REC#1610528): PLAN SPLICE FEE: $50 by: LBENNETT for Construction: added an additional overhead door | LBENNETT | LBENNETT | | XBS | T | 6137120 |
DRUMMOND PLUMBING LLC | XPS | P | 07/26/2018 | PLAN SPLICE FEE: by: DALEH for Plumbing: removed finishes | DALEH | DALEH | | XPS | P | 5915250 |
TRI-STAR MASONRY, INC. | XBS | T | 07/26/2018 | PAID (REC#1559948) PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Delete interior finish and change to Core and Shell | MICHAELA | MICHAELA | | XBS | T | 5915208 |
TRI-STAR MASONRY, INC. | XES | P | 07/26/2018 | PLAN SPLICE: (No Fee) by: BERTHA for Electrical: Removed scope - removed tenant finish - return to core and shell. | BERTHA | BERTHA | | XES | P | 5915168 |